MODEL WPMZ-5-□□□-□□-□□□
8/12
IM-0834-03
10-2.
AVAILABLE UNITS
The WPMZ has selectable 62 units.
Unit
μA,mA,A,kA,μV,mV,V,kV,VA,W,kW,MW,
μm,mm,cm,m,Ω,kΩ,MΩ,g,kg,N,kN,MN,
Pa,kPa,MPa,hPa,J,kJ,MJ,Hz,kHz,MHz,m
3
,
mm/s,mm/min,cm/min, m/s,m/min,m/h,m/s
2
,
m
3
/s,m
3
/min,m
3
/h,kg/h,kg/m
2
,kg/m
3
,N/m
2
,
ℓ,ℓ/s,ℓ/min,ℓ/h,%,%
0
,%RH,
℃
,
pH,ppm,rpm,t,inch
10-3.
SETTING OPERATION
Setting procedure is same as “
8. BASIC OPERATIONS FOR
SETTING DISPLAY
”. Operate in the track of SETTING DIPLAY.
11.
COMPARATIVE OUTPUT FUNCTION
Settings of comparative output functions needs 10 parameters to
set for each output.
The following describe only main setting parameters and refer to
detailed manual which can be downloaded from our homepage for
other parameters.
11-1.
LOCATIONS OF PARAMETERS FOR COMPARATIVE
OUTPUT FUNCTION SETTING
1st layer
2nd layer
3rd layer
4. Output
settings
Comparative output AL1
(
Comparative output AL2
)
(
Comparative output AL3
)
(
Comparative output AL4
)
pattern select
output source display
value
camparison mode
compare ON condition
compare judgement value
campare ON delay
campare OFF delay
output mode
output logic
compare ON background
color
*Refer to “7. SETTING LAYER OVERVIEW”
11-2.
SETTING OF OUTPUT SOURCE DISPLAY VALUE
Comparative outputs AL1-AL4 are settable independently and
they have no magnitude relationship.
For example, instantaneous measured value of Ach is assigned to
AL1, instantaneous measured value of Bch is assigned to AL2
and instantaneous calculate value is assigned to AL3,4 and so on.
Every display item can be freely assigned to comparative
outputs.
Setting procedure is same as “8. BASIC OPERATIONS FOR
SETTING DISPLAYS”. Operate in the track of the procedure of
SETTING DISPLAYS.
Caution: COM (emitter) terminal is common for AL1-AL4 in
open-collector output products. Each AL1&2, AL3&4 have
common terminal in relay ouput products.
11-3.
COMPARISON JUDGEMENT VALUE
The comparison judgement value is a threshold value to judge.
Although, the setting procedure is same as “8. BASIC
OPERATIONS FOR SETTING DISPLAY”, comparison
judgement values need the settings of numerical values.
Therefore, its procedure is shown below.
*
The following is an explanation for the compare mode of “Level
judgement ”.
●
Level judgement action
Comparative
Output
Comparison
type
Comparison
formula
judgement
result
AL1
alarm when
over
display value
>
AL1
judgement value
AL1 ON
AL2
alarm when
over
display value
>
AL2
judgement value
AL2 ON
AL3
alarm when
under
display value
<
AL3
judgement value
AL3 ON
AL4
alarm when
under
display value
<
AL4
judgement value
AL4 ON
*
Refer to “17. SPECIFICATIONS –output specifications
[comparative output]”
(Measurement display)
ENTER
Moves to setting display(1st layer)by
MENU key.
ENTER
Moves to 2nd layer by right
arrow key.
Moves to 4th
layer by right
arrow key.
Moves to numerical value
setting display by ENTER key.
Selects numerical
value by arrow keys
(up/down/left/right)
Registers selected numerical
value by ENTER key.
Returns to 3rd
layer by left
arrow key.
Stores selected parameters
and returns measurement
display by MENU key.
1st layer
3rd layer
MENU
1st layer
Moves to 3rd
layer by right
arrow key.
2nd layer
3rd layer
4th layer
4th layer(numerical value setting)
4th layer
3rd layer
MENU
Returns to 2nd layer by
left arrow key.
Moves to other setting items
by up/down arrow keys.
4th layer(numerical value setting)
Moves to setting
“2.output” by down
arrow keys.
Moves to “Threshold
value” by down arrow keys.
AL1 Hysteresis
Display value
AL1 Judgement value(Over)
AL2 Hysteresis
AL2 Judgement value(Over)
AL3 Hysteresis
AL3 Judgement value(Under)
AL4 Hysteresis
AL4 Judgement value(Under)
AL2
AL1
AL3
AL4
J
ud
ge
m
en
t
re
su
lt