TROUBLESHOOTING GUIDE 

cont’d:

 12.   Control valve fails to 

draw in regenerant

 A. Injector is plugged

 A.  Remove injector and clean or replace

 B.  Faulty regenerant piston

 B.  Replace regenerant piston

 C. Regenerant line connection leak

 C. Inspect regenerant line for air leak

 D.  Drain line restriction or debris cause excess 

back pressure

 D.  Inspect drain line and clean to 

correct restriction

 E. Drain line too long or too high

 E.  Shorten length and or height

 F. Low water pressure

 F.  Check incoming water pressure – water 

pressure must remain at minimum of 25 psi

 13.   Water running to 

drain

 A. Power outage during regeneration

 A.  Upon power being restored control will finish 

the remaining regeneration time. Reset time of 
day. If PC board has battery back up present 
the battery may be depleted. See front cover 
and drive assembly drawing for instructions.

 B. Damaged seal/stack assembly

 B.  Replace seal/stack assembly

 C. Piston assembly failure

 C. Replace piston assembly

 D. Drive cap assembly not tightened in properly

 D.  Retighten the drive cap assembly

 14.   E1, Err – 1001, 

Err – 101 = 
Control unable 
to sense motor 
movement

 A.  Motor not inserted fully to engage pinion, 

motor wires broken or disconnected

 A.  Disconnect power, make sure motor is fully 

engaged, check for broken wires, make sure 
two pin connector on motor is connected to the 
two pin connection on the PC board labeled 
MOTOR. Press NEXT and REGEN buttons for 
3 seconds to resynchronize software with piston 
position or disconnect power supply from PC 
board for 5 seconds and then reconnect.

 B. PC board not properly snapped into drive bracket

 B.  Properly snap PC board into drive bracket and 

then Press NEXT and REGEN buttons for 3 
seconds to resynchronize software with piston 
position or disconnect power supply from PC 
board for 5 seconds and then reconnect.

 C. Missing reduction gears

 C.  Replace missing gears

 D. Board unable to read middle reduction gear

 D.  Check foil on reduction gear; make sure no film 

is covering foil on reduction gear

 E. Defective Optical Encoder

 E. Replace PC board

 15.   E2, Err – 1002, Err – 

102 = Control valve 
motor ran too short 
and was unable to 
find the next cycle 
position and stalled

 A. Foreign material is lodged in control valve

 A.  Open up control valve and pull out piston 

assembly and seal/stack assembly for 
inspection. Press NEXT and REGEN buttons for 
3 seconds to resynchronize software with piston 
position or disconnect power supply from PC 
board for 5 seconds and then reconnect.

 B. Mechanical binding

 B.  Check piston and seal/stack assembly, check 

reduction gears, check drive bracket and main 
drive gear interface. Press NEXT and REGEN 
buttons for 3 seconds to resynchronize software 
with piston position or disconnect power supply 
from PC board for 5 seconds and then reconnect.

 C. Main drive gear too tight

 C.  Loosen main drive gear. Press NEXT and 

REGEN buttons for 3 seconds to resynchronize 
software with piston position or disconnect 
power supply from PC board for 5 seconds 
and then reconnect.

 PROBLEM 

CAUSE 

CORRECTION 

Содержание Ion Pro Series

Страница 1: ...Ion Pro and CareClear Pro Series Water Filters For Models IPHS IPFE IPG IPCG AN CCP CCP AN...

Страница 2: ...ty 30 Quick Reference Guide 31 32 Your WaterCare water filters are precision built high quality products These units will deliver filtered water for many years to come when installed and operated prop...

Страница 3: ...y Remaining and Days to a Regeneration are optional displays but are not normally used Vacation Mode is used only when there will be no water usage for an extended period of time If activated once 50...

Страница 4: ...regeneration water to the unit while also providing untreated water to the distribution system Fig 1 2 BYPASS POSITION The inlet and outlet handles point to the center of the bypass The system is iso...

Страница 5: ...een its outlet and the inlet of a water heater CAUTION To protect the unit in the event of a hot water heater backup the manufacturer recommends the use of an expansion tank on the outlet side of the...

Страница 6: ...low control fitting and solder joints Failure to do this could cause interior damage to the flow control Backwash of an automatic filter can be directed into a septic tank in most cases but because of...

Страница 7: ...regeneration which comes into contact with the chlorine pellets dissolves them and is then drawn into the filter to disinfect the system periodically and then safely rinsed away We recommend the use...

Страница 8: ...neration initiation will be called for on that day even if a sufficient number of gallons were not used to call for a regeneration Set Day Override using or buttons 3 is recommended set number of days...

Страница 9: ...t OFF as the default This feature is used to signal service into the future This is typically set by the installing dealer to warn homeowner that service is required after a preset number of gallons h...

Страница 10: ...ushing and holding the REGEN button for three seconds while in the Backwash Air cycle will skip the remaining mini steps and proceed to the next cycle of regeneration which is usually Backwash The sys...

Страница 11: ...system goes through a regeneration cycle based on the days override value 6 DEALER NAME AND PHONE NUMBER is the dealer information to call when service is needed this screen will only appear if set by...

Страница 12: ...ed with an audible alarm and visual alarm This alarm is set by the installing dealer and is used to warn of pending service based on gallons or time To turn off alarm If the audible alarm sounds press...

Страница 13: ...o media level when filling Do not overfill The additional media added should not be higher than two thirds of the tank height when measuring from the bottom see diagram Once the right height has been...

Страница 14: ...board C Restricted stalled meter turbine C Remove meter and check for rotation or foreign material D Meter wire not installed securely into three pin connector D Verify meter cable wires are installed...

Страница 15: ...in regenerant tank G Check refill setting in programming Check refill flow control for restrictions or debris and clean or replace H Damaged seal stack assembly H Replace seal stack assembly I Contro...

Страница 16: ...r 3 seconds to resynchronize software with piston position or disconnect power supply from PC board for 5 seconds and then reconnect B PC board not properly snapped into drive bracket B Properly snap...

Страница 17: ...on A Drive bracket not snapped in properly and out enough that reduction gears and drive gear do not interface A Snap drive bracket in properly then Press NEXT and REGEN buttons for 3 seconds to resyn...

Страница 18: ...iston position or disconnect power supply from PC board for 5 seconds and then reconnect 20 Err 109 A Invalid motor state detected A Replace PC board 21 Err 201 A Invalid regeneration cycle step detec...

Страница 19: ...buttons 1 CV3837 01 CareClear Pro cover blue buttons 1 2 CV3107 1 Motor 1 3 CV3106 1 Drive bracket spring clip 1 4 CV4062WX PC board 1 5 CV3110 Drive gear 12 x 36 3 6 CV3109 Drive gear cover 1 7 CV30...

Страница 20: ...w 1 CV3407 1 25 piston assembly downflow 1 5 CV3174 Regenerant piston 1 6 CV3180 O ring 337 1 7 CV3105 O ring 215 1 CV3358 O ring 219 1 25 distributor 8 CV3556 Screw 1 4 20x1 1 2 18 8SS 1 9 CCI 003183...

Страница 21: ...on Qty 1 CV3151 Nut 1 quick connect 2 2 CV3150 Split ring 2 3 CV3105 O ring 215 2 4 CV3145 Bypass rotor 1 2 5 CV3146 Bypass cap 2 6 CV3147 Bypass handle 2 7 CV3148 Bypass rotor seal retainer 2 8 CV315...

Страница 22: ...0 1H H injector assembly GREEN CV3010 1I I injector assembly ORANGE CV3010 1J J injector assembly LIGHT BLUE CV3010 1K K injector assembly LIGHT GREEN not shown CV3170 O ring 011 lower not shown CV317...

Страница 23: ...1 0 DLFC for 3 4 elbow CV3162 013 1 3 DLFC for 3 4 elbow CV3162 017 1 7 DLFC for 3 4 elbow CV3162 022 2 2 DLFC for 3 4 elbow CV3162 027 2 7 DLFC for 3 4 elbow CV3162 032 3 2 DLFC for 3 4 elbow CV3162...

Страница 24: ...1 Turbine assembly 1 4 CV3105 O ring 215 1 5 CV3003 01 Meter plug assembly 1 6 CV3013 Optional mixing valve 1 REPLACEMENT PARTS Although no tools are necessary to assemble or disassemble the valve the...

Страница 25: ...LY Item No Part No Description Qty 1 CH4600 50 474 safety float valve 1 2 CH4640 32 474 float assembly 1 3 CH4500 48 474 air check 1 4 CN1043 10 pad for feeder 1 5 CH7001 Grid for feeder 1 REPLACEMENT...

Страница 26: ...51 Nut 1 quick connect 2 2 CV3150 Split ring 2 3 CV3105 O ring 215 2 4 CV3188 Fitting 2 3 4 BRASS SWEAT Item No Part No Description Qty CV3007 03 3 4 brass sweat assembly 2 1 CV3151 Nut 1 quick connec...

Страница 27: ...Bite assembly 2 1 CV3151 Nut 1 quick connect 2 2 CV3150 Split ring 2 3 CV3105 O ring 215 2 4 CV3629 Fitting 2 3 4 BRASS SHARK BITE Item No Part No Description Qty CV3007 12 3 4 brass Shark Bite assem...

Страница 28: ...19 0 22 0 Continuous Flow GPM 3 0 3 0 5 0 3 0 3 0 5 0 2 Peak Flow GPM 6 0 8 0 10 0 6 0 8 0 10 0 Backwash Flow GPM 6 5 9 0 11 0 6 5 9 0 11 0 3 Iron Removal 4 0 4 0 4 0 4 0 4 0 4 0 4 Hydrogen Sulfide Re...

Страница 29: ...1 4 x 1 8 21 lb 1 4 x 1 8 14 lb 1 4 x 1 8 14 lb 1 4 x 1 8 21 lb 1 4 x 1 8 Gravel Amount Size No 2 7 lb 20 7 lb 20 7 lb 20 7 lb 20 7 lb 20 7 lb 20 Continuous Flow GPM 5 0 5 0 6 0 6 0 7 0 11 0 Peak Flo...

Страница 30: ...xpense and return part freight collect The above provisions of the warranty are valid as long as the unit is connected in compliance with local plumbing codes and in an equivalent manner and condition...

Страница 31: ...N TIME MINUTES SET TIME HOUR SET 2 00 AM MANUAL REGENERATION NOTE For softeners if brine tank does not contain salt fill with salt and wait at least two hours before regeneration If you need to initia...

Страница 32: ...d button simultaneously 2 Adjust hardness using and buttons 3 Press NEXT 4 Adjust days between regenerations using and buttons 5 Press NEXT 6 Adjust time of regeneration hour with and buttons AM PM to...

Отзывы: