INSTRUCTION GUIDE: COLOR TOUCHSCREEN COMMUNICATING THERMOSTAT
IG1601EW 06/16
*IG1601EW*
997-012330-14-R
Dealer
This screen allows the dealer to input their contact information
to be viewed by the homeowner.
Status
Displays the equipment status for MODE and FAN as well as
temperature status for ROOM TEMP and REMOTE TEMP,
OUTDOOR TEMP if applicable.
Restore Defaults
This will allow you to revert to the factory default settings.
Fan with Heat (For Dual Fuel Applications)
Options are ON or OFF. This selection determines whether G
(fan) output is to be ON or OFF when W (auxilliary heat) output
is ON.
Humidity Settings
(NOTE: This option is not available if configured as a Zone
Thermostat, but is available at the MasterStat.)
If your system is setup with a humidifier, or you desire a
dehumidification option, select the appropriate setting.
HUMIDIFY
DEHUMIDIFY
BOTH (H or DH)
NONE
Humidify
- Turns on the H output when the room humidity is
below the set point and MODE is set to HEAT, EHEAT,
or AUTO when Heating was the last mode run.
Dehumidify
– Turns on the DH output when the room
humidity is above the set point and the MODE is set to
COOL or AUTO when Cool was the last mode run.
– Turns on Active Dehumidification
(variable speed heat pumps only)
Both
– HUMIDIFY operates in the HEAT mode and
DEHUMIDIFY operates in COOL mode.
NONE
– Neither is active.
Restart
The Restart button is used to load firmware updates and give
the capability to reboot the thermostat without cycling power to
the heat pump.
Installer Setting Page Two
Press NEXT button. It will bring you to the second page of
installer setting.
Cycles Per Hour
(NOTE: This option is not available on variable speed systems
or if configured as a Zone Thermostat)
This feature will not allow more than the specified number of
equipment cycles per hour. Values can range from 4 or 6 (or 1
cycle every 15 minutes (default) or 1 cycle every 10 minutes, if
6 is set). Factory default setting is 4. This default selection will
provide optimum performance in nearly all installations.
Differential
(NOTE: This option is not available if configured as a Zone
Thermostat, but is available at the MasterStat.)
This adjustment will vary the number of degrees, from the set
point, before a call for heating or cooling is made. Adjustments
can range between 0.2˚ and 4˚ differential. Default is 0.5˚ offset.
(If your set point is 70˚F in heating, your thermostat will not call
for heat until the temperature is 69.5˚F, with a 0.5 differential).
Auto/Manual
Default is AUTO. If MANUAL is chosen, you will need to change
from heating to cooling or vice versa. When MANUAL is set,
AUTO is removed from the MODE screen as a choice and
AUTO CHANGEOVER will not be selectable in the installer
screens.