background image

4

TRUCLIMATE 700 90-140 TON  INSTALLATION MANUAL 

Safety Considerations

This appliance is not intended for use by persons 
(including children) with reduced physical, sensory, 
or mental capabilities, or lack of experience and 
knowledge, unless they have been given supervi-
sion or instruction concerning use of the appliance 
by a person responsible for their safety.

Children should be supervised to ensure that they 
do not play with the appliance.

Maximum altitude for this equipment shall not 
exceed 2000 m.

For installation only in locations not accessible to 
the general public.

Installing and servicing air conditioning and 

heating equipment can be hazardous due to system 
pressure and electrical components.  Only trained and 
qualified service personnel should install, repair or service 
heating and air conditioning equipment.  When working 
on heating and air conditioning equipment, observe 
precautions in the literature, tags and labels attached to the 
unit and other safety precautions that may apply.

Follow all safety codes.  Wear safety glasses and work 
gloves.  Use quenching cloth for brazing operations.  Have 
fire extinguisher available for all brazing operations.

NOTE:

  Before installing, check voltage of unit(s) to ensure 

proper voltage.

WARNING:  Before performing service or 
maintenance operations on the system, turn off 
main power switches to the unit.  Electrical shock 
could cause serious personal injury.

Application

Units are not intended for heating domestic (potable water) 
by direct coupling.  If used for this type of application, a 
secondary heat exchanger must be used.

Moving and Storage

Move units in the normal “Up” orientation as indicated by 
the labels on the unit packaging.  When the equipment 
is received, all items should be carefully checked against 
the bill of lading to ensure that all crates and cartons 
have been received in good condition.  Examine units for 
shipping damage, removing unit packaging if necessary 
to properly inspect unit.  Units in question should also 
be internally inspected.  If any damage is observed, the 
carrier should make the proper notation on delivery receipt 

General Installation Information

acknowledging the damage. Units are to be stored in a 
location that provides adequate protection from dirt, debris 
and moisture.

Units are setup to be side picked using a fork lift. Some 
units include pick bars allowing for picking from the end 
with required fork lengths. Note unit labels and markings 
for safe picking points. Do not pick the unit up from points 
not specified and keep the unit level during transport and 
handling. Using improper equipment handling methods can 
result in damage and/or void the warranty. 

WARNING: To avoid equipment damage, do not 
leave the system filled in a building without heat 
during cold weather, unless adequate freeze 
protection levels of antifreeze are used. Heat 
exchangers do not fully drain and will freeze 
unless protected, causing permanent damage. 

Unit Location

Provide sufficient room to make water and electrical 
connections.  If the unit is located in a confined space, 
provisions must be made for unit servicing.  Locate the 
unit in an indoor area that allows easy removal of the 
access panels and has enough space for service personnel 
to perform maintenance or repair.  These units are not 
approved for outdoor installation and, therefore, must be 
installed inside the structure being conditioned.  Do not 
locate units in areas subject to freezing conditions. 

WARNING: Do not store or install units in 
corrosive environments or in locations subject 
to temperature or humidity extremes. Corrosive 
conditions and high temperature or humidity can 
significantly reduce performance, reliability, and 
service life.
 
WARNING: To avoid equipment damage and 
possible voiding of warranty, be sure that properly 
sized strainers are installed upstream of both 
brazed plate heat exchangers to protect them 
against particles in the fluid.

Содержание TruClimate 700

Страница 1: ...entive Maintenance TruClimate 700 90 140 Ton Installation Manual I ll i M l Commercial 60 Hz Water Cooled Chiller R 513A Refrigerant 90 140 Ton Lead Variable Speed Compressor Installation Information...

Страница 2: ......

Страница 3: ...stance Transport 19 Water Quality 20 Water Connections 22 Operating Limits 22 Electrical Data 23 Electrical Connections 23 Electrical System and Controls Safety Circuit 24 Wiring Schematics 26 HydroLi...

Страница 4: ...condition Examine units for shipping damage removing unit packaging if necessary to properly inspect unit Units in question should also be internally inspected If any damage is observed the carrier s...

Страница 5: ...oltage 4 460 60 3 Electrical Option A Fused Disconnect Control Option D Primary Unit Master Controller Non Standard Options SSS None Future Option N Not Applicable Future Option 0 Not Applicable Futur...

Страница 6: ...modules B 3 modules C 4 modules D 5 modules Family HSC HydroLink Supervisory Control Chiller Module N NXW Compact Scroll D WC Dual Scroll Modular Chiller S WCHVE VS Dual Screw Chiller Header Rack A No...

Страница 7: ...d standard provisions for remote access using BACnet Color touch screen chiller interface provides easy to use instant access to unit performance Low impedance line reactors reduce harmonic noise and...

Страница 8: ...speed drive integrated with compressor provides envelope control for improved reliability DC Inverted Variable Speed Single Screw Compressor Removable 4 pipe header rack Full enclosure foam lined pan...

Страница 9: ...d WaterFurnace modular screw units feature several industry firsts to provide a true modular chiller 1 Modular chiller unit can be removed from the bank and replaced with a new unit using strategicall...

Страница 10: ...10 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data...

Страница 11: ...11 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data Service Clearance...

Страница 12: ...12 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data Center of Gravity...

Страница 13: ...13 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data Rigging Data...

Страница 14: ...er in the back It is recommended to carry the load a low as possible maximum of 2 inches NOTE The placement of the compressor and heat exchangers on this unit creates greater weight toward the rear 4...

Страница 15: ...INSTALLATION MANUAL Chiller Installation cont 5 Remove 4 u bolts image below and retain for later installation 6 Remove 4 pipes that are attached to the pipe rack in shipment image below Remove 4 U bo...

Страница 16: ...victaulic connections that were previously removed 8 Using a forklift move main unit into position carefully guiding pipes from heat exchangers into the pipe rack 9 Once both unit and pipe rack are in...

Страница 17: ...TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Chiller Installation cont 10 Install bolts along the junction of pipe rack frame and unit body 11 Attach the quick connect isolation valves and flow switc...

Страница 18: ...e unit frame see image 2 Slightly lift 2in maximum the module and pull away from the bank Make sure the module sensors do not come into contact with any of the structural members of the header rack 3...

Страница 19: ...sport 1 When lifting the chiller all lifting brackets must be used 2 Always use spreader bars The sound enclosure of the chiller may be damaged if spreader bars are not used 3 The front pockets of the...

Страница 20: ...the basis of acceptable pressure drop and not on pipe diameter The strainers selected should have a pressure drop at the nominal ow rate of the units low enough to be within the pumping capacity of th...

Страница 21: ...en egg smell appears at 0 5 ppm 10 50 ppm Less than 1 ppm Sulfates Less than 125 ppm Less than 125 ppm Less than 200 ppm Chlorine Less than 0 5 ppm Less than 0 5 ppm Less than 0 5 ppm Chlorides Less t...

Страница 22: ...art up is scheduled Each water header is equipped standard with a temperature well sensor for supply and return water temperatures of the units performance Also included is a flow switch located on th...

Страница 23: ...A Min Circ Amp Max Fuse HACR MOA RLA LRA1 090 460 60 3 414 506 190 0 156 0 20 0 156 0 195 0 350 115 460 60 3 414 506 225 0 185 0 20 0 185 0 231 3 400 140 460 60 3 414 506 290 0 240 0 20 0 240 0 300 0...

Страница 24: ...he compressor contactor CC output of the Aurora control Anytime Aurora senses a fault that would require compressor shutdown it will trigger the STO input to turn the motor off High Pressure Switch NC...

Страница 25: ...25 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Wiring Schematic next page...

Страница 26: ...NET P6 RS485 EXP P3 SW2 On Future Use L Output Type CC Dual Single Acc Dip 5 Acc Dip 4 RV B O FP2 15 F 30 F FP1 15 F 30 F Com1 LED5 Com2 LED5 Test Mode F1 3A P1 C PWM 1 2 3 4 5 6 7 8 ALM ALG ACC COM A...

Страница 27: ...ED PRESSURE TRANSDUCER T TEMP SENSOR LPS LOW PRESSURE SWITCH HPS HIGH PRESSURE SWITCH Hydrolink 2 Controller 24VAC DC RS 485 1 S EEV HR4 4 3 2 1 Red White Green White SA5 Black SA4 Yellow SA3 Red SA2...

Страница 28: ...splayed on the factory mounted touchscreen tablet Each chiller is equipped with a hardwire Ethernet connection that offers additional connectivity options to display chiller information without tappin...

Страница 29: ...nnected to ALG Access Relay Operation SW2 4 SW2 5 Cycles with Blower ON ON Cycle with Compressor OFF OFF Water Valve Slow Opening ON OFF Reserved OFF ON Software Features Safety Features The following...

Страница 30: ...ec recognition of the EST Condenser or Evaporator HX temperature above specified limit It is recommended that the Alarms be set 1 2 degrees off of the Fault set points so that the Alarm will trigger f...

Страница 31: ...e Flash Code 4 Load Shed Flash Code 5 ESD Flash Code 6 Future Use Flash Code 7 Future Use Configuration LED LED2 Yellow Description of Operation Configuration LED Yellow Not used Fast Flash Fault LED...

Страница 32: ...ime power measurement Watt of compressor Performance Monitoring provides entering and leaving loop water temperatures loop flow rate as well as heat of extraction or rejection rate into the loop requi...

Страница 33: ...r Soft Open Crkt Run Start or welded cont 11 Not Used 11 Yes Hard or Soft Not used ABC AXB Advanced Faults 12 Not Used 12 Not Used 13 Non CriticAXBSnsrErr 13 No Auto Any Other Sensor Err 14 CriticAXBS...

Страница 34: ...opens for 5 continuous seconds the compressor s will be immediately shut down until flow returns If flow does not return within 60 seconds the controller will issue an E 31 fault code for Source Flow...

Страница 35: ...ngle shielded twisted pair cable 22 gauge to the RS 485 card on the HydroLink Aurora on one of the chillers Daisy chain to each additional chiller BACnet The BAS will land a single shielded twisted pa...

Страница 36: ...36 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Evaporator Pressure Drop...

Страница 37: ...37 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Condenser Pressure Drop...

Страница 38: ...e has been Running for 4 Minutes Suction Temperature Discharge Pressure Super Heat Hx1 Gas Pressure Subcooling Hx1 Sat Capacity Hx2 Gas Pressure Return Water from Geo Field Hx2 Sat Hx2 Gas Temperature...

Страница 39: ...39 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Screw Refrigeration Cycle Analysis...

Страница 40: ...quare inch HC Heating Capacity in MBTUH HE Heat of Extraction in MBTUH kW kilowatt ft hd pressure drop in feet of head HR Heat of Rejection Verify the following High voltage is correct and matches nam...

Страница 41: ...is Check water flow rates and pressure drops across evaporators and condensers Verify graphical data and trending Properly document all data Annual Checks Remove and clean all waterside strainers Back...

Страница 42: ...tal Amps Comp Fan n _____ AMPS n ______ AMPS n ______ AMPS Watts m x n x 0 85 o _____ WATTS o ______ WATTS o ______ WATTS 6 CAPACITY Cooling Capacity HR o x 3 413 p _____ btu hr Heating Capacity HE o...

Страница 43: ...VERIFY ALL REFRIGERANT VALVES ARE OPEN OK NG VERIFY ELECTRICAL PANELS ARE FREE OF FOREIGN MATERIALS AND ALL WIRING IS TIGHT AND SECURE OK NG L1 L2 VOLTAGE V L1 L3 VOLTAGE V L2 L3 VOLTAGE V L1 TO GROUN...

Страница 44: ...LOAD SIDE ANTIFREEZE CONCENTRATION TYPE CONDENSER LOAD SIDE ANTIFREEZE CONCENTRATION TYPE SOURCE LOAD SIDE ANTIFREEZE CONCENTRATION TYPE APPROVAL OF ANTIFREEZE CONCENTRATION TO ADJUST FREEZE PROTECTI...

Страница 45: ...ED CONTROLS ONLY OK NG VERIFY WATER TEMPERATURES CLOSELY MATCH REFRIGERANT SAT TEMPERATURES OK NG VERIFY COMPRESSOR AND UNIT SETTINGS ARE CORRECT SEE SHEET BELOW OK NG COMPUTER STATIC IP ADDRESS IF AP...

Страница 46: ...L LEVEL OK NG MODE F ENTERING HOT WATER TEMP F LEAVING HOT WATER TEMP F ENTERING COLD WATER TEMP F LEAVING COLD WATER TEMP F COMPRESSOR 1 CAPACITY COMPRESSOR AMPERAGE A COMPRESSOR 2 CAPACITY COMPRESSO...

Страница 47: ...47 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Pages Description Date By All Document Creation 13 April 2023 MA Revision Guide...

Страница 48: ...research and development and reserves the right to change design and speci cations without notice Product TruClimate 700 Type Water Cooled Chiller 60 Hz Size 90 140 Tons Document Installation Manual I...

Отзывы: