background image

15 

 

TROUBLE SHOOTING GUIDE 

 

PROBLEM: TEMPERATURE REMAINS BELOW THE DESIRED CONTROL POINT 

 

     CAUSES   

 

 

 

          CORRECTIONS 

1.

 

Adjusting setting too low. 

1.   Raise setting. 

2.

 

Bulb at hot location. 

2.   Relocate bulb to more representative 

average temperature location or add agitation. 

3.

 

Stem adjustment too long. 

3.

 

Readjust. 

 

(Closes with temperature increase) 

 

 

4.

 

Valve size too small. 

4.   Replace valve with larger size. 

5.

 

Valve inlet pressure too low. 

5.

 

Increase supply pressure. 

6.

 

Heat exchanger not large enough. 

6.

 

 Replace with proper capacity. 

7.

 

Faulty steam trap. 

7.

 

Install trap of proper capacity. 

8.

 

Heat exchanger not large enough. 

8.

 

Replace with proper capacity. 

 

(Opens with temperature increase) 

 

 

9.

 

Foreign material under seats holding the 

valve seat open. 

9.

 

Heat the bulb to open the valve and allow 

it to open further. 

10.

 

Erosion of seats with resulting high 

leakage. 

10.

 

Repair or replace valve body assembly. 

11.

 

Pressure drop across the valve is too high. 

11. Reduce pressure drop or replace single 

seated valve with double seated. 

12.

 

Stem moves into body to close valve. 

 

12.Change to stem moves into body to open  

valve. 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание W91 Series

Страница 1: ...2440300 Rev A Page 83 Series W91 94 Self Operating Temperature Regulator Installation Operation Maintenance Instructions...

Страница 2: ...n 6 Repairing Valve Body Assembly 7 Reversing the Valve Action 9 3 Way Regulator Installation Maintenance 10 Typical Applications 12 13 Heat Exchanger Application Using a Self Op 2 Way Valve Heat Exch...

Страница 3: ...MA Valve bodies in through 2 sizes are rated for 250 PSIG max Valve bodies in 2 through 4 sizes are rated for 125 PSIG max Maximum Pressure Drop through the Valve The Pressure Drop is the change in pr...

Страница 4: ...n tailpieces of unions on piping first and then tighten both valve union nuts simultaneously Positioning the Indicator The Model W91 94 Self Operating Regulator contains an intergral dial thermometer...

Страница 5: ...abuse Coil all excess tubing and place in a cool location If motion or vibration may occur secure the tubing to the bulb mounting so all moves as one If vibration or fluid pulsations may be transmitte...

Страница 6: ...acking seal is self adjustable See fig 2 below Fig 2 Do not tighten the packing nut beyond finger tight Leakage should never be tolerated Any leak at bonnets unions plugs etc requires immediate correc...

Страница 7: ...t V rings and flat side out e Packing nut 10 Tighten packing nut all the way down onto the bonnet to push all rings down into the stuffing box and to obtain proper spring load on the assembled rings T...

Страница 8: ...eventing the valve from closing Disassembly of the valve may be required See section on Reversing Valve Action b If debris is successfully removed and valve reassembled repeat step 2 c If no motion is...

Страница 9: ...cially cool with ice if necessary 3 Record the current actuator adjusting screw setting relative to the reference scale 4 Turn the actuator adjusting screw in up to reference number 8 5 Place valve st...

Страница 10: ...o hold the valve body remove both the bonnet and the bottom plug from the valve body See Figure 7 Never use a wrench or vise on the bronze body 5 Look into the valve body on the side the valve plug wa...

Страница 11: ...Replacing Valve Stem Packing 14 Install the bottom plug using a suitable thread compound 15 Replace the locknuts and reassemble the valve to the actuator See Replacing the Valve Body Assembly 3 WAY R...

Страница 12: ...sizes flanged ends E G F MIXING FLOW DIAGRAM TEMPERATURE COLD B C CLOSED A TEMPERATURE SET POINT B A C TEMPERATURE HOT B A C CLOSED DIVERTING FLOW DIAGRAM TEMPERATURE COLD B C CLOSED A TEMPERATURE SET...

Страница 13: ...to OPEN Valve WATER INLET STEAM OR WATER RETURN Influence Side Process Side FROM PROCESS RETURN TO PROCESS HEAT EXCHANGER HEATING Connect Upper Port C to Water Glycol Return and Lower Port B To Heat E...

Страница 14: ...Operating Regulator W91 with In to Close Valve STEAM INLET FUEL OIL STORAGE TANK PUMP HEAT EXCHANGER Process Side Influence Side STEAM RETURN TO TRAP THEN BOILER Sensor installed into pipe line using...

Страница 15: ...agitation 3 Tube system assembly has lost pressure fill 3 Replace the thermal actuator 4 Stem adjustment too small 4 Readjust Closes with temperature increase 5 Foreign material under seats holding va...

Страница 16: ...ure 6 Heat exchanger not large enough 6 Replace with proper capacity 7 Faulty steam trap 7 Install trap of proper capacity 8 Heat exchanger not large enough 8 Replace with proper capacity Opens with t...

Отзывы: