Installation manual
Measure with a pressure measuring instrument (manometer) with an empty drum and with a program without heat.
By opening and closing the damper (B) the pressure at the heating sensor (NTC sensor) (A) is either lowered or
raised.
The optimum drying performances are achieved when the measured static pressure correspond to the value listed in
the following table.
Heating / Frequency
Static pressure in NTC sen-
sor position (Pa)
Resulting Nominal air flow cold empty machine (m
3
/h)
Electric / 50 Hz
500
1140
Electric / 60 Hz
1150
1140
Gas / 50 Hz
750
1140
Gas / 60 Hz
1150
1140
Steam / 50 Hz
900
1380
Steam / 60 Hz
1100
1380
Alternative measuring meathod
Adjusting the air flow may only be carried out by authorized personnel.
Use a home made U tube manometer, a hose (max
⌀
10 mm), with water. Insert one end of the hose in the hole, hold
the hose according to the picture so that the water is in level.
Start the machine and measure the difference between the water in one of the hose ends with the other.
1 mm = 10 Pa.
X mm
fig.7528
When the dryer is adjusted remount the heating sensor (NTC sensor) (A) and lock the damper (B) in the new position
with the screws.
Remount the lower back panel.