Watlow EZ-ZONE
®
PM Integrated Controller
•
57
•
Chapter 5 Operations Page
Operations Page
Dis-
play
Parameter name
Description
Range
Default
Modbus
Relative Ad-
dress
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Param-
eter ID
Data
Type
& Read/
Write
[LiM]
[oPEr]
Limit Menu
[`LL;S]
[ LL.S]
Limit (1)
Limit Low Set Point
Set the low process
value that will trigger
the limit.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
Instance 1
Map 1
Map 2
684
724
0x70 (112)
1
3
38
12003 float
RWES
[`Lh;S]
[ Lh.S]
Limit (1)
Limit High Set Point
Set the high process
value that will trigger
the limit.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
0.0°F or
units
-18.0°C
Instance 1
Map 1
Map 2
686
726
0x70 (112)
1
4
39
12004 float
RWES
No
Dis-
play
Limit (1)
Limit State
Clear limit once limit
condition is cleared.
[`off]
Off (62)
[none]
None (61)
[`li;h]
Limit High (51)
[`li;l]
Limit Low (52)
[`err]
Error (28)
- - - -
Instance 1
Map 1
Map 2
690
730
0x70 (112)
1
6
- - - -
12006 uint
R
[`lCr]
[ LCr]
Limit (1)
Limit Clear Request
Clear limit once limit
condition is cleared.
[`Clr]
Clear (0)
[ignr]
Ignore (204)
- - - -
Instance 1
Map 1
Map 2
680
720
0x70 (112)
1
1
- - - -
12001 uint
W
[`l;st]
[ L.St]
Limit (1 to 4)
Limit Status
Reflects whether or not
the limit is in a safe or
failed mode.
[fail]
Fail (32)
[safe]
Safe (1667)
- - - -
Instance 1
Map 1
Map 2
- - - -
744
0x70 (112)
1
0x0D (13)
- - - -
12013 uint
R
[Mon]
[oPEr]
Monitor Menu
[C;MA]
[C.MA]
Monitor (1 to 2)
Control Mode Active
View the current control
mode.
[`off]
Off (62)
[AUto]
Auto (10)
[MAn]
Manual (54)
Instance 1
Map 1
Map 2
1882 2362
Instance 2
Map 1
Map 2
1952
2432
0x97 (151)
1 to 2
2
- - - -
8002
uint
R
[`h;Pr]
[ h.Pr]
Monitor (1 to 2)
Heat Power
View the current heat
output level.
0.0 to 100.0%
0.0
Instance 1
Map 1
Map 2
1904 2384
Instance 2
Map 1
Map 2
1974
2454
0x97 (151)
1 to 2
0xD (13)
- - - -
8011
float
R
[`C;Pr]
[ C.Pr]
Monitor (1 to 2)
Cool Power
View the current cool
output level.
-100.0 to 0.0%
0.0
Instance 1
Map 1
Map 2
1906 2386
Instance 2
Map 1
Map 2
1976
2456
0x97 (151)
1 to 2
0xE (14)
- - - -
8014
float
R
[`C;SP]
[ C.SP]
Monitor (1 to 2)
Closed Loop Set Point
View the set point cur-
rently in effect.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
Instance 1
Map 1
Map 2
2172 2652
Instance 2
Map 1
Map 2
2252
2732
0x6B (107)
1 to 2
7
- - - -
8029
float
R
Note:
Some values will be rounded off to fit in the four-character display. Full values can
be read with other interfaces.
R: Read
W: Write
E: EEPROM
S: User
Set