Compressor Fixed On Delay Time
The Compressor Fixed On Delay Time will ensure that the
compressor output (B02) is not enabled for 90 seconds
after the control receives a call to start the compressor.
This delay is adjustable from 30 – 300 seconds over a BAS
or a MUI. If the control is in test mode the Compressor Fixed
On Delay Timer will be shortened to 5 seconds.
Compressor Minimum On Delay
The compressor minimum on delay will ensure that the
compressor output is enabled for a minimum of two (2)
minute each time the compressor output is enabled. This
will apply in every instance except in the event the high
pressure switch is tripped or emergency shutdown then the
compressor output will be disable immediately.
Compressor Short Cycle Delay Time
The compressor short cycle time delay will ensure that
the compressor output will not be enabled for a minimum
of five (5) minutes after it is disabled. This allows for
the system refrigerant pressures to equalize after the
compressor is disabled.
Heating Cycle
On a call for heating, the blower enable output and
accessory output 2 will turn on immediately after the
random start delay timer has been satisfied. If the
compressor short cycle time delay has been satisfied,
the compressor will turn on after the blower enable and
accessory output 2 are on and the fixed compressor start
delay timers have been satisfied.
NOTE:
Auxiliary heat output
can be controlled over the BAS.
Set Point Control Mode
In set point control mode the reversing valve output
will be disabled. As the temperature drops below the
heating set point and begins to operate in the heating
proportional band, the compressor (low capacity for
two-stage compressors) output (BO-2) will be enabled.
For units with two-stage compressors, a PI loop in the
programming of the control will determine when the full
capacity compressor output (BO-4) is to be enabled.
The compressor must be operating in low capacity
for a minimum of 30 seconds before the full capacity
compressor output can be enabled. During low capacity
compressor operation the variable speed ECM blower
will operate in medium speed and will operate in high
speed when the compressor is operating at full capacity.
Thermostat Control Mode
In thermostat mode the compressor will be cycled
based on Y1 and Y2 calls from a room thermostat.
When the control receives a Y1 command (BI-7) from
the thermostat the low capacity compressor output
(BO2) will be enabled and the variable speed ECM
blower will operate in medium speed. When the control
receives a Y2 command (BI-8) from the thermostat the
variable speed ECM blower will operate in high speed.
During the heating cycle the reversing valve will be
commanded into the off position.
Cooling Cycle
On a call for cooling, the blower enable output and
accessory output 2 will turn on immediately after the
random start delay timer has been satisfied. If the
compressor short cycle time delay has been satisfied,
the compressor will turn on after the blower enable and
accessory output 2 are on and the fixed compressor start
delay timers have been satisfied.
Set Point Control Mode
In set point control mode the reversing valve output
will be enabled. As the temperature rises above the
cooling set point and begins to operate in the cooling
proportional band, the low capacity compressor output
(BO-2) will be enabled. A PI loop in the programming
of the control will determine when the full capacity
compressor output (BO-4) is to be enabled. The
compressor must be operating in low capacity for
a minimum of 30 seconds before the full capacity
compressor output can be enabled. During low capacity
compressor operation the variable speed ECM blower
will operate in medium speed and will operate in high
speed when the compressor is operating at full capacity.
Thermostat Control Mode
In thermostat mode the compressor will be cycled
based on Y1 and Y2 calls from a room thermostat.
When the control receives a Y1 command (BI-7) from
the thermostat the low capacity compressor output
(BO2) will be enabled and the variable speed ECM
blower will operate in medium speed. When the control
receives a Y2 command (BI-8) from the thermostat the
full capacity compressor output will be enabled and the
variable speed ECM blower will operate in high speed.
During the cooling cycle the reversing valve will be
commanded into the “ON” position.
Variable Speed ECM Blower Operation
Blower speeds will be selected through the user interface or
the facility management system. There will be a total of 12
speeds selectable with only three being selected at any one
time. The lowest numbered speed selection set to ON will
select the low-speed blower setting, the middle selection
set to ON will select the medium-speed blower setting and
the highest selection set to ON will select the high-speed
blower setting. If all selections are set to OFF
Controls - FX10 (optional) cont.