D8 Series User’s Guide
Chapter 2: Installation
39
External
Switching
Device
TB50
Input
Control Com
Figure 2.23
– Wiring Digital Inputs
Functions Activated by Digital Inputs
Use digital inputs to activate the following functions:
• Load a job that is stored in controller memory. See BCD Job Load on page 100.
• Change all loops to manual mode at specified output levels. See Mode Override on page
• Enable thermocouple short detection. See Thermocouple Short Alarm on page 104.
• Restore automatic control after a failed sensor has been repaired. See Restore Automatic
TB18 Connections
Table 2.7
–
TB18 Connections
TERMINAL
FUNCTION
CONTROL OUTPUT
1
4-LOOP MODEL
8-LOOP MOEL
1
+5VDC
2
CTRL COM
3
Watchdog timer
4
Global alarm
5
Output 1
Loop 1 heat
Loop 1 heat
6
Output 2
Loop 2 heat
Loop 2 heat
7
Output 3
Loop 3 heat
Loop 3 heat
8
Output 4
Loop 4 heat
Loop 4 heat
9
Output 5
Loop 1 cool
Loop 5 heat
10
Output 6
Loop 2 cool
Loop 6 heat
11
Output 7
Loop 3 cool
Loop 7 heat
12
Output 8
Loop 4 cool
Loop 8 heat
13
Output 9
Loop 1 cool
14
Output 10
Loop 2 cool
15
Output 18
2
Serial DAC clock
Serial DAC clock
16
Input 1
17
Input 2
18
Input 3