Problem 

Cause 

Fix 

System overheating 

 

Oil level in the air compressor is low 

Check for oil leaks and repair as needed. Use 
ISO 68 viscosity hydraulic oil, filling to the mid-
dle of the sight glass. 

Plugged water strainer at oil cooler 

Remove strainer and clean screen. 

Inadequate water supply 

Verify that water is being circulated within the 
pump (TANK TO PUMP valve completely open 
with the TANK FILL valve 1/4 open). 

Overheated water supply 

Supply the pump with fresh cool water and open 
a discharge valve or TANK FILL valve, allowing 
the heated water to be dumped to atmosphere. 

Compressor overspeeding in UNLOAD mode 

Do not run compressor in excess of 8950 RPM. 
Compressor speed can be calculated as follows: 
drive line (engine) speed x 2.5 x gear ratio in the 
pump transmission. 

Temperature gauge inoperative 

 

Wires unconnected 

Check wire connections at the gauge, sending 
unit and power supply. 

Wires improperly connected 

Check wiring for proper sequence (green to 
large terminal; yellow to small terminal) - See F-
1031, Section 3027 (S100 Eclipse) or F-1031, 
Section 3028 (CX Eclipse). 

Excessive oil consumption 

 

Reservoirs overfilled with oil 

Check oil level while on a level surface. Reduce 
level to middle of the sight glass. 

Flowing in excess of 200 CFM 

Reduce RPM and flow CAFS and recheck oil 
level. 

Oil/Air filter torn or damaged 

Result of flowing air in excess of 200 CFM. Re-
place air filter, flow CAFS, shut down the pump 
for 15 minutes and check oil level. 

Oil siphon line and check valve 

Check oil siphon line for obstruction and inspect 
check valve for operation. 

Excessive compressor bleed down time 
(time may vary) 

 

Inlet air trim valve closed too far 

Reference “Control Air Circuit Calibration In-

structions” on Page 12. 

Debris in inlet air trim valve 

Clean valve and reference “Control Air Circuit Cali-

bration Instructions” on Page 12. 

Engine stalls upon compressor engage-
ment 

 

Electric Auto-Sync in FIXED or AUTO position 

Place the Electric Auto-Sync in the  UNLOAD 
setting. 

Engaging compressor when under load 

Operating under this condition causes the com-
pressor oil to accumulate in the compressor cre-
ating a condition similar to a hydraulic pump. To 
correct, allow air to bleed off, restart the com-
pressor and immediately begin flowing air 
through a discharge. 

Air compressor locked up 

Due to a lack of compressor oil/lubrication. Re-
pair or replace the compressor. 

Содержание Eclipse ES CX

Страница 1: ...hut Down Procedure 9 Compressed Air Foam Operations 9 Compressed Auto Shut Down 9 Service and Maintenance 9 Poly Chain Replacement and Adjustment 10 Calibration Control Air Circuit 12 Troubleshooting...

Страница 2: ...and nozzle used for air discharge will be come hot due to the hot air flowing through it Wear protective gloves Also be prepared for noz zle reaction when air discharge and nozzle are opened Air Sourc...

Страница 3: ...has a siphon tube that picks up the recovered oil for return to the air compressor The compressor s air output is controlled by a modulating inlet valve The inlet valve is opened and closed by the Au...

Страница 4: ...Belt 19 Compressor Oil Sump 5 Belt Adjustment Hardware 19A Safety Relief Valve 6 Air Inlet Valve 20 Oil Temperature Gauge 7 Auto Balancing Valve 21 Oil Temperature Sensor 8 Air Clutch Solenoid 22 Oil...

Страница 5: ...of 0 2 and 0 3 are typically ade quate to produce compressed air foam that is formed in a hoseline and used on Class A combustibles Higher set tings will result in a drier appearing foam Lower settin...

Страница 6: ...olution from another discharge while pumping com pressed air foam from yet another or varying foam con sistencies expansion ratios from different discharges simultaneously NOTE Monitor compressor inst...

Страница 7: ...ler is running the FOAM LED will be lit The FOAM LED will blink when the motor control output is active The LED will be lit and not blink during the initial pump delay or when the system is on but no...

Страница 8: ...position 3 Move the Auto Sync control to the AUTO posi tion The air pressure should rise to within plus or minus 5 of the water discharge pressure The Auto Sync system will balance the air and water p...

Страница 9: ...Overheat light will illuminate The water pump and foam proportioning systems will continue to operate and are not affected by the compressor shut down To re start perform the follow ing 1 Correct the...

Страница 10: ...amage or excessive wear semi annually or more frequently as dictated by the amount of use Belt tension may be checked by applying a 10 12 lb load to the belt mid span between drive and driven sprocket...

Страница 11: ...nment in which the unit operates will determine the frequency of air filter replacement In any situation replace at least annually 12 Replace the air oil separator cartridge every 24 months or if the...

Страница 12: ...d regulator is performing by varying the compressor speed and monitoring the air pressure gauge The pressure should remain steady at the fixed pressure setting With the final adjustments to the FIXED...

Страница 13: ...ge and correct as needed Air inlet trim valve out of adjustment Reference Control Air Circuit Calibration In structions on Page 12 Debris in air inlet trim valve AITV Clean debris from air inlet trim...

Страница 14: ...Eclipse Excessive oil consumption Reservoirs overfilled with oil Check oil level while on a level surface Reduce level to middle of the sight glass Flowing in excess of 200 CFM Reduce RPM and flow CA...

Страница 15: ...requires repair Water in compressors oil air Leaking oil cooler Isolate the heat exchanger and check for leaks Replace if necessary Typical cause is freez ing Discharge air check valve s malfunctionin...

Страница 16: ...wing the interaction of the control air system compo nents in each mode as well as explanations of the work ings of specific components The status of the control air circuit is also described when the...

Страница 17: ...ar If the compressor discharge air pressure is above 40 50 psi 2 8 3 4 bar then the control air closes the air inlet valve This causes the control air pressure to drop below 40 50 psi 2 8 3 4 bar the...

Страница 18: ...si 10 3 bar When the discharge air pres sure is below the set point 150 psi 10 3 bar then the fixed air regulator closes Now the control air pres sure is not high enough to keep the air inlet valve cl...

Страница 19: ...high enough to keep the air inlet valve closed The air inlet valve opens allowing air into the compressor raising the control air pressure above 100 psi 8 6 bar The balance valve opens and closes as n...

Страница 20: ...t or have any influence They are basically bypassed The auto sync solenoids are also bypassed and it doesn t matter whether they are opened or closed They have no influence on shutdown Pressure Hazard...

Страница 21: ...flow at the compressor discharge To stop the compressor pressure increase or restrict the compressor air flow the air inlet valve needs to close The air inlet valve will close when the control air pr...

Страница 22: ...egulator operate in the air control circuit when in the FIXED or AUTO modes Fixed Mode The regulator basically operates as de scribed above If the compressor discharge pressure is above the fixed air...

Страница 23: ...Bal ance Valve Open The balance valve can be calibrated or biased via the BTV See control air control circuit cali bration in the maintenance manual How does the balance valve operate in the air cont...

Страница 24: ...he CIAP is always 14 5 psia or less and the CDAP is 40 psig or greater minimum pressure valve setting allowing the shuttle valve to stay closed The figure on the right shows the shuttle valve in an op...

Отзывы: