ENVISION POOL HEATER INSTALLATION MANUAL
Field connections must comply with national and local
codes. The work must be done by a qualified electrician.
The pool heater must be permanently grounded
and bonded.
Use copper conductors only.
Disconnect all power sources before performing any work
on unit.
Standard Power Supply: 230/60/1
Electrical Connections
Wiring Main Power Supply
1. Remove the screws from the plastic front panel, located
on the control display side of the unit.
2. Remove the screws from the front panel of the
control box.
3. Route weather tight flexible conduit through the
opening at the base of the unit. Connect conduit to the
bottom of the electrical control enclosure to accept
either a 3/4 in. or 1 in. fitting. Mounting conduit directly
to the electrical control enclosure will ensure a moisture
tight seal, extending the life of the heater.
4. Attach grounding conductor to the ground lug provided
inside the electrical control enclosure.
5. Install L1 and L2 input conductors to the input lugs of
the compressor contactor.
6. Connect bond wire (at least #8 solid copper wire) from
bond lug on the right side of coil header plate to the
pool pump bonding terminal or other suitable location.
NOTE:
According to NEC 680-22, all metal surrounding a
pool including pumps, handrails, rebar, etc. must be bonded
together to eliminate any difference in potential between
the parts. If a pool is properly installed, it has a bonding
grid established.
Electrical Data
NOTES:
HACR circuit breaker in USA only
Model
Rated
Voltage
Voltage
Min/Max
Compressor
Fan Motor
FLA
Total Unit
FLA
Min
Circ Amp
Max
Fuse/HACR
MCC
RLA
LRA
0750
208-
230/60/1
187/253
20.5
11.6
74.0
2.8
14.4
17.3
25
1100
33.0
21.1
105.0
2.8
23.9
29.2
50
1250
36.0
23.0
130.0
2.8
25.8
31.6
50
1500
45.0
29.0
130.0
2.8
31.8
39.1
60
1750
42.0
26.9
145.0
2.8
29.7
36.4
60