Chapter 4: Troubleshooting
PPC-2000 User’s Guide
154
Watlow Anafaze
Doc.# 30002-00 Rev 2.3
Troubleshooting and Corrective Actions
If the system fails to perform as expected, it may be necessary
to perform one or more of the following procedures to discover
the cause and restore normal operation.
Digital Inputs and Outputs
If a digital input or output doesn’t seem to be working, check
the following:
•
Is the digital I/O point’s
Direction
set correctly as an input
or output? See
•
Is the
Logic
•
Is the output selected as an Output Destination for more
than one function (e.g. a control output and an alarm
output)? See
.
•
Is the digital I/O point associated with a variable set as an
output in a logic program? Refer to the
LogicPro User’s
Guide
.
•
Are the cable and wiring connections correct? See
Connecting I/O to the PPC-2010 on page 37, Connecting to
the Relay Outputs on the PPC-206x on page 70
Connecting Digital Inputs to the PPC-207x on page 74
.
•
Is leakage current from one of the configurable I/O points
such that a device is being switched on or partly on? See
Connecting Digital Outputs on page 41
.
•
Is the field I/O device powered? Note digital outputs on the
PPC-2010 and PPC-2040 sink current. That current must
be sourced by an external device that is referenced to the
PPC’s common. See
Connecting Digital Outputs on page 41
Connecting Digital Outputs on page
for the PPC-2040.
Process Variable
If the Process Variable is not updating, check the following:
•
Is a valid analog input selected as the
PV Source
? See
.
•
Is the input corresponding to the
PV Source
updating as
expected? If not check LEDs on the associated module, See
corresponding module section in this chapter.
•
Is the input wiring correct? See
PPC-2010 on page 37, Connecting Analog Inputs to the
PPC-2021 — 2025 on page 45, Connecting Encoders and
Analog Outputs to the PPC-2030 on page 55, or Connecting
to the Relay Outputs on the PPC-206x on page 70
Содержание Anafaze PPC-2000
Страница 2: ......
Страница 14: ...Table of Contents PPC 2000 User s Guide viii Watlow Anafaze Doc 30002 00 Rev 2 3...
Страница 24: ...List of Tables PPC User s Guide xviii Watlow Anafaze Doc 30002 00 Rev 2 3...
Страница 36: ...Chapter 1 Overview PPC 2000 User s Guide 12 Watlow Anafaze Doc 30002 00 Rev 2 3...
Страница 112: ...Chapter 2 Hardware Installation PPC 2000 User s Guide 88 Watlow Anafaze Doc 30002 00 Rev 2 3...
Страница 184: ...Chapter 4 Troubleshooting PPC 2000 User s Guide 158 Watlow Anafaze Doc 30002 00 Rev 2 3...
Страница 296: ...Chapter 7 Specifications PPC 2000 User s Guide 268 Watlow Anafaze Doc 30002 00 Rev 2 3...
Страница 310: ...Appendix A Modbus Protocol PPC 2000 User s Guide 282 Watlow Anafaze Doc 30002 00 Rev 2 3...
Страница 311: ...Doc 30002 00 Rev 2 3 Watlow Anafaze 283 B Appendix B Declaration of Conformity...
Страница 319: ...PPC 2000 User s Guide Glossary Doc 30002 00 Rev 2 3 Watlow Anafaze 291...
Страница 320: ...Glossary PPC 2000 User s Guide 292 Watlow Anafaze Doc 30002 00 Rev 2 3...