WATLOW Series 988 Calibration Manual

7

rSt/dFL Prompts

Calibration Restore Prompt

If you make a mistake while calibrating your control, the rSt prompt near the end of
the calibration menu restores the original factory calibration settings.  At the rSt
prompt, simply press the Up or Down key to change the upper display to read YES;
press the Mode key.  The original factory calibration values are restored.

The dFL Prompt

To set the operating parameter defaults for either domestic or international, use
the dFL (default) prompt at the end of the Calibration menu.  Once you have
entered the Calibration menu, use the Mode key to advance to the dFL prompt.
Press the Up or Down key to change the upper display to US or SI.  For domestic
prompts, select US and receive:

°

F

Rate in minutes

Proportional band in degrees or units

Reset in repeats per minute

For international prompts, select SI and receive:

°

C

Derivative in minutes

Proportional band in % of span

Integral in minutes per repeat

Input Calibration

Once you enter the Factory menu, press the Up or Down key until the CAL prompt
appears in the upper display with Fcty in the lower display.  Press the Mode key to
advance to the first calibration prompt.  See Figure 2 on the previous page.  The
upper display shows the prompt default no, while the lower display indicates the
input signal prompt.  

Each input calibration prompt is preceded by an A or B, signifying Input 1 or 2
respectively.  Refer to the Calibration menu on the previous page again.   Before
advancing to the next prompt when calibrating, always apply the correct input signal
and allow to stabilize for 10 seconds before changing the upper display to YES.  If
the parameter is left at no, the calibration information 

will not be entered.  Once the

appropriate parameters are calibrated, press the Display key to exit the CAL menu.

Output Calibration

After calibrating the Input 1 and 2 prompts, the next prompts apply to Output 1
through 3 which are for process outputs only.  
Model numbers affected are 

Output 1

98_ _ - _ _ _ - _ _ _ _

Output 2

98_ _ - _ _ _ - _ _ _ _

Output 3

98_ _ - _ _ _ _ - M_ _ _
98_ _ - _ _ _ _ - N_ _ _

The prompt in the lower display indicates the output signal while the upper display
reads a hexidecimal value which matches the output value.  The upper display
value is for internal use only and should be ignored.  

Each output calibration prompt is preceded by a 1, 2, or 3, signifying Output 1, 2, or 3
respectively.  If your unit does not have Output 2 or 3, these prompts will not appear.
Once the appropriate parameters are calibrated, press the Display key to exit the
CAL menu.

Содержание 981 Series

Страница 1: ...s to Series 981 982 983 984 986 987 988 989 Calibration Manual Watlow Controls 1241 Bundy Blvd P O Box 5580 Winona MN 55987 5580 Phone 507 454 5300 Fax 507 452 4507 W988 CM10 9345 November 1993 5 00 M...

Страница 2: ...ion Restore Prompt 7 The dFL Prompt 7 Input Calibration 7 Output Calibration Calibration Procedures 8 Low Gain Thermocouple Input 9 High Gain Thermocouple Input 10 RTD Input 11 mA Process Input 12 VDC...

Страница 3: ...control It is explained in detail on Page 4 of this manual In the Calibration menu CAL various input signals must be supplied for the control to go through its auto calibration See Page 5 for the com...

Страница 4: ...hotocopies instead diAg Software revision Serial number Ambient temperature Ambient A D count Diagnostics Factory ship date Your Readings DAtE SOFt Sn _ _ AMb Acnt gnd cnt2 itY1 itY2 cnt1 OtY1 OtY2 Ot...

Страница 5: ...Universal RTD Curr Heater current Output Types nonE No module rLAB Relay A B SSR1 0 5A SSR rABS Relay A B with suppression SS1S 0 5A SSR with suppression 2rLY Two relays SSr2 2 0A SSR Proc Process SS...

Страница 6: ...IES 988 MODE AUTO MAN CAL Calibration A 50 tc A 0H A 20 A 15 A 00 A380 A 0U A20A b 15 b380 A10U b10U b 0U b 4A b 0u Your Settings b100 1 4 1 20 1 0 1 10 2 4 A 4A b20A Default parameters Your Settings...

Страница 7: ...pt See Figure 2 on the previous page The upper display shows the prompt default no while the lower display indicates the input signal prompt Each input calibration prompt is preceded by an A or B sign...

Страница 8: ...ter warm up put the unit in the CAL menu See Page 6 When performing calibration procedures always do the Input 1 prompts beginning with an A first then continue on to the Input 2 prompts beginning wit...

Страница 9: ...llivolt source to the Series 988 Allow at least 10 seconds to stabilize Press the Up key to change the upper display to YES Press the Mode key 5 At the A 00 or B 00 prompt enter 0 00mV from the milliv...

Страница 10: ...s to 1 OFF 2 OFF 3 ON NOTE Any prompt begin ning with an A applies to Input 1 Those beginning with a B apply to Input 2 3 Apply power to the unit and let it warm up for 15 minutes After warm up put th...

Страница 11: ...om the case and set the Input 2 DIP switches to 1 ON 2 ON 3 ON 3 Apply power to the unit and let it warm up for 15 minutes After warm up put the unit in the CAL menu See Page 6 When performing calibra...

Страница 12: ...he Input 2 DIP switches to 1 ON 2 ON 3 ON 3 Apply power to the unit and let it warm up for 15 minutes After warm up put the unit in the CAL menu See Page 6 When performing calibration procedures alway...

Страница 13: ...ontrol from the case and set the Input 2 DIP switches to 1 1 ON 2 OFF 3 ON 3 Apply power to the unit and let it warm up for 15 minutes After warm up put the unit in the CAL menu See Page 6 When perfor...

Страница 14: ...bilize Press the Up key to change the upper display to YES Press the Mode key To conclude the slidewire feedback calibration press the Display key Current Transformer Input Procedure Equipment Require...

Страница 15: ...nutes After warm up put the unit in the CAL menu See Page 6 When performing calibration procedures always do the Output 1 prompts beginning with a 1 first then continue on to the Output 2 prompts begi...

Страница 16: ...nutes After warm up put the unit in the CAL menu See Page 6 When performing calibration procedures always do the Output 1 prompts beginning with a 1 first then continue on to the Output 2 prompts begi...

Страница 17: ...ance to the next prompt To conclude the process retransmit output calibration press the Display key VDC Retransmit Output 3 Calibration Equipment Required 4 1 2 digit Digital Multimeter Setup and Cali...

Страница 18: ...18 WATLOW Series 988 Calibration Manual...

Страница 19: ...Watlow Process Controls Calibration Manual Watlow Controls 1241 Bundy Blvd P O Box 5580 Winona MN 55987 5580 Phone 507 454 5300 Fax 507 452 4507...

Отзывы: