WaterFurnace GeoLink FC1-GL Скачать руководство пользователя страница 20

20

FLOW CENTER INSTALLATION AND LOOP FLUSHING MANUAL

 “P” Series/ “E” Series equipment includes freeze protection thermistors to protect the water-to-refrigerant heat exchang-

er (coax) from damage caused by freezing liquid. Be sure the “Loop/Well” DIP switch is in the “Loop” position if antifreeze is 
used and in the “Well” position if plain water is used in the loop.

Selection of the antifreeze solution for closed loop earth coupled systems requires the consideration of many important 

factors which have long-term implications on the performance and life of the equipment. Each area of concern leads to a 
different “best choice” of antifreeze. The fact is that there is no “ideal” antifreeze and any choice will require compromises in 
one area or another. Some of the factors to consider are:

Safety—

The toxicity and fl ammability of the brine (antifreeze 

solution of any type).

Thermal performance—

The heat transfer and viscosity effects 

of the brine.

Cost—

The prices vary widely.

Corrosiveness—

System materials must be compatible with the brine.

Stability—

Will the brine require periodic change out or maintenance?

Convenience—

Is the brine available and easy to transport and install?

Codes—

Will the brine meet local and national regulatory standards?

The following are some general observations about the types of brine presently being used:

Methanol—

Considered toxic in pure form, good heat transfer, low to mid price, fl ammable in concentrations greater than 

25%, non-corrosive, low viscosity.

Ethanol (Environol 1000 and 2000)—

Good heat transfer (slightly less than methanol), high price, fl ammable in concentra-

tions greater than 25%, non-corrosive and low viscosity.

Propylene glycol—

Nontoxic-noncorrosive, expensive, hard to handle when cold, poorest heat transfer, has formed “slime-

type” coatings inside pipe. Poor heat transfer has required its removal in some systems.

GS4 (Potassium acetate)

 

Due to its low surface tension, GS4 is known to leak through mechanical fi ttings and most 

thread sealants. It is corrosive when exposed to air. The manufacturer does not recommend use of GS4 with its products.

Note:

 Consult with your representative or distributor if you have any questions regarding antifreeze selection, or any com-

ments to report about problems or success with any particular methods.

Antifreeze Selection And Use

Type

Size

Volume

(U.S. Gal/100’ Pipe)

Volume 

(Liters/10 Meters)

Copper

1" CTS

4.1

15.5

Copper

1.25" CTS

6.4

24.2

Copper

1.5" CTS

9.2

34.8

Polyethylene

.75" - IPS SDR 11

3.0

11.4

Polyethylene

1" - IPS SDR 11

4.7

17.8

Polyethylene

1.25" - IPS SDR 11

7.5

28.4

Polyethylene

1.50" - IPS SDR 11

9.8

37.1

Polyethylene

2" - IPS SDR 11

15.4

58.3

Approximate Fluid Volume per 100’ of Pipe

Type

Minimum Temperature for Freeze Protection

10

°

 F (-12.2

° 

C)

15

°

 F (-9.4

° 

C)

20

°

 F (-6.7

°

 C)

25

°

 F (-3.9

°

 C)

Methanol*

25%

21%

16%

10%

Environol™ 1000* (premix)

100%

87%

72%

48%

Environol™ 2000* (pure)

27%

24%

20%

13%

Antifreeze Requirements

Notes: 

Not all currently available in all areas. All % are by volume.

Caution: Use extreme care when open-
ing, pouring and mixing fl ammable 
antifreeze solutions. Remote fl ames or 
electrical sparks can ingnite undiluted 
antifreezes and vapors. Use only in 
a well-ventilated area. Do not smoke 
when handling fl ammable antifreezes. 
Failure to observe safety precautions 
may result in fi re, injury or death.

Содержание GeoLink FC1-GL

Страница 1: ...ng and Charging Procedures Unit Pressure Drop Tables Antifreeze Use Troubleshooting Flow Centers FC1 GL FC2 GL FC1 FPT FC2 FPT FC1 FPTB FC2 FPTB Flush Cart LFC F Flow Center Installation and Loop Flus...

Страница 2: ...Flow Center Model Nomenclature Flow Center Type GL 1 GeoLink Connections w high impact polystyrene cabinet FC 1 GL Number of Pumps FPT 1 Female Pipe Thread Connection w metal cabinet FPTB 1 Female Pi...

Страница 3: ...menclature 2 General Installation Information 4 7 Electrical 8 9 Flush Cart Information 10 Flushing and Charging 11 14 Initial Start up 15 16 Unit Pressure Drop Tables 17 18 Troubleshooting 19 Antifre...

Страница 4: ...s Various fittings are available for FC1 GL and FC2 GL units for loop connections See Adapter Sets table below and Connection Options table page 5 for all adapter fittings Typically one pump flow cent...

Страница 5: ...ough center of brackets into one stud Finished wall drywall mounting notes The flow center can be mounted by using two lag screws through drywall into stud through center holes in top and bottom of ca...

Страница 6: ...UAL Figure 2a FPT Style Flow Center Three Way Valve Position Indicator 1 FPT Access Ports for Flushing 1 FPT Fittings 4 Typical HEAT PUMP CONNECTIONS GROUND LOOP CONNECTIONS 12 38 4 25 13 58 5 88 3 25...

Страница 7: ...P FLUSHING MANUAL Figure 2b GL Style Flow Center A B C D E F G H INCHES 15 0 10 3 7 0 14 0 2 0 2 6 5 0 4 5 CM 38 1 26 0 17 8 35 6 5 1 6 7 12 7 11 4 TYPE SHIPPING WEIGHT FC1 GL 26 LBS FC2 GL 31 LBS Gen...

Страница 8: ...PB1 as shown in Figure 4 The pumps will automatically be cycled as required either by the unit or by a signal from another unit sharing the same flow center Electrical Information Compressor Contacto...

Страница 9: ...it S C Figure 5 Pump Connection Option Figure 6 Pump Connection Option Multiple Units On One Flow Center When two units are connected to one loop pumping system pump control is automatically achieved...

Страница 10: ...ions 1 PVC braid Valves 1 high flow ball valves Pump Drain Integral petcock valve Priming Drilled into pump volute housing integral petcock valve to bleed air Tubing 1 Copper type L Hand Truck Industr...

Страница 11: ...tank reservoir A drop of more than 2 inches indicates that there is air in the loop Power flushing can be achieved using the home s city water supply or well water connected to the flush cart This use...

Страница 12: ...e direction only Flush the lowest portion of the system first Depending upon the individual layout this could be the loop or the unit Restart pump Once you have a steady flow of water on the return si...

Страница 13: ...er Remove caps from flow center access ports Connect flush cart hoses to access ports Position valve stems as shown below Proceed with steps 4 through 8 on page 12 Rotate the flow center valves to iso...

Страница 14: ...er length of garden hose to the other port in the flow center leading to drain Flush flow center and unit with domestic water until all air is removed Close boiler drain valve on discharge hose and pr...

Страница 15: ...d Perform this by deadheading the pump by closing the return hose ball valve This will increase the pressure on the loop via the flush cart pump As the pressure will fluctuate with the seasons higher...

Страница 16: ...hurt the performance However insufficient flow can significantly reduce capacity and possibly even damage the heat pump in extreme conditions Notes Pressure temperature gauges should be lubricated wi...

Страница 17: ...5 16 0 5 8 13 4 E EZ Dual Capacity E036 Low 4 0 1 0 2 2 5 0 1 5 3 4 E036 High 7 0 2 8 6 5 9 0 4 5 10 4 E048 Low 6 0 1 9 4 4 9 0 3 5 8 1 E048 High 9 0 3 5 8 1 12 0 5 6 12 9 E060 Low 8 0 2 0 4 6 11 0 2...

Страница 18: ...0 6 2 14 3 V L X 015 3 0 1 6 3 6 4 0 2 1 4 9 V L X 018 4 0 2 0 4 7 5 0 3 4 7 9 Versatec V L X 024 4 5 3 1 7 2 6 0 6 0 13 9 Horizontal V L X 030 6 0 2 4 5 4 8 0 3 8 8 8 V L X 036 7 0 3 6 8 3 9 0 5 3 1...

Страница 19: ...shaft is rotating Flush the loop to eliminate the air Add pump capacity Replace Check for leaks add fluid flush loop in the earth loop need more than 3 psi Change type of antifreeze Switch Thermostat...

Страница 20: ...slightly less than methanol high price flammable in concentra tions greater than 25 non corrosive and low viscosity Propylene glycol Nontoxic noncorrosive expensive hard to handle when cold poorest h...

Страница 21: ...With reference to 60 F water courtesy of Carbide and Carbon Chemicals Corporation Antifreeze Selection and Use cont 35 10 5 0 10 15 20 25 30 100 90 80 70 60 50 40 30 20 0 10 F by Volume 5 Figure 16 En...

Страница 22: ...16458 6 48 4 77 13165 46 38 35 10 19 19690 20 22 7 79 17206 7 00 4 98 13763 48 21 78 8 13 17954 7 54 5 20 14361 50 23 39 8 47 18703 8 10 5 42 14960 BRINE 4 20 METHANOL 30 F Viscosity 0 002 lbm ft sec...

Страница 23: ...8962 1 65 1 87 6413 0 87 1 43 5603 0 30 0 91 4479 10 27 79 6 31 12419 9 73 4 06 9958 1 99 2 08 7126 1 04 1 59 6225 0 36 1 01 4976 11 32 83 6 94 13661 11 50 4 46 10953 2 35 2 28 7838 1 23 1 74 6848 0 4...

Страница 24: ...of continuous product research and development and reserves the right to change design and specifications without notice Product Flow Center Installation and Loop Flushing Type FC1 GL FC2 GL FC1 FPT F...

Отзывы: