INSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT

IG1601EW   06/16

*IG1601EW* 

 

 

997-012330-14-R

Offsets

Temperature Offsets

 – This option allows calibration (or 

deliberate miscalibration) of the room temperature 
sensor(s). There are various reasons why the 
displayed temperature would be adjusted to a higher 
or lower value. NOTE: Do not adjust for 30 minutes 
after installation because board may be heated by 
handling. The selected number is the number of 
degrees, plus or minus, which will be added to actual 
temperature. The numbers can range between -5˚ and 
+5˚. Default values are set to 0˚ offset.

 

 

Temperature Offset

 

 

Remote Indoor Offset (if sensor is attached)

 

 

Outdoor Offset (if sensor is attached)

Humidity Offset

 – This option allows calibration of the 

humidity sensor. Adjustments can range between -10% 
and +10%. Default is 0% offset.

Auto Changeover

With auto changeover, the thermostat automatically switches 
itself from heating to cooling, or vise versa, based on the 
setpoints. When setting up the thermostat you have to enter 
both a cooling setpoint and a heating setpoint. The thermostat 
will also prevent the user from setting the cooling setpoint lower 
than the heating setpoint. Mode is set to AUTO for this operation 
to work.

Auto Changeover Time

 – This setting sets the minimum off 

time before the thermostat can change from one mode 
to another. Default is 5 minutes. Range is from 5-125 
minutes in 15 minute increments. 

Auto or Manual Change

 – Default is AUTO. If MANUAL 

is chosen, you will need to change from heating to 
cooling or vise versa. When MANUAL is set, AUTO is 
removed from the MODE screen as a choice. 

USB

Allows Import and Export of Installer Settings, User Settings, 
Program, and Dealer Details. If configured as a zone thermostat 
this can also be done at the MasterStat. 

°F / °C

(NOTE: This option is not available if configured as a Zone 
Thermostat, but is available at the MasterStat.)

This screen changes the unit of measurement that is displayed 
on the thermostat. Fahrenheit is the default setting. 

Installer Setting Page Four

Press NEXT button. It will bring you to the Installer Setting page 
four.

Residential/Commercial  

For future use

Energy Demo Mode

(NOTE: This option is not available if configured as a Zone 
Thermostat, but is available at the MasterStat.)

This screen is used for demonstration purposes only. It allows 
the installer to show the user what those screens will display 
once their system is running for the time periods shown (if 
equipped with energy monitoring). Energy Demo is located 
in the installer setup screen on page 4 of 4. In the weekly 
screen, the seven days usage will be displayed across the top, 
and the current day and daily average will be displayed along 
the bottom. In the monthly screen, the 12 months usage will 
be displayed across the top, and the current month, monthly 
average, and annual total will be displayed across the bottom. 
These are just images representing energy usage, not actual 
data from the system. You can view both the weekly and 
monthly data. After approximately 5 minutes of inactivity, the 
demo mode will exit and go back to the home screen. 

Thermostat Fault Codes

NZ-1 

Humidity temperature sensor open

NZ-2 

Humidity temperature sensor shorted

NZ-3 

Outdoor temperature sensor error

NZ-4 

Humidity reading too low

NZ-5 

Humidity reading too high

NZ-6 

Humidity sensor failure

NZ-8 

Remote room sensor error

NZ-9 

Primary temperature sensor open

NZ-10 

Primary temperature sensor shorted

NZ-11 

Temperature reading too low

NZ-12 

Temperature reading too high

NZ-13 

ABC control no communication

NZ-14 

Low voltage under 19VAC

NZ-15 

Low voltage under 16VAC

NOTE:

 If you experience an NZ-11 fault, it is because the 

ambient temperature is below 40°F. To protect the compressor, 
only auxiliary electric heat will be available. Once the set point is 
met, the auxiliary electric heat will turn off, and the compressor 
will operate as intended. 

Содержание TPCC32U01

Страница 1: ...els Displayed if configured as a Zone Thermostat Comp SPD and Room Humidity only displayed if configured as a stand alone thermostat Heating Set Point Time Date Outside Temperature If installed Room Humidity Mode Comp SPD Fan Operation Error Code If present Cooling Set Point Room Temperature Zone NOTE Outdoor temperature is only displayed if an outdoor sensor is installed 1 To select a MODE press ...

Страница 2: ... energized Ranges are OFF to 20 minutes in 5 minute increments Then adjust the time of the fan is OFF Ranges are 5 40 minutes in 5 minute increments Fan ON and OFF cycles will continue until the fan has been energized by a call for heating or cooling Humidity NOTE This option is not available if configured as a Zone Thermostat but is available at the MasterStat The humidity function must be enable...

Страница 3: ...ttings Set Date and Time NOTE This option is not available if configured as a Zone Thermostat but is available at the MasterStat NOTE If this thermostat is installed with an AWL and Time Synchronization is enabled then Date and Time will be updated via the internet and cannot be manually adjusted If AWL Time Synchronization is disabled or no AWL is installed then follow the steps below for setting...

Страница 4: ... CANCEL button 3 Press the OK to return to the previous menu USB This screen allows you to import or export the User setting or Program Superboost Variable Speed Heat Pumps Only NOTE This option is not available if configured as a Zone Thermostat but is available at the MasterStat Superboost can be found under the main menu settings of the thermostat The Superboost option temporarily enables a lar...

Страница 5: ...bled Installer Information Advanced Features Safety Considerations Improper wiring or installation may damage thermostat Wiring must conform to local and national electrical codes Introduction The thermostat is a wall mounted low voltage thermostat which maintains room temperature by controlling the operation of a heating and air conditioning system Batteries are not required temperature and mode ...

Страница 6: ...4VAC Hot DX Communication ABC Controller Thermostat Connection DX Communication TPCC32U01 Color Touchscreen Thermostat Thermostat Connections C 24V Common for Control Circuit R 24V Supply for Control Circuit DX Communication Terminal DX Communication Terminal S1 S2 Remote Temperature Sensor indoor or outdoor WARNING Before installing thermostat turn off all power to unit There may be more than one...

Страница 7: ... operates in the HEAT mode and DEHUMIDIFY operates in COOL mode NONE Neither is active Restart The Restart button is used to load firmware updates and give the capability to reboot the thermostat without cycling power to the heat pump Installer Setting Page Two Press NEXT button It will bring you to the second page of installer setting Cycles Per Hour NOTE This option is not available on variable ...

Страница 8: ... terminals Compressor Satisfy NOTE This option is not available if configured as a Zone Thermostat Normal allows compressor downstaging from Y2 to Y1 Recommended setting for most products Y2 Finish Once the heat pump has engaged Y2 the thermostat will not allow downstaging to Y1 The call is satisfied in Y2 Option not available on variable speed systems Installer Setting Page Three Press NEXT butto...

Страница 9: ...one Thermostat but is available at the MasterStat This screen changes the unit of measurement that is displayed on the thermostat Fahrenheit is the default setting Installer Setting Page Four Press NEXT button It will bring you to the Installer Setting page four Residential Commercial For future use Energy Demo Mode NOTE This option is not available if configured as a Zone Thermostat but is availa...

Страница 10: ...igure Aurora System screen Yes Yes No Install communicating thermostat Do you have an AID tool No Get an AID tool Yes Which of these do you have TST ABC AXB IZ2 AOC MOC EEV Wire non communicating 8 wire thermostat to P1 terminal on the ABC board Is the thermostat communicating Yes No Issue resoled Variable Speed unit Single and Dual Capacity unit Y Active Communication N Device has been found but ...

Страница 11: ...ride and the TST removed from the Configure Aurora System screen No Yes Yes Replace the ABC board Replace the thermostat DX R C DX 1 2 3 4 C R Can you send a picture of the ABC P7 connector and thermostat wiring connections Review and confirm the thermostat is wired correctly Check the continuity of the thermostat wires by removing wires from the green plug at ABC P7 and wire tying wires 1 and 2 t...

Страница 12: ...01EW 06 16 IG1601EW 997 012330 14 R NOTES 2016 WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 WaterFurnace has a policy of continual product research and development and reserves the right to change design and specifications without notice ...

Отзывы: