1.3.2
Output limitations due to gas feed pressure and lower
heating value
Fig 1-2
Output limitations for gas feed pressure and LHV, 480/500kW per cylinder
NOTE
The above given values for gas feed pressure is before the engine (after the gas
regulating unit).
No compensation (uprating) of the engine output is allowed, neither for gas feed
pressure higher than required in the graph above nor lower heating value above
36 MJ/m
3
N
.
Values are given in m
3
N
is at 0 °C and 101.3 kPa.
If the gas pressure is lower than required, a pressure booster unit can be installed
before the gas regulating unit to ensure adequate gas pressure. If pressure arise
is not possible the engine output has to be adjusted according to above.
A 18 kPa higher gas feed pressure is required per 10 °C higher charge air receiver
temperature, due to increased charge air pressure.
1-4
Wärtsilä 34DF Product Guide - a16 - 23 September 2016
Wärtsilä 34DF Product Guide
1. Main Data and Outputs
Содержание WARTSILA 34DF
Страница 1: ...WÄRTSILÄ 34DF PRODUCT GUIDE ...
Страница 20: ...This page intentionally left blank ...
Страница 50: ...This page intentionally left blank ...
Страница 58: ...This page intentionally left blank ...
Страница 98: ...This page intentionally left blank ...
Страница 142: ...This page intentionally left blank ...
Страница 152: ...This page intentionally left blank ...
Страница 160: ...This page intentionally left blank ...
Страница 192: ...This page intentionally left blank ...
Страница 198: ...This page intentionally left blank ...
Страница 204: ...This page intentionally left blank ...
Страница 218: ...This page intentionally left blank ...
Страница 224: ...This page intentionally left blank ...
Страница 226: ...This page intentionally left blank ...
Страница 229: ......
Страница 230: ......
Страница 231: ......