TRUCLIMATE 700 90-140 TON INSTALLATION MANUAL
Electrical System and Controls - Safety Circuit
-
--
-
--
-
--
-
--
--
-
I
In
n
n
stantaneous Lock-Out
-
--
-
--
-
--
-
--
--
-
I
In
n
n
st
antaneous Lock-Out
--
-
--
-
--
-
--
-
-
--
-
Lock-Out after 30 sec
Chiller Safety Circuit
•
Safe Torque Off (STO)
• “motor-off”
function.
•
Inverter (VFD) is powered anytime the chiller power is on.
•
STO is wired to the compressor contactor (CC) output of the Aurora control.
•
Anytime Aurora senses a fault that would require compressor shutdown, it will trigger the STO input to turn
the motor off.
•
High Pressure Switch
•
NC below 320 psig
•
Low Pressure Switch
•
NC above 4 psig
•
Emergency Stop Switch (E-stop)
•
Wired to ABC – emergency shutdown (ES) input.
•
LED on E-stop will illuminate when tripped.
•
HydroLink will display that ABC has been put into emergency shutdown mode.
ABC Compressor Controller
Relay
Compressor
STO
VFD
Power
Compressor
VFD
Содержание TruClimate 700
Страница 2: ......
Страница 10: ...10 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data...
Страница 11: ...11 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data Service Clearance...
Страница 12: ...12 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data Center of Gravity...
Страница 13: ...13 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data Rigging Data...
Страница 25: ...25 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Wiring Schematic next page...
Страница 36: ...36 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Evaporator Pressure Drop...
Страница 37: ...37 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Condenser Pressure Drop...
Страница 39: ...39 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Screw Refrigeration Cycle Analysis...