ENVISION POOL HEATER INSTALLATION MANUAL

Startup Procedures

Before proceeding with this section make certain all 

plumbing connections are airtight and leak-free.

Flow rates should not exceed 70 gpm maximum. Use of 

an external bypass is necessary at 70 gpm and above. 

Minimum flow rate is 20 gpm.

•  Turn filter pump time clock to the ON position and set filter 

pump hours. For initial heating, the pool heater and filter 

pump may need to run continuously until your desired 

temperature is reached. After initial heating is achieved, the 

heater will run only to maintain desired temperature.

•  Turn power supply to heater ON.

•  The amber Standby LED will be activated.

•  Select POOL or SPA and set your desired water 

temperature by scrolling either up or down.

•  If your programmed water temperature is above the 

actual water temperature, the red HEAT LED will light up 

indicating HEAT mode. The can will start, and then the 

compressor will start.

NOTE:

 Each time the compressor turns off, it is protected 

by a 3 – 5 minute anti-short cycling delay.

Initial Heating

Initial heating may require you to run your heater and 

filter pump continuously for at least 24 hours, or more, 

depending on the following factors:

•  Temperature difference between actual water 

temperature and desired water temperature

•  Size of pool

•  Ambient air temperature, the cooler the air temperature, 

the longer the heating time

•  Heat loss (evaporative, convective, radiative, and 

conductive)

•  A pool cover/solar blanket may reduce initial heating 

time by up to 50%

Defrost Cycle

The heat pump pool heater has automatic defrost. When 

the outdoor temperature drops below 40°F, frost may 

start to form on the evaporator coil. Frost buildup will be 

heaviest on humid days when the temperature is between  

35 – 40°F. During the defrost cycle, the Defrost LED will be 

illuminated to indicate that the unit is defrosting. During 

this time the fan is funning and the compressor is inactive.

Internal Protection Analyzers

The heater is equipped with internal devices to monitor 

and protect the integrity of the unit. Should an abnormal 

condition occur, these devices will interrupt the operation 

of the unit and may display the appropriate code on the 

control panel.

Reducing Heat Loss - Pool Cover/Solar Blanket

We highly recommend the use of a pool cover/solar 

blanket. Covering your pool is the single most cost effective 

means of reducing heat costs from 50 – 70%. Heating 

a pool without a cover is like heating a house without a 

roof. They also reduce the amount of maintenance costs. 

By reducing evaporation, covers reduce the quantity of 

chemicals needed. Because evaporation accounts for about 

70% of pool heat loss, the beneficial effect of using a pool 

cover/solar blanket can be dramatic.

Wind Speed Reduction

Reducing wind velocity at the water surface reduces 

convective and evaporative losses. Fences, trees, hills, 

or tall hedges close to the pool perimeter are effective 

windbreaks. Locate these obstructions to take maximum 

advantage of their effectiveness as windbreaks, without 

shading the pool surface from the sun.

Содержание Envision

Страница 1: ...Installation Information Water Piping Connections Chemical Use Electrical Startup Procedures Preventive Maintenance Troubleshooting IM1009PN 04 13 Envision Pool Heater Installation Manual Pool Heater...

Страница 2: ......

Страница 3: ...llation 5 Dimensional Data 6 Physical Data 6 Water Flow and Connections 7 Chemical Use 7 Electrical Connections 8 Electrical Data 8 Electronic Control Panel 9 Modes of Operation 9 Wiring Schematic 10...

Страница 4: ...T Titanium Rev 18 April 2013D Performance Data Model GPM High Ambient Low Ambient EWT 80 F EAT 80 6 70 7 F EWT 80 F EAT 50 44 2 F Capacity BTUH COP Capacity BTUH COP 0750 22 50 000 6 0 31 000 4 0 110...

Страница 5: ...consumes in electrical power In addition it will still warm your pool even as outdoor temperatures drop into the 40s The information in this manual was prepared to assist in the proper installation o...

Страница 6: ...0 32 9 24 5 38 0 26 0 2 ID PVC UNION 1100 1750 32 9 32 5 38 0 34 0 2 ID PVC UNION 04 11 13 NOTE All dimensions are in inches Physical Data Model 0750 1100 1250 1500 1750 Compressor Reciprocating Scrol...

Страница 7: ...ain Skimmer Check Valve Chlorine Gas Trap Ball Valves Filter Pump In Out Heat Pump Pool Heater Heat Pump Pool Heater In Out Pump Filter From Main Drain Skimmer Return Ball Valve For Flow Rates Greater...

Страница 8: ...ht seal extending the life of the heater 4 Attach grounding conductor to the ground lug provided inside the electrical control enclosure 5 Install L1 and L2 input conductors to the input lugs of the c...

Страница 9: ...inal strip and install the remote control system The mode jumper must be on pins 3 4 for this mode of operation See the Terminal Strip and Mode Configuration Pins illustration for pin settings 4 3 2 1...

Страница 10: ...Remote Automation Microprocessor Control TEST PIN CC HP LP DC WT FS1 FS2 Field Installed Flow Switch See Table 1 Remote Automation Jumper P1 P2 P3 PIN 1 2 3 Field Installed home automation control See...

Страница 11: ...conductive A pool cover solar blanket may reduce initial heating time by up to 50 Defrost Cycle The heat pump pool heater has automatic defrost When the outdoor temperature drops below 40 F frost may...

Страница 12: ...breakers or replace fuses if necessary 2 Check to be sure the electronic control panel is set properly The unit must be in either the POOL or SPA mode and the desired temperature must be set above th...

Страница 13: ...13 ENVISION POOL HEATER INSTALLATION MANUAL Notes...

Страница 14: ...e By 4 Added Nomenclature 19 Apr 2013 DS 4 Added Performance Data 19 Apr 2013 DS 6 Added Dimensional and Physical Data 19 Apr 2013 DS 8 Updated Electrical Data 19 Apr 2013 DS 15 Added New Warranty 19...

Страница 15: ...of the unit D Malfunction or damage due to negligence abuse freezing conditions accident or acts of God E Malfunction of damage from plants or animals F Malfunction or damage from the attachment of a...

Страница 16: ......

Страница 17: ...llation Do not mail the warranty certi cate Mail To WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 Fax To 800 934 9934 Is Pool Covered Yes No Circle One Is Pool Screened...

Страница 18: ......

Страница 19: ......

Страница 20: ...l Inc 9000 Conservation Way Fort Wayne IN 46809 www waterfurnace com 2013 WaterFurnace International Inc 9000 Conservation Way Fort Wayne IN 46809 9794 WaterFurnace has a policy of continual product r...

Отзывы: