background image

2 10  Electrical connections

Ensure  that  the  general  electrical  power  supply  has 

been cut off before starting any repair work.

2 10 1   Characteristic of the electrical supply

The  electrical  installation  must  be  conducted  in 

accordance with the prevailing regulations.
The electrical connections must only be made when all 

the other fitting operations have been completed (fixing, 

assembly, etc.).

 

"

Warning !

The contract concluded with the energy provider must 

be sufficient not only to cover the heat pump's power but 

also the combined sum of all the appliances likely to be 

operating at the same time. When the power is too low, 

check with your energy provider the value subscribed to 

in your contract.
Never use a socket for the power supply.
The heat pump must be supplied with power by special 

protected leads from the electric panel via 2-pole circuit 

breakers specially dedicated to the heat pump, Curve 

D for the outdoor unit, curve C for the electrical heating 

and domestic water back-ups (see tables on 

page 25

).

The electrical installation must necessarily be equipped 

with a 30mA differential protection.
This appliance is designed to operate under a nominal 

voltage of 230 V or 400 V, +/- 10%, 50 Hz (according to 

model).

2 10 2   General remarks on electrical connections

It is essential to maintain the live-neutral polarity when 

making the electrical connections.
Tighten  the  screws  on  the  terminal  blocks  perfectly. 

Unsufficient tightening can cause overheating, leading 

to breakdown or even a fire.
Tighten the cables using the cable glands to prevent the 

conductors from disconnecting accidentally.
Connection  to  Earth  and  Earth  bonding  continuity  are 

essential.

• Connecting to screw terminals

Rigid wires

 (

A

)

Rigid wires are always preferable for fixed installations, 

particularly in a building.

 -Always select a wire that complies with the prevailing 

standards.

 -Strip away around 25 mm from the end of the wire.
 -With  round  end  pliers,  form  a  loop  with  a  diameter 

corresponding to the tightening screws on the terminal.

 -Tighten the terminal screw firmly onto the loop created.

Flexible wires

 (

B

)

H07RNF type (or superior quality) flexible wire can be 

used with certain precautions:

 -Strip away around 10 mm from the end of the wire.
 -With tightening pliers, fit a round tag with a diameter 

corresponding to the terminal screw's diameter on the 

end of the wire.

 -Tighten  the  tag  firmly  onto  the  terminal  with  a 

screwdriver. We strongly advise against using flexible 

wires without round tags.

 -Always protect the cables when passing them through 

cable clamps with PVC protective conduit 0,5 to 1 mm 

thick.

A : Rigid wires

Loop

25 mm

10 mm

Round terminal 

tightened

Special screw  

and  

washer

Terminal 

block

B : Flexible wires

• Connecting to regulation cards

 -Remove the corresponding connector and make the 

connection.

• Connecting to spring terminals

Rigid wires

 -Strip away around 10 mm from the end of the wire.
 -Slide  the  wire  into  the  opening  provided  for  this 

purpose.

 -Push  the  spring  with  a  screwdriver  so  that  the  wire 

enters the cage.

 -Remove the screwdriver and then check that the wire 

is jammed in the cage by pulling on it.

Flexible wires

 -Use the ends and proceed as before.

2

1

3

Pre-cabled bundle connector  and/or   Screw connector

Installation and operating manual "1533 - EN"

Air to Water Heat Pump

- 24 -

Содержание WS G140DC6 Series

Страница 1: ...1533 0 05 06 2012 FR EN IT NL DE Fujitsu General Euro GmbH Werftstrasse 20 40549 D sseldorf Germany Subject to modifications without notice Non contractual document Split system Air to Water Heat Pum...

Страница 2: ...operation single phase outdoor unit 20 Pump down operation Refrigerant collecting operation 3 phase outdoor unit 21 Hydraulic connecting 22 General 22 Rinsing out the installation 22 Filling and purgi...

Страница 3: ...Overall hydraulic layout 50 Electrical wiring diagrams 52 Troubleshooting 56 Faults displayed on the hydraulic unit 56 Information display 57 Faults displayed on the single phase outdoor unit 58 Fault...

Страница 4: ...convectors Heating the swimming pool These options require the use of additional kits see para Optional equipment Optional equipment 2nd circuit kit code UTW KZS D for connecting 2 heating circuits Re...

Страница 5: ...ircuit Maximum operating pressure bar 3 Hydraulic system flow rate mini maxi 4 C t 8 C nominal conditions l h 1170 2340 1460 2920 1170 2340 1460 2920 1650 3290 Various Weight of outdoor unit kg 92 99...

Страница 6: ...Side view Air Air figure 1 Dimensions in mm 900 1290 9 21 650 370 Air 31 12 330 400 Air Air Overflow hole 20 4 Holes 10 Sight of lower part Front view Top view Side view Installation and operating ma...

Страница 7: ...800 832 8 97 98 457 81 479 Heating return M 26x34 Heating flow M 26x34 Front view Side view Hydraulic module figure 2 Dimensions in mm Installation and operating manual 1533 EN 7 Air to Water Heat Pu...

Страница 8: ...ic values of the sensors outside unit 20 10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 10000 1000 100 10 1 Compressor Discharge Condensation Evaporator outlet Evaporator center Compressor casing Out...

Страница 9: ...d temperature insulated inverter compressor 11 Refrigeration connection valves flared connectors with protective caps 12 Holding tank with condensate drain hole 13 High performance exchange surface ev...

Страница 10: ...t periods Legend 1 Electric box 2 Regulator User interface 3 Start stop switch 4 Heating circulation pump 5 Heating flow 6 Gas refrigeration connection 7 Liquid refrigeration connection 8 Heating retu...

Страница 11: ...20 is set nominal temperature can be reached 24h day or only at night or depending on the heat pump program If the contract concluded with the energy provider includes a subscription to day night tari...

Страница 12: ...intervention of a qualified person Choose the site of the outdoor unit and the hydraulic unit after discussion with the customer Observe the maximum and minimum distances between thehydraulicunitandt...

Страница 13: ...d not transmit any vibration to the dwelling Anti vibratory blocks are available as an option The wall brackets is strongly discouraged due to vibration figure 11 Minimum installation clearances aroun...

Страница 14: ...ound because it will cause trouble 2 4 3 Condensate drain hose see figure 12 If the use of a discharge pipe is imperative Use the elbow provided C to connect a 16mm diameter hose for draining away the...

Страница 15: ...ni 300 mm mini 350 mm mini 188 mm figure 13 Mounting bracket Be careful not to bring inflammable gas near to the heat pump during its installation in particular when it requires brazing The appliances...

Страница 16: ...iance Proceed to insulate the gas and liquid pipes to avoid any condensation Use pipe insulators resistant to temperatures over 90 C In addition if the humidity level in areas where the refrigeration...

Страница 17: ...er flaring check the condition of the working radius L This must not show any scratch or trace of any fracturing Also check the dimension B 2 6 5 Shaping the refrigeration pipes The refrigeration pipe...

Страница 18: ...refrigeration connections Present the pipe to the flared connector and screw the nut by hand while holding the connector with a wrench until contact Warning Avoid positioning the Gas pipe in front of...

Страница 19: ...re is a leak Find and repair the leak and then recommence vacuum testing When the pressure remains steady for a few hours after stopping the vacuum pump the circuit can be considered airtight Remove t...

Страница 20: ...additional meter Length of the connections 15 m 20 m max Additional charge none 250 g The charge in the outdoor units corresponds to the maximum distances between the outdoor unit and the hydraulic un...

Страница 21: ...he following procedures to collect the refrigerant 1 Turn OFF the start stop switch ref 3 figure 7 page 10 2 Remove the front panel Then turn ON the DIP SW 1 on the interface card 3 Turn ON the start...

Страница 22: ...mestic and heating water in our price catalogue It is also necessary to ensure that the treated water does not become aggressive 2 8 2 Rinsing out the installation Before connecting the hydraulic unit...

Страница 23: ...ar 1 mbar 10 mmCE 100 Pa m h 3 1 1 5 2 2 5 0 5 0 2 4 6 6 ext in 2 4 6 7 4 2 0 100 200 300 400 500 600 mbar 1 mbar 10 mmCE 100 Pa m h 3 1 1 5 2 2 5 0 5 0 2 4 7 7 ext in 2 4 6 7 4 2 ext in 2 4 6 7 4 2 D...

Страница 24: ...prevent the conductors from disconnecting accidentally Connection to Earth and Earth bonding continuity are essential Connecting to screw terminals Rigid wires A Rigid wires are always preferable for...

Страница 25: ...the outdoor unit by means of a cable with 4 x 1 5 mm phase neutral earth communication bus Power supply to the electrical back ups The hydraulic unit contains two stages of electrical back ups install...

Страница 26: ...the connections in accordance with the diagram figure 33 page 30 Use cable clamps to prevent the conductors from being disconnected accidentally Use the cover plate to hold the cables against the ins...

Страница 27: ...o 3 phase outdoor unit s terminal block Remove the screws and push downwards Front panel Terminal block figure 28 Connections to 3 phase outdoor unit s terminal block 1 INDOORUNIT POWER 2 3 L1 L2 L3 N...

Страница 28: ...mp s operation can be controlled to suit special contracts e g off peak day night In particular domestic hot water DHW at Nominal temperature will be produced during the off peak hours when electricit...

Страница 29: ...Interface card Cable grommet sensors Terminal blocks Model single phase External faults the heat pump Any component of carryforward of information thermostat pressure switch etc may signal an externa...

Страница 30: ...hase Electrical back up supply 230 V single phase Electricity supply 400 V 3 phase Electrical back up supply 400 V 3 phase External component contact External component contact Red Red Blue Blue Brown...

Страница 31: ...board using the connector provided terminals 1 2 and 3 Wireless remote control Connect the wireless remote control to the connector X60 2 13 Commissioning Close the installation s main circuit breake...

Страница 32: ...15 Configuring remote control wireless During commissioning after an initialisation period of approx 3 minutes the user s language must be set Press OK Choose menu Operator section Choose language Se...

Страница 33: ...Installation and operating manual 1533 EN 33 Air to Water Heat Pump...

Страница 34: ...ption and Room thermostat option figure 34 C Auto Auto ESC OK 0 4 8 12 16 20 24 1 2 3 4 5 6 7 8 11 5 2 10 11 Remote control option Room thermostat option 1 2 3 4 5 6 7 8 9 User interface Installation...

Страница 35: ...mode switchover is automatic Constant comfort temperature Constant reduced temperature Stand by mode with anti frost protection Provided that the heat pump s electrical power supply is not interrupted...

Страница 36: ...ter temperature in the heating circuit The off set in the temperature control parameter 721 modifies the initial temperature of all the curves without modification of the slope figure 37 The correctiv...

Страница 37: ...721 No correction No correction No correction No correction No correction OK OK OK OK OK OK Cold Cold Cold Cold Cold Hot Hot Hot Hot Hot Hot Cold No correction Corrective actions on the temperature co...

Страница 38: ...tes 00 00 23 59 1 2 U Day Month 01 01 31 12 1 3 U Year 1900 2099 1 5 S Start of Summer time Day Month 01 01 31 12 1 25 03 6 S End of Summer time Day Month 01 01 31 12 1 25 10 The change of hour will a...

Страница 39: ...end 00 00 10 min 22 00 523 U 2nd phase On start 00 00 10 min 524 U 2nd phase Off end 00 00 10 min 525 U 3rd phase On start 00 00 10 min 526 U 3rd phase Off end 00 00 10 min 535 U Copy 536 U Default va...

Страница 40: ...Preselection Period 1 to 8 Period 1 652 U Period Start Day Month 01 01 31 12 1 653 U Period End Day Month 01 01 31 12 1 658 U Operating level Frost protection Reduced Frost protection Heating circuit...

Страница 41: ...curing function figure 39 Off Off Early interruption of the current program program inactive Functional heating Heating ready for occupation Functional heating Curing heating Curing heating Functiona...

Страница 42: ...65 C Important Note Maximum temperature limitation is not a safety function as required by ground heating 1050 S Room influence 1 100 1 50 If the installation is fitted with a room thermostat This fu...

Страница 43: ...e case of a day night contract the electric back ups for the DHW tank are subject to the power supplier s tariffs Switching on the electric back up for the DHW tank is only authorised during off peak...

Страница 44: ...circuit and with or without DHW tank Pre setting 4 Boiler connection and 2 heating circuits and with or without DHW tank Pre setting 5 and more Not used 5710 S Heating circuit 1 Off On On 5711 S Cool...

Страница 45: ...C 0 5 Inputs outputs test 7700 I Relay test 0 This consists of instructing the regulator s relays one by one and checking their outputs This enables you to check that the relays are working and that t...

Страница 46: ...73 I Sensor temperature BX31 Mixing circuit temp 28 350 C 7974 I Sensor temperature BX32 28 350 C 7975 I Sensor temperature BX33 28 350 C 7976 I Sensor temperature BX34 Swimming pool exchanger tempera...

Страница 47: ...is used for automatic Summer Winter switchover line 730 8704 I Outside temp composite 50 50 C The mixed outside temperature is a combination of the current outside temperature and the average outside...

Страница 48: ...S Not used 8981 S Not used 9031 I Relay output QX1 Off On On 9032 I Relay output QX2 Off On On 9033 I Relay output QX3 Off On On 9034 I Relay output QX4 Off On Off 9035 I Relay output QX5 Off On Off 9...

Страница 49: ...Installation and operating manual 1533 EN 49 Air to Water Heat Pump...

Страница 50: ...ircuit SA SE R SP MH CC Legend CC Heating circulation pump MH Hydraulic unit R Radiators SA Room thermostat or Remote control option SE Outdoor sensor SP Heated floor thermal safety fuse Installation...

Страница 51: ...S CC Legend AE Electrical back up CC Heating circulation pump KS DHW kit MH Hydraulic unit R Radiators SA Room thermostat or Remote control option SE Outdoor sensor SP Heated floor thermal safety fuse...

Страница 52: ...er Fan motor 2 lower Option connector Refer to the technical manual Fuse Fuse Power source 230 V Interconnection between the outdoor unit and the hydraulic unit F4 T 5A 250 V F2 T 3 15A 250 V Fuse 10A...

Страница 53: ...istor heat exchanger out Thermistor outdoor temp Thermistor compressor temp Pressure sensor Reactor fan Solenoid coil Solenoid coil Inj Expansion valve coil Fan motor 1 upper Fan motor 2 lower Option...

Страница 54: ...e Except installer s connections Connections to the heat pump regulator accessories and options see figure 31 page 28 Connection to terminal block see figure 33 page 30 Connection to terminal block se...

Страница 55: ...draulic unit HP 3 phase Except installer s connections Connections to the heat pump regulator accessories and options see figure 31 page 28 Connection to terminal block see figure 33 page 30 Connectio...

Страница 56: ...ction error In the start phase see the para Start up See below and page 58 59 No Hydraulic unit Flashing of the diode visible on the interface card Diodes display Error contents LED 2 green LED 1 red...

Страница 57: ...e 8022 State DHW 8003 State swimming pool 8011 State heating circuit 1 8000 State heating circuit 2 8001 State cooling circuit 1 8004 Outdoor temperature 8700 Room temperature 1 8740 Room setpoint 1 F...

Страница 58: ...error 7 Flashes Outdoor temperature thermistor error 8 Flashes Compressor thermistor error 9 Flashes Heat sink thermistor error 11 Flashes Discharge temperature protection permanent stoppage 12 Flash...

Страница 59: ...shes Heat exchange thermistor intermediate error 6 Flashes Expansion valve thermistor error 7 Flashes Outdoor temperature thermistor error 8 Flashes Compressor thermistor error 9 Flashes Heat sink the...

Страница 60: ...ks Main system pressure and degassing Refrigeration connections and checks see chapiters Refrigeration connections page 16 Filling the installation with gas page 19 OK Non compliant Connections betwee...

Страница 61: ...ximum start setting 741 1041 Outdoor unit checks OK Non compliant Value Operation of fan s compressor Current measurement After a few minutes measurement of air temp delta Check condensation and evapo...

Страница 62: ...release DHW 1640 to 1642 legionella cycle DHW 5024 DHW switch on differ DHW tank 5030 charging time limitation DHW tank 5061 heater release DHW tank Setting Description Set to Menus Boiler backup 370...

Страница 63: ...put temperature C T condensation C Tank water input temperature C T secondary C Evaporation temperature LP bar C Suction temperature C Overheating C Battery air input temperature C T evaporation C Bat...

Страница 64: ...EC Directive 2006 42 EC Machinery Directive for pressurised equipment 97 23 EC This appliance also conforms to Regulation 842 2006 of the european parliament on certain fluorinated greenhouse gases Th...

Отзывы: