6 . 1 8
■
P a r a m e t e r s
Wa t l o w S e r i e s F 4 P
* Note: Digital inputs are edge triggered and require a transition from a
high to low or low to high state.
✔
Note: Press the Information Key
ˆ
for more task-related tips.
Setup Page Parameter Table
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
(I/O, Set)
Parameters to Appear
Setup Page Parameter Table
Modbus
Register
Range
read/write
Conditions for
Parameter
Description
(Modbus Value)
Default
(I/O, Set)
Parameters to Appear
Active if Boost Type is set to Set
Point.
882
r/w
Process
Process (0)
Deviation (1)
Boost Set Point Type (1B)
Select which type of set
point will control output
1B.
Active if Boost Type is set to
Power.
881
r/w
Boost Auto
Auto Only (0)
Auto/Manual (1)
Boost Power Mode (1B)
Select whether boost
power operates in Manu-
al Mode.
Active if the control output func-
tions are both set to heat or
cool.
885 r/w
Power
Boost on Power (0)
Boost on Set Point (1)
Boost Type (1B)
Select what will activate
control output 1B.
Active: Always.
Output
715
[1A]
732
[1B]
r/w
0%
0% to High Limit -1
( )
Low Power Limit
Set low limit control
(PID mode only) output
power level.
Active: Always.
Output
714
[1A]
731
[1B]
r/w
100%
Low Limit +1 to 100%
( )
High Power Limit
Set high limit control
(PID mode only) output
power level.
Active if output 1A is a process
output.
844
r/w
Off
Off (0)
On (1)
Duplex (1A)
Control both heat and
cool from one output.
Active if the controller is
equipped with a process output.
Output
701
[1A]
718
[1B]
r/w
4 to 20mA
4 to 20mA (0)
0 to 20mA (1)
0 to 5V (2)
1 to 5V (3)
0 to 10V (4)
20 to 4mA (5) [reverse
value]
Process
Set process output type.
Active if Cycle Time Type is set
to Fixed Time.
Output
506
[1A]
556
[1B]
1 second
0.1 to 60 seconds
(1 to 600) in tenths
Cycle Time Value
Select the cycle time pe-
riod.
Active if output x is not a me-
chanical relay or process out-
put.
Output
509
[1A]
559
[1B]
r/w
Fixed Time
Variable Burst (0)
Fixed Time (1)
Cycle Time Type
Select the time base.
Active: Always.
Output
700
[1A]
717
[1B]
r/w
Heat (1A)
Off (1B)
Off (0) [1B only]
Heat (1) [reverse]
Cool (2) [direct]
Function
Select type of function
for output.
Main > Setup > Control Output x (1A and 1B)
Control Output x (1A and 1B)
Active: Always.
Input
1061 [1]
1063 [2]
1065 [3]
1067 [4]
r/w
Low
Low (0)
High (1)
Condition*
Select the condition to
trigger digital input.
Содержание F4P Series
Страница 4: ...ii Table of Contents Watlow Series F4P Notes...
Страница 14: ...2 8 Operating from the Front Panel Watlow Series F4P Notes...
Страница 58: ...6 32 Parameters Watlow Series F4P Notes...
Страница 77: ...Watlow Series F4P Features 7 19 Notes...
Страница 78: ...7 20 Features Watlow Series F4P Notes...
Страница 94: ...8 16 Installation and Wiring Watlow Series F4P Notes...
Страница 108: ...Notes 9 14 Communications Watlow Series F4P...