When installed in a pipeline, continuous flow past the sensing bulb must be maintained to obtain continuous 

temperature signal to the regulator.  If the flow stops, the pipeline may cool or warm to local room temperature 

causing false reactions from the regulating valve.  On some systems this may require a small by-pass flow line around 

the valve to maintain representative system temperatures at the sensing bulb. 

 

Sensing Bulb Installation  

To install a union connected sensing bulb, remove the union hub or Thermowell from the sensing bulb and install this 

hub or Thermowell into the process piping or tank.  If using a Thermowell, liberally coat the sensing bulb with the 

heat transfer paste supplied with the Thermowell.  Now slip the sensing bulb through the hub or into the well until 

fully seated.  Tighten the coupling nut.  Do not over tighten. 

 

Never attempt to tighten, loosen or otherwise rotate the hub or Thermowell. 

This will prevent twisting and kinking of the connecting tubing thus preventing premature failure. 

 

Keep all bends in the tubing greater than 1-½” radius.  Do not subject the tubing to repeated flexing, vibration, heat, 

cutting, kinking or other abuse.  Coil all excess tubing and place in a cool location.  If motion or vibration may occur, 

secure the tubing to the bulb mounting so all moves as one.  If vibration or fluid pulsations may be transmitted to the 

bulb, it must be housed in a Thermowell for protection from fatigue. 

 

Placing The Regulator Into Operation And Setting The Control Point 

Using the supplied ¼” rod, turn the 1-¾” adjusting screw to a position on the “0 to 8” reference scale that 

approximately corresponds to the relative position of the desired control point within the adjustable range.  The “V” 

slot in the adjusting screw is intended as the index line for recording the setting number in maintenance logs.  To 

raise the control point, turn the adjusting screw from left to right up toward “HIGH” marked on the reference scale.  

To lower the control point, turn the adjusting screw from right to left down toward “LOW” marked on the reference 

scale.  This adjustment must be done at system operation pressure to balance the stem thrust load for 

proper regulation. (Refer to fig. 1 below) 

 

DO NOT TURN THE SMALL HEX STEM JAM NUTS 

This is a critical setting for the proper seating & stroke of the Regulator 

CAUTION:  DO NOT TURN THE SCREW BELOW THE “0” MARK 

 

Figure 1 

 

 

When the downstream units are ready to receive flow, close the by-pass valve and open all upstream supply valves 

slowly to allow gradual start-up. 

Содержание W91 Series

Страница 1: ...2440300 Rev A Page 83 Series W91 94 Self Operating Temperature Regulator Installation Operation Maintenance Instructions...

Страница 2: ...n 6 Repairing Valve Body Assembly 7 Reversing the Valve Action 9 3 Way Regulator Installation Maintenance 10 Typical Applications 12 13 Heat Exchanger Application Using a Self Op 2 Way Valve Heat Exch...

Страница 3: ...MA Valve bodies in through 2 sizes are rated for 250 PSIG max Valve bodies in 2 through 4 sizes are rated for 125 PSIG max Maximum Pressure Drop through the Valve The Pressure Drop is the change in pr...

Страница 4: ...n tailpieces of unions on piping first and then tighten both valve union nuts simultaneously Positioning the Indicator The Model W91 94 Self Operating Regulator contains an intergral dial thermometer...

Страница 5: ...abuse Coil all excess tubing and place in a cool location If motion or vibration may occur secure the tubing to the bulb mounting so all moves as one If vibration or fluid pulsations may be transmitte...

Страница 6: ...acking seal is self adjustable See fig 2 below Fig 2 Do not tighten the packing nut beyond finger tight Leakage should never be tolerated Any leak at bonnets unions plugs etc requires immediate correc...

Страница 7: ...t V rings and flat side out e Packing nut 10 Tighten packing nut all the way down onto the bonnet to push all rings down into the stuffing box and to obtain proper spring load on the assembled rings T...

Страница 8: ...eventing the valve from closing Disassembly of the valve may be required See section on Reversing Valve Action b If debris is successfully removed and valve reassembled repeat step 2 c If no motion is...

Страница 9: ...cially cool with ice if necessary 3 Record the current actuator adjusting screw setting relative to the reference scale 4 Turn the actuator adjusting screw in up to reference number 8 5 Place valve st...

Страница 10: ...o hold the valve body remove both the bonnet and the bottom plug from the valve body See Figure 7 Never use a wrench or vise on the bronze body 5 Look into the valve body on the side the valve plug wa...

Страница 11: ...Replacing Valve Stem Packing 14 Install the bottom plug using a suitable thread compound 15 Replace the locknuts and reassemble the valve to the actuator See Replacing the Valve Body Assembly 3 WAY R...

Страница 12: ...sizes flanged ends E G F MIXING FLOW DIAGRAM TEMPERATURE COLD B C CLOSED A TEMPERATURE SET POINT B A C TEMPERATURE HOT B A C CLOSED DIVERTING FLOW DIAGRAM TEMPERATURE COLD B C CLOSED A TEMPERATURE SET...

Страница 13: ...to OPEN Valve WATER INLET STEAM OR WATER RETURN Influence Side Process Side FROM PROCESS RETURN TO PROCESS HEAT EXCHANGER HEATING Connect Upper Port C to Water Glycol Return and Lower Port B To Heat E...

Страница 14: ...Operating Regulator W91 with In to Close Valve STEAM INLET FUEL OIL STORAGE TANK PUMP HEAT EXCHANGER Process Side Influence Side STEAM RETURN TO TRAP THEN BOILER Sensor installed into pipe line using...

Страница 15: ...agitation 3 Tube system assembly has lost pressure fill 3 Replace the thermal actuator 4 Stem adjustment too small 4 Readjust Closes with temperature increase 5 Foreign material under seats holding va...

Страница 16: ...ure 6 Heat exchanger not large enough 6 Replace with proper capacity 7 Faulty steam trap 7 Install trap of proper capacity 8 Heat exchanger not large enough 8 Replace with proper capacity Opens with t...

Отзывы: