WattNode T-WNB-3Y-208 Скачать руководство пользователя страница 1

WattNode

®

 Pulse Output kWh Transducer Connection Instructions 

For use with HOBO

®

 H21, H22, U30, UX90, UX120, and RX3000 series data loggers, and HOBO data nodes

 

© 2005–2015 Onset Computer Corporation. All rights reserved. Onset, HOBO, HOBOware, and HOBOlink are registered trademarks of 
Onset Computer Corporation. Other products and brand names may be trademarks or registered trademarks of their respective owners. 

10332-M MAN-WATTNODE 

Applies to these WattNode Pulse Output kWh Transducers: 

Onset Part No. 

Configuration / VAC 

Output 

Maximum Pulse Output 

WattNode Part No. 

T-WNB-3Y-208 

Single-phase 120 or 
Wye 208-240 

Pulses representing kWh 

4 Hz 

WNB-3Y-208-P 

T-WNB-3Y-208-P 

Single-phase 120 or 
Wye 208-240 

Pulses representing kWh 

4 Hz 

WNB-3Y-208-P 

option P3

 

T-WNB-3D-240 

Delta 208-240 

Pulses representing kWh 

4 Hz 

WNB-3D-240-P 

T-WNB-3D-480 

Delta (or Wye) 480 

Pulses representing kWh 

4 Hz 

WNB-3D-480-P 

 

 

DANGER!

—HIGH VOLTAGE HAZARD

 

 

Installing transducers in an energized electrical enclosure or on any energized conductor can result in severe injury or death. 
These transducers are for installation by qualified personnel only. To avoid electrical shock, do not perform any installation or 
servicing of these transducers unless you are qualified to do so. Disconnect and lock-out all power sources during installation 
and servicing. Please read transducer user manuals for instructions and use. 
 

 

This document provides instructions on connecting the WattNode Pulse Output 
kWh Transducers listed above to HOBO H21, H22, U30, UX90, UX120, and 
RX3000 series data loggers and to ZW series data nodes. 

Note:

 For information 

on connecting the kWh transducer to the power source and other transducer 
details, refer to the WattNode documentation provided by Continental Control 
Systems. 

Required 

 

Selected WattNode Pulse Output kWh Transducer 

 

Appropriately rated Current Transducer(s) 

 

Smart Sensor-compatible HOBO data logger (H21, H22, U30, or RX3000 series) with: 

o

 

Pulse Input Adapter(s), Onset Part No: S-UCC-M00x

*

 

o

 

HOBOware

®

 software (version 2.2 or higher for H21 or H22, 2.4 or higher for U30), or HOBOlink for 

RX3000 

 

22 AWG twisted pair wire (customer supplied) for UX120 series with HOBOware software, version 3.2.0 or higher 

 

Pulse input-compatible HOBO data node (ZW series) and HOBO data logger (UX90 series) with: 

o

 

Onset Part No: CABLE-2.5-STEREO

*

 

o

 

HOBOware Pro software, version 3.0 or higher for ZW series and HOBOware version 3.3 or higher for UX90 
series 

*

  For monitoring power demand as well as generated power, a second S-UCC-M00x pulse input adapter (for H21, H22, U30 

or RX3000 series) or CABLE-2.5-STEREO (for pulse input-compatible ZW series) is required (at output terminal P2). 

WattNode Pulse Output kWh Transducer Features 

 

The WattNode transducer includes three LEDs—one per phase—for diagnostics and indication of power direction and 

correctly installed CTs. 

 

The WattNode transducer provides bidirectional kWh energy pulses. Positive energy pulses (energy consumed from the 

utility) are output on the P1 and COM terminals and negative energy pulses (energy produced and supplied to the 
utility) are output on the P2 and COM terminals. It can be used for conventional power and energy measurement as 
well as for net metering and PV applications. For monitoring power demand as well as generated power, a second S-

WattNode Pulse Output kWh Transducer 

(Onset Part No. T-WNB-3Y-208-P shown) 

Shop for Data Logging products online at:   

www.

DataLoggerStore

.ca   

1.800.561.8187

Содержание T-WNB-3Y-208

Страница 1: ...kWh transducer to the power source and other transducer details refer to the WattNode documentation provided by Continental Control Systems Required Selected WattNode Pulse Output kWh Transducer Appr...

Страница 2: ...UX120 terminal block to P1 Output P3 P2 P1 COM Customer supplied 22 AWG twisted pair HOBO UX90 001 M Data Logger Output P3 P2 P1 COM White Black Red wire not used CABLE 2 5 STEREO Red wire not used Fi...

Страница 3: ...be used depending on the line to neutral voltage Line to Neutral Voltage WattNode Model 120 VAC WNB 3Y 208 P Single Phase Three Wire This configuration is seen in North American residential and comme...

Страница 4: ...this configuration the WattNode is powered from the A and B phase A and phase B terminals For best accuracy we recommend connecting the WattNode N neutral terminal to earth ground This will not cause...

Страница 5: ...e Models The following table shows the WattNode model that should be used depending on the line to neutral voltage and line to line voltage also called phase to phase voltage Line to Neutral Voltage L...

Страница 6: ...and ground If you see a reading between 0 and 5 VAC that leg is probably grounded The WattNode will correctly measure circuits with a grounded leg but the measured voltage and power for the phase will...

Страница 7: ...d P3 Output P3 P2 P1 COM Connect to pulse port Customer supplied 22 AWG twisted pairs HOBO H21 H22 or U30 Series Data Logger H22 001 shown HOBO UX120 Series Data Logger HOBO ZW Series Wireless Data No...