Wa t l o w S e r i e s F 4 P
P a r a m e t e r s
■
6 . 2 9
✔
Note: For more information about how parameter settings
affect the controller’s operation, see the Features Chapter.
*The tenth digit of your model number,
F4PX-XXXX-X
X
XX
,
determines what RTD calibration resistance values the unit
uses. Refer to the Ordering Information in the Appendix.
Options 1-4, 100
Ω
RTD - 15.00 and 380.00
Ω
Options 5-8, 500
Ω
or 1000
Ω
RTD - 240.00 and 6080.00
Ω
Factory Page Parameter Table
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
(I/O, Set)
Parameters to Appear
Active: Always.
Inputs 2 and 3 appear only if the
controller is the enhanced ver-
sion (F4P _ - _ _ AB - _ _ _ _).
1603 [1]
1608
[2]
1613
[3]
r/w
Yes (7)
380.0 Ohms*
Store 380.00
Ω
calibration
for input RTD.
Active: Always.
Input
1603 [1]
1608 [2]
1613 [3]
w
Yes (6)
240.0 Ohms*
Store 240.00
Ω
calibration
for the 500
Ω
or 1k
Ω
RTD
input.
Active: Always.
Inputs 2 and 3 appear only if the
controller is the enhanced ver-
sion (F4P _ - _ _ AB - _ _ _ _).
1603 [1]
1608
[2]
1613
[3]
r/w
Yes (6)
15.0 Ohms*
Store 15.00
Ω
calibration
for input RTD.
Active: Always.
Inputs 2 and 3 appear only if the
controller is the enhanced ver-
sion (F4P _ - _ _ AB - _ _ _ _).
1603 [1]
1608
[2]
1613
[3]
r/w
Yes (5)
Lead
Store calibration for lead
resistance.
Active: Always.
Inputs 2 and 3 appear only if the
controller is the enhanced ver-
sion (F4P _ - _ _ AB - _ _ _ _).
1603 [1]
1608
[2]
1613
[3]
r/w
Yes (4)
Ground
Store calibration for
ground at gains of 1 and
32.
Active: Always.
Inputs 2 and 3 appear only if the
controller is the enhanced ver-
sion (F4P _ - _ _ AB - _ _ _ _).
1603 [1]
1608
[2]
1613
[3]
r/w
Yes (3)
32°F Type J
Store 32°F type J calibra-
tion.
Active: Always.
Inputs 2 and 3 appear only if the
controller is the enhanced ver-
sion (F4P _ - _ _ AB - _ _ _ _).
1603 [1]
1608
[2]
1613
[3]
r/w
Yes (2)
50.00mV Thermocouple
Store 50.000mV calibra-
tion for input thermocou-
ple.
Active: Always.
Inputs 2 and 3 appear only if the
controller is the enhanced ver-
sion (F4P _ - _ _ AB - _ _ _ _).
1603 [1]
1608
[2]
1613
[3]
r/w
Yes (1)
0.00mV Thermocouple
Store 0.000mV calibra-
tion for input thermocou-
ple.
Main Page > Factory > Calibration > Calibrate Input x (1 to 3)
Calibrate Input x (1 to 3)
Active: Always.
1602 r
Yes (800)
Full Defaults
Causes all parameter
values to revert to their
factory default settings.
Active: Always.
1513 w
(1)
Display Test
Checks LED display seg-
ments by turning them
on and off.
Содержание F4P Series
Страница 4: ...ii Table of Contents Watlow Series F4P Notes...
Страница 14: ...2 8 Operating from the Front Panel Watlow Series F4P Notes...
Страница 58: ...6 32 Parameters Watlow Series F4P Notes...
Страница 77: ...Watlow Series F4P Features 7 19 Notes...
Страница 78: ...7 20 Features Watlow Series F4P Notes...
Страница 94: ...8 16 Installation and Wiring Watlow Series F4P Notes...
Страница 108: ...Notes 9 14 Communications Watlow Series F4P...