Watlow EZ-ZONE
®
PM Integrated Controller
•
74
•
Chapter 6 Setup Page
Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus Rela-
tive
Address
CIP
Class
Instance
Attribute
hex (dec)
Pro-
fibus
Index
Param-
eter ID
Data
Type
&
Read/
Write
[iP;10]
[ip.10]
Linearization (1 to 2)
Input Point 10
Set the value that will be
mapped to output 10.
-1,999.000 to 9,999.000
9.0
Instance 1
Map 1 Map 2
- - - -
3592
Instance 2
Map 1 Map 2
- - - -
3662
0x86 (134)
1 to 2
0x11 (17)
175
34017 float
RWES
[oP;10]
[op.10]
Linearization (1 to 2)
Output Point 10
Set the value that will be
mapped to input 10.
-1,999.000 to 9,999.000
9.0
Instance 1
Map 1 Map 2
- - - -
3612
Instance 2
Map 1 Map 2
- - - -
3682
0x86 (134)
1 to 2
0x1B (27)
176
34027 float
RWES
[``Pu]
[`Set]
Process Value Menu
[``Fn]
[ Fn]
Process Value (1 to 2)
Function
Set the function that will
be applied to the source
or sources.
Note:
Differential and Ratio not
available using instance 2.
[`oFF]
Off (62)
[usla]
Vaisala RH Compen-
sation (1648)
[`W;b]
Wet Bulb/Dry Bulb
(1369)
[`S;bA]
Sensor Backup (1201)
[rAti]
Ratio (1374)
[diFF]
Differential (1373)
[root]
Square Root (1380)
[`alt]
**Pressure to Altitude
(1649)
Off
Instance 1
Map 1 Map 2
- - - -
3320
Instance 2
Map 1 Map 2
- - - -
3390
0x7E (126)
1 to 2
0x15 (21)
123
26021 uint
RWES
[p;unt]
[P.unt]
Process Value (1 to 2)
Pressure Units**
Set the units that will be
applied to the source.
[`psi]
Pounds per Square
Inch (1671)
[pasc]
Pascal (1674)
[atm]
Atmosphere (1675)
[mbr]
Millibar (1672)
[torr]
Torr (1673)
PSI
Instance 1
Map 1 Map 2
- - - -
3334
Instance 2
Map 1 Map 2
- - - -
3404
0x7E (126)
1 to 2
0x1C (28)
- - - -
26028 uint
RWES
[a;unt]
[A.unt]
Process Value (1 to 2)
Altitude Units**
Set the units that will be
applied to the source.
[`Hft]
Kilofeet (1677)
[``ft]
Feet (1676)
HFt
Instance 1
Map 1 Map 2
- - - -
3336
Instance 2
Map 1 Map 2
- - - -
3406
0x7E (126)
1 to 2
0x1D (29)
- - - -
26029 uint
RWES
[`b;pr]
[ b.Pr]
Process Value (1 to 2)
Barometric Pressure**
Set the units that will be
applied to the source.
10.0 to 16.0
14.7
Instance 1
Map 1 Map 2
- - - -
3338
Instance 2
Map 1 Map 2
- - - -
3408
0x7E (126)
1 to 2
0x1E (30)
- - - -
26030 float
RWES
[`Fil]
[ FiL]
Process Value (1 to 2)
Filter
Filtering smooths out
the output signal of this
function block. Increase
the time to increase fil-
tering.
0.0 to 60.0 seconds
0.0
Instance 1
Map 1 Map 2
- - - -
3330
Instance 2
Map 1 Map 2
- - - -
3400
0x7E (126)
1 to 2
0x1A (26)
- - - -
26026 float
RWES
Note:
Some values will be rounded off to fit in the four-character display. Full values can be read
with other interfaces.
R: Read
W: Write
E:
EEPROM
S:
User
Set
** Pressure Altitude calculation is based on the International Standard Atmosphere 1976