Proportional Control

Some processes need to maintain a temperature or 
process value closer to the set point than on-off con-
trol can provide. Proportional control provides closer 
control by adjusting the output when the temperature 
or process value is within a proportional band. When 
the value is in the band, the controller adjusts the out-
put based on how close the process value is to the set 
point. 

The closer the process value is to the set point, the 

lower the output power. This is similar to backing off 
on the gas pedal of a car as you approach a stop sign. 
It keeps the temperature or process value from swing-
ing as widely as it would with simple on-off control. 
However, when the system settles down, the tempera-
ture or process value tends to “droop” short of the set 
point.

With proportional control the output power level 

equals (set point minus process value) divided by the 
proportional band value.

Adjust the proportional band with Proportional  

[`Pb]

.

Time

Temperature

Proportional Control

Set Point

Proportional Band

Droop

Overshoot

Proportional plus Integral (PI) Control

The droop caused by proportional control can be cor-
rected by adding integral control. When the system 
settles down, the integral value is tuned to bring the 
temperature or process value closer to the set point. 
Integral determines the speed of the correction, but 
this may increase the overshoot at startup or when 
the set point is changed. Too much integral action will 
make the system unstable. Integral is cleared when 
the process value is outside of the proportional band.

Integral 

[Int]

 is measured in minutes per repeat. A 

low integral value causes a fast integrating action.

Proportional plus Integral plus Derivative (PID) 
Control

Use derivative control to minimize the overshoot in 
a PI-controlled system. Derivative 

[dEu]

 adjusts the 

output based on the rate of change in the temperature 
or process value. Too much derivative will make the 
system sluggish.

Time

Temperature

PID Control

Set Point

Reduced Overshoot

Proportional Band

Proportional Band x 2

Heating Slows

On-Off Control

On-off control switches the output either full on or full 
off, depending on the input, set point and hysteresis 
values. The hysteresis value indicates the amount the 
process value must deviate from the set point to turn on 
the output. Increasing the value decreases the number 
of times the output will cycle. Decreasing hysteresis im-
proves controllability. With hysteresis set to the lowest 
value of 3

°

C or 5

°

F, the process value would stay closer 

to the set point, but the output would switch on and off 
more frequently, and may result in the output “ chatter-
ing.” Both the control mode (

[Cnt]

 prompt) and hyster-

esis (

[Hys]

 prompt) values can be changed either using 

the front panel or via Modbus communications. 

Set Point

Time

Temperature

The heating action switches off when the process 

temperature rises above the set point.

The heating action

switches on at startup.

Hysteresis

Process Temperature

On/Off System Cycles

The heating action switches on when the process temperature 

drops below the set point minus the hysteresis.

Mounting the Series EHG CL

88.8 mm

(3.496 in)

55.8 mm

(2.196 in)

Base Controlller

front

48.4 mm

(1.907 in)

Base Controller

side

Содержание EHG CLseries

Страница 1: ...erature controller and safety limit Process temperature output 10 amp NO ARC relay Safety limit 10 amp relay On off and PID temperature control algorithm Up graded via communications to PID algorithm...

Страница 2: ...to 0 C 32 F to SLA setting 150 C 302 F 34 unsigned integer RWE No Dis play Heat Output Power Read via Modbus communications the present heat output power level 0 to 100 0 22 unsigned integer R No Dis...

Страница 3: ...19 200 16 384 38 400 17 9 600 16 unsigned integer RWE tU tU Temperature Units Select the temperature scale F F 4 C C 5 C 17 unsigned integer RWE rpp rPP Restore Programmed Parameters Restore factory...

Страница 4: ...on on off off Ambient Alarm Abt 85 C on on off off Health Check Error Normal Operating Range Limit High Set Point SLA Closed Loop Set Point Closed Loop Set Point Temperature Alarm Hysteresis Alarm Hys...

Страница 5: ...1 507 494 5656 E12 CPU Clock Error Clock frequency is 5 MHz or 13 1 MHz Contact Technical Support at 1 507 494 5656 E13 Stack Over ow Stack has over owed Contact Technical Support at 1 507 494 5656 E1...

Страница 6: ...l is cleared when the process value is outside of the proportional band Integral Int is measured in minutes per repeat A low integral value causes a fast integrating action Proportional plus Integral...

Страница 7: ...r 4800 0021 With the control facing you this connector is on the right side L1 Switched black L2 white yellow red yellow red 1 3 4 5 7 8 6 2 Heater Limit Thermocouple Process Thermo couple Thermocoupl...

Страница 8: ...parts which upon examination prove to be defective within the warranty period specified This warranty does not apply to damage resulting from transportation alteration misuse or abuse WARNING To avoi...

Страница 9: ...nity EN 61000 4 4 2011 Electrical Fast Transient Burst Immunity EN 61000 4 5 2006 Surge Immunity EN 61000 4 6 2008 Conducted Immunity EN 61000 4 8 2009 Power frequency magnetic field immunity EN 61000...

Страница 10: ...ebsite www watlow co uk From outside The United Kingdom Tel 44 115 964 0777 Fax 44 115 964 0071 Asia and Paci c Watlow Singapore Pte Ltd 16 Ayer Rajah Crescent 06 03 04 Singapore 139965 Tel 65 6773 94...

Отзывы: