Surge Counter & Smart Detector
FAQ & Help (2/2)
5. I have question for Surge Counter how the minimum of Input Current for testing?
Surge count test of minimum input current:
It is tested in the factory with a 1.2/50μs + 8/20μs combination wave generator
If it is only to test the digital display of the surge count, a 10μF 400V capacitor can be used, refer to the following steps
Note: This method cannot simulate 8/20μs surge waveform.
Step 1: Turn on the power switch to charge the capacitor for 1 second
Step 2: Turn on the power switch to make the capacitor short-circuit discharge
www.watchfuleyesolutions.com - Page D2 - Back to TOP -