![WattNode BACnet Скачать руководство пользователя страница 10](http://html1.mh-extra.com/html/wattnode/bacnet/bacnet_reference-manual_3741255010.webp)
10
Installation
Single-Phase Two-Wire with Neutral
This configuration is most often seen in homes and offices. The two conductors are neutral and
line. For these models, the meter is powered from the
N
and
Ø
A
terminals.
Up to three such circuits may be monitored with one meter by also using the
Ø
B
and
Ø
C
inputs.
Figure 2: Single-Phase Two-Wire Connection
Recommended WattNode Models
The following table shows the WattNode models that should be used, depending on the line to
neutral voltage.
Line to Neutral Voltage
WattNode Model
120 Vac
WNC-3Y-208-BN
230 Vac
WNC-3Y-400-BN
277 Vac
WNC-3Y-480-BN