Low Gain Thermocouple Input Procedure

For all thermocouple inputs excluding Type R, S and B

Equipment Required

Type J reference compensator with reference junction at 32

°

F/0

°

C, or 

Type J thermocouple calibrator set at 32

°

F/0

°

C

Precision millivolt source, 0 - 50mV minimum range, 0.01mV resolution

Setup and Calibration
1. Connect the AC voltage L1, L2 and ground to the proper terminals on the Series

988.  See Chapter 2 in the user's manual.

2. For Input #1 calibration: Connect the millivolt source to terminal #9 (+) and

terminal #10 (-) on the 988 terminal strip.  Use 20 to 24 gauge copper wire.  If
you have model number 98_ _ - _ _ _ - _ _ _ _, remove the control from the
case and set the Input 1 DIP switches to:

1 OFF

2 ON

3 ON

For Input #2 calibration:  Connect the millivolt source to terminal #19 (+) and
terminal #20 (-) on the 988 terminal strip.  Use 20 to 24 gauge copper wire.   If
you have model number 98_ _ - __ _ - _ _ _ _, remove the control from the 
case and set the Input 2 DIP switches to:

1 OFF

2 ON

3 ON

3. Apply power to the unit and let it warm up for 15 minutes.  After warm-up, put

the unit in the CAL menu.  See Page 6.

When performing calibration procedures, always do the Input 1 prompts
(beginning with an “A”) first, then continue on to the Input 2 prompts
(beginning with a “B”).  See the Calibration menu on Page 6.

4. At the A 50 prompt, or the B 50 prompt, enter 50.00mV from the millivolt source

to the Series 988.  Allow at least 10 seconds to stabilize.  Press the Up key to
change the upper display to YES.  Press the Mode key.

5. At the A 00 prompt, or the B 00 prompt, enter 0.00mV from the millivolt source

to the Series 988.  Allow at least 10 seconds to stabilize.  Press the Up key to
change the upper display to YES.  Press the Mode key.

6. At the tc prompt, disconnect the millivolt source, and connect the reference

compensator or T/C calibrator to terminal #9 (+) and terminal #10 (-) on the 988
terminal strip.  If using a compensator, turn it on and short the input wires.
When using a Type J calibrator, set it to simulate 32

°

F/0

°

C.  Allow 10 seconds

for the control to stabilize.  Press the Up key to change the upper display to
YES.  To conclude the T/C calibration, press the Display key.

8

WATLOW Series 988 Calibration Manual

Low Gain T/C

NOTE:

Any prompt begin-
ning with an “A”
applies to Input 1.
Those beginning
with a “B” apply to
Input 2.

Содержание 981 Series

Страница 1: ...s to Series 981 982 983 984 986 987 988 989 Calibration Manual Watlow Controls 1241 Bundy Blvd P O Box 5580 Winona MN 55987 5580 Phone 507 454 5300 Fax 507 452 4507 W988 CM10 9345 November 1993 5 00 M...

Страница 2: ...ion Restore Prompt 7 The dFL Prompt 7 Input Calibration 7 Output Calibration Calibration Procedures 8 Low Gain Thermocouple Input 9 High Gain Thermocouple Input 10 RTD Input 11 mA Process Input 12 VDC...

Страница 3: ...control It is explained in detail on Page 4 of this manual In the Calibration menu CAL various input signals must be supplied for the control to go through its auto calibration See Page 5 for the com...

Страница 4: ...hotocopies instead diAg Software revision Serial number Ambient temperature Ambient A D count Diagnostics Factory ship date Your Readings DAtE SOFt Sn _ _ AMb Acnt gnd cnt2 itY1 itY2 cnt1 OtY1 OtY2 Ot...

Страница 5: ...Universal RTD Curr Heater current Output Types nonE No module rLAB Relay A B SSR1 0 5A SSR rABS Relay A B with suppression SS1S 0 5A SSR with suppression 2rLY Two relays SSr2 2 0A SSR Proc Process SS...

Страница 6: ...IES 988 MODE AUTO MAN CAL Calibration A 50 tc A 0H A 20 A 15 A 00 A380 A 0U A20A b 15 b380 A10U b10U b 0U b 4A b 0u Your Settings b100 1 4 1 20 1 0 1 10 2 4 A 4A b20A Default parameters Your Settings...

Страница 7: ...pt See Figure 2 on the previous page The upper display shows the prompt default no while the lower display indicates the input signal prompt Each input calibration prompt is preceded by an A or B sign...

Страница 8: ...ter warm up put the unit in the CAL menu See Page 6 When performing calibration procedures always do the Input 1 prompts beginning with an A first then continue on to the Input 2 prompts beginning wit...

Страница 9: ...llivolt source to the Series 988 Allow at least 10 seconds to stabilize Press the Up key to change the upper display to YES Press the Mode key 5 At the A 00 or B 00 prompt enter 0 00mV from the milliv...

Страница 10: ...s to 1 OFF 2 OFF 3 ON NOTE Any prompt begin ning with an A applies to Input 1 Those beginning with a B apply to Input 2 3 Apply power to the unit and let it warm up for 15 minutes After warm up put th...

Страница 11: ...om the case and set the Input 2 DIP switches to 1 ON 2 ON 3 ON 3 Apply power to the unit and let it warm up for 15 minutes After warm up put the unit in the CAL menu See Page 6 When performing calibra...

Страница 12: ...he Input 2 DIP switches to 1 ON 2 ON 3 ON 3 Apply power to the unit and let it warm up for 15 minutes After warm up put the unit in the CAL menu See Page 6 When performing calibration procedures alway...

Страница 13: ...ontrol from the case and set the Input 2 DIP switches to 1 1 ON 2 OFF 3 ON 3 Apply power to the unit and let it warm up for 15 minutes After warm up put the unit in the CAL menu See Page 6 When perfor...

Страница 14: ...bilize Press the Up key to change the upper display to YES Press the Mode key To conclude the slidewire feedback calibration press the Display key Current Transformer Input Procedure Equipment Require...

Страница 15: ...nutes After warm up put the unit in the CAL menu See Page 6 When performing calibration procedures always do the Output 1 prompts beginning with a 1 first then continue on to the Output 2 prompts begi...

Страница 16: ...nutes After warm up put the unit in the CAL menu See Page 6 When performing calibration procedures always do the Output 1 prompts beginning with a 1 first then continue on to the Output 2 prompts begi...

Страница 17: ...ance to the next prompt To conclude the process retransmit output calibration press the Display key VDC Retransmit Output 3 Calibration Equipment Required 4 1 2 digit Digital Multimeter Setup and Cali...

Страница 18: ...18 WATLOW Series 988 Calibration Manual...

Страница 19: ...Watlow Process Controls Calibration Manual Watlow Controls 1241 Bundy Blvd P O Box 5580 Winona MN 55987 5580 Phone 507 454 5300 Fax 507 452 4507...

Отзывы: