F-1031, Section 2416
Page 17 of 23
Observed
Symptom
Probable Cause
Suggested Remedy
Sump fire
Check system and repair
Low oil level or no oil
Check system and repair
Air flow meter stuck
at "0" CFM
Magnet uncoupled in
meter
Turn air flow on and off to re-couple
Air flow meter stuck
at high CFM
Move large amounts of air out discharge and turn air flow on and off to re-couple
Poor foam (wet or
dry) or no foam
(assuming air
pressure to
discharges is OK)
Using wetting agent and
not foam concentrate.
Use foam concentrate
Foam proportioning
control turned too low.
Increase amount of concentrate delivered to manufacturer recommended amount.
Foam proportioning
control OFF or turned
too low, foam tank
empty.
Make sure proportioner is turned on, foam supply valve is open, foam tank has
concentrate, Y strainer is clean, and supply line is connected to injector.
Discharge hose
shaking (slug flow)
Foam proportioner ON,
setting correct, and tank
has foam concentrate,
but not providing foam
solution.
Refer to foam proportioner manufacturer's instructions for detailed calibration and
troubleshooting instructions
Foam in the water
system (when
proportioner turned
off)
Foam concentrate was
poured into the on-board
water tank
Flush tank and pump with clean water, refill
Foam manifold drain
lines not isolated from
water drain lines
Isolate to separate drain valve
Cooler line plumbed
from foam manifold
Relocate line to discharge side of pump
Foam manifold check
valve defective
Rebuild/replace check valve
Water in
compressor oil/air
Leaking inside cooler
Freeze damage
Isolate cooler and check for leaks, replace if needed, check drain
Defective air check
valves
Replace or check
Missing air check valves
for discharges
Install check valves
Clutch smoking
Engaging in RUN
position
Engage in AUTO/UNLOAD only
Slight air leak from
solenoid to clutch
Repair air leak
Содержание 80-P