SELECT
Selects data to display. The default is to display flow rate. Pressing
the SELECT button will scroll through the list, then wrap back around
to the top of the list. The associated LED will light to indicate what
data is being displayed.
Flow Rate
Mix Percentage
Total Water
Total Product
Holding the select button for more than 2 seconds, will lock display
current position. Pressing the select button again will unlock.
UP ARROW
When the Mix Percentage is displayed, the current mix setpoint will
be displayed. Subsequent presses of the UP ARROW button will
increase the Mix Setpoint by 0.1%. After a 10 second timeout, the
display will return to the Flow Rate display.
DOWN ARROW
When the Mix Percentage is displayed, the current mix setpoint will be
displayed. Subsequent presses of the DOWN ARROW button will
decrease the Mix Setpoint by 0.1%. After a 10 second timeout, the
display will return to the Flow Rate display
Pressing both UP and DOWN simultaneously when the Total Water is
displayed resets the Total Water accumulator to Zero.
Pressing both UP and DOWN simultaneously when the Total Product
is displayed resets the Total Product accumulator to Zero.
Pressing both UP and DOWN simultaneously, for 2 seconds, when the
Flow Rate is displayed enters the MANUAL mode of operation. See
Manual Mode operation below.
Pressing both UP and DOWN simultaneously while in Mix % will go to
the preset default %.
FOAM
Pressing the FOAM button will alternately start and stop the foam
operation. When the controller is running, the FOAM LED will be lit.
The FOAM LED will blink when the motor control output is active.
Manual Mode
If the display is showing the flow rate, and the two ARROW keys are
pressed simultaneously, held for 2 seconds, the % MIX LED will light
and the display will show a default value of 2.0.
Use the UP or DOWN arrow keys to increment or decrement this value
in steps of 0.5.
Note:
Pump output is based on a theoretical ratio of foam to water at
50 GPM.
While in manual mode, you can pause the motor by pressing the RED
FOAM button (once). You can increase or decrease the foam
percentage at this time. Resume foam flow by pressing the RED
button once.
Pressing both ARROW keys again exits the MANUAL mode and stops
the pump.