Installation
12.11.2015
18 / 60
Z21826
Copyright
2013 by: WATERKOTTE GmbH. Subject to changes
6
Installation
Installation of the heat pump must be performed on a flat and horizontal sur-
face.
We recommend a concrete base
Recommendation:
Wall clearance left, right and on top must be at least 400 mm.
Wall clearance in rear must be at least 200 mm.
Figure 5: Recommendation - wall clearances
6.1
Environmental conditions for installation
The room must be dry. Room temperature should be between
+10 °C and +30 °C.
To facilitate maintenance, the use of a base plate is recommended. Acoustics in
installation rooms with rigid walls can noticeably increase operating noise.
Counter measure: acoustic insulation of one of the opposite wall or ceiling surfac-
es.
6.2
Creating the foundation and installing heat pump
Within the device
an electrically driven
air
compressor is used
,
causing
the
vibra-
tion. For the best attenuation of the vibration it gets placed on rubber mounting
feet, the weight and the excitation get balanced on. The hydraulic connections are
also connected with flexible hoses. In this way the transmissions of the vibrations
is reduced to a minimum. An additional improvement can be obtained by creating
an heat pump size corresponding base (see below), are achieved with an insulat-
ing pad made of polyurethane rubber.