15
7 SERIES 700A11 INSTALLATION MANUAL
Auxiliary Heat Ratings
Auxiliary Heat Electrical Data
Model
kW
Stages
Btu/h
Min CFM
Model Compatibility
208V
230V
208V
230V
036
048
060
EAL(H)10
7.2
9.6
2
24,600
32,700
1100
•
•
•
EAL(H)15
10.8
14.4
3
36,900
49,100
1250
•
•
•
EAL(H)20
14.4
19.2
4
49,200
65,500
1500
•
•
Air flow level for auxiliary heat (Aux) must be above the minimum cfm in this table
Order the “H” part number when installed on horizontal and vertical rear discharge units
6/1/12
Model
Supply
Circuit
Heater Amps
Min Circuit Amp
Max Fuse (USA)
Max Fuse (CAN)
Max CKT BRK
208 V
240 V
208 V
240 V
208 V
240 V
208 V
240 V
208 V
240 V
EAL(H)10
Single
34.7
40
53.3
60
60
60
60
60
60
60
EAL(H)15
Single
52.0
60
75
85
80
90
80
90
70
100
L1/L2
34.7
40
53.3
60
60
60
60
60
60
60
L3/L4
17.3
20
21.7
25
25
25
25
25
20
30
EAL(H)20
Single
69.3
80
96.7
110
100
110
100
110
100
100
L1/L2
34.7
40
53.3
60
60
60
60
60
60
60
L3/L4
34.7
40
43.3
50
45
50
45
50
40
50
All heaters rated single phase 60 cycle and include unit fan load
All fuses type “D” time delay (or HACR circuit breaker in USA)
6/1/12
Electrical Data
Model
Rated
Voltage
Voltage
Min/Max
Compressor
Drive
HWG
Pump
FLA
Ext Loop
FLA
Blower
Motor
FLA
Total Unit
FLA
Minimum
Circuit
Amp
Max Fuse
HACR
Breaker
LRA
CMCC
LRA
Internal
Breaker
036
208-230/60/1
187/253
10.2
18.0
22.0
30.0
0.4
5.4
4.0
31.8
37.3
40
*036
208-230/60/1
187/253
10.2
18.0
22.0
30.0
0.4
5.4
7.0
34.8
40.3
45
048
208-230/60/1
187/253
12.0
23.5
28.0
35.0
0.4
5.4
7.0
40.8
47.8
50
060
208-230/60/1
187/253
12.0
30.0
33.0
40.0
0.4
5.4
7.0
45.8
54.1
60
*With optional 1 hp ECM Motor
Rated Voltage of 208/230/60/1
HACR circuit breaker in USA only
All fuses Class RK-5
3/26/12