CLS200 Series User’s Guide
Chapter 8: Troubleshooting and Reconfiguring
153
slot unlatches and the battery holder comes off the module.
5. Remove the battery from the holder.
6. Follow local applicable recycling requirements for Coin Cell Lithium type BR-1632 Battery.
Figure 8.7
— Battery-Backed RAM Module on the Processor Board
To replace the battery, if desired:
1. Align the contact springs on the battery holder with the contacts on the RAM module.
2. Hook the battery holder flange under the RAM module’s base board.
3. Fit the alignment ribs on the battery holder into the alignment notches in the RAM module’s
base board.
4. Push down and forward and latch the battery holder on the module.
5. To reassemble the unit reverse steps 3 through 7 of the procedure
. However, at step 6 insert the two-board assembly straight in to the carrier making
sure all four arms latch on the boards.
6. Power up the controller.
7. Re-enter the controller settings, if necessary.
Changing Communications
To switch between EIA/TIA-232 and EIA/TIA-485, change the jumpers as shown in
Figure 8.8
.
JU1
JU2
JU3
JU4
JU5
A B
A B
A B
Configured for
EIA/TIA-232
Configured for
EIA/TIA-485
Last controller in
system configured
for EIA/TIA-485
Figure 8.8
— Jumper Configurations
You will need tweezers and a Phillips head screwdriver to switch between EIA/TIA-232 and