plug. If leak persists, remove heating unit and  add  teflon tape or sealing compound to threads and re-install. 
Care should be taken to observe the orientation of the flange or plug to its original position. 

 Troubleshooting

 

PROBLEM 

Cause / Correction 

 

No power available to heater 

Check disconnect switch to ensure it is in the "ON" position 

 and that fuses are not blown. Replace fuses if they are blown 
 

Fuses blowing 

Check heater electrical rating. Applied voltage may be wrong 

 Check fuse rating. Fuses should be at least 25% more than full  
 load amperage. 
 Disconnect heater power source. Check the heater resistance  
 to ground. This should be no less than 1 Megohm. Refer to  
 Megohm checking. 
 

Not enough power 

Check line voltage to ensure it is within specification 

 Check full line current if voltage is correct. If line current is lower, 
 the heater may be wired wrong or has open elements 
 

Fluid not heating to desired  

Not enough Kw 

temperature 

Too much heat loss 

   

High limit tripping / alarm 

Not enough fluid flow 

 Too much Kw 
 Line voltage higher than designed / allowable 

 

 Preventative Maintenance

 

CAUTION: HAZARD OF ELECTRIC SHOCK. TURN ALL POWER TO HEATER OFF, USE 
APPROPRIATE DISCONNECT LOCKOUTS AND ALLOW SYSTEM/HEATER TO COOL BEFORE 
PERFORMING ANY MAINTENANCE 

!

 

 

Check line connections to make sure they are tight, free of oxide build-up, and that no dust or dirt build-up is 
present. Retighten to 20 in-lbs as necessary. 
 
Check enclosure (inside) for rust, dirt or dust. Remove rust if present, with steel wool (or equal) and 
thoroughly blow clean with dry, oil-free air. 
 
If enclosure is moisture resistant, check condition of cover gasket. A replacement can be obtained from the 
factory. 
 
Liquid immersed units should be removed from tank and checked periodically for scale build-up. Clean as 
required.  Scale can cause high sheath temperature and result in inefficiency and shortened life. 

When the 

heater is removed or tightened, take care to orient the heater in the position it was originally 
oriented. 
 

 Replacement Parts

 

Reference the Circulation heater part number on the nameplate when ordering replacement parts. 
Recommended spare parts would be : an immersion heater, flange gasket, and thermostat (if supplied). 
 

Содержание WATROD 316-42-5-1

Страница 1: ...ibility of moisture absorption by the insulation material within the element is possible To ensure proper megohm values a minimum 500 VDC megohm meter Megger should be used to ensure that the megohm r...

Страница 2: ...from itself as under normal operating conditions Consult your local authorized sales representative for specific recommendations for your application 3 Terminal Enclosures Terminal enclosures should...

Страница 3: ...ions care should be taken to avoid supporting the tank by the nozzles Mounting blocks are provided to help prevent this Provisions for thermal expansion and contraction should be considered slotted bo...

Страница 4: ...le the bottom nut is supported Ground connection color coded green is supplied inside the housing for ground wire Line voltage must be equal to or less than rating stamped on the heater assembly Some...

Страница 5: ...rent if voltage is correct If line current is lower the heater may be wired wrong or has open elements Fluid not heating to desired Not enough Kw temperature Too much heat loss High limit tripping ala...

Страница 6: ...han this warranty Watlow is not liable for incidental or consequential damages resulting from use of the product whether a claim for such damages is based upon warranty contract negligence or other fa...

Страница 7: ..._________________________________________________________________________________________________________________________________________________________________________________ WATLOW IND n 6 INDUSTR...

Отзывы: