10) Press the first threaded linkage nut into the socket on the
actuator rail and hold. The dovetail on the threaded linkage
nut must fully engage the groove on the linkage base track.
Press the front linkage lock nut into the socket on the actuator
rail and hold. The teeth on the front linkage lock nut must
engage the lowest teeth possible on the linkage base track.
The dovetail on the front linkage lock nut must fully engage
the groove on the linkage base track. Tighten the socket
head cap screw hand tight. Repeat for the second threaded
linkage nut. The number of teeth visible on the linkage base
tracks below the front linkage lock nuts should be the same
on both sides. If the number of teeth visible on the linkage
base tracks below the front linkage lock nuts is not the same
on both sides, loosen the socket head cap screws then repeat
this step.
11) Tighten both 4 mm socket head cap screws to 44 in-lbf torque.
12) Use actuator manual override to verify the metal actuator
stem touches the top of the stem adapter (See manual
override on page 3).
WARNING: DO NOT FORCE OR TURN THE MANUAL
OVERRIDE WHEN THE MANUAL OVERRIDE
BUTTON IS NOT PRESSED. DOING SO MAY CAUSE
DAMAGE TO THE ACTUATOR GEARS.
13) Lock stem connector clamp, use fingers on the front and
back sides of black lock assembly to evenly lower the lock
assembly.
WARNING: WHEN HANDLING THE ACTUATOR TAKE
CARE NOT TO DAMAGE THE STEM CONNECTOR
CLAMP AND CROSS BAR ASSEMBLY.
14) Install orange travel indicators (Item 8) on embossed actuator
rail above and below travel indicator cross bar. Push orange
travel indicators on leg of actuator to contact cross bar.
15) Connect power and signal to actuator. (See also Set-Up on
page 12)
16) Press the Adaption (Auto Calibration) button on the actuator
and wait until the cycle is complete.
17) Stroke valve several times to check operation.
18) Return line pressure to valve.
REMOVAL & INSTALLATION OF ACTUATOR AND LINKAGE BASE
Содержание E025
Страница 16: ...16 2600 Emrick Blvd Bethlehem PA 18020 USA 800 922 0085 www warrencontrols com D3400024...
Страница 17: ...17 HVAC_BAC_ELECTRIC_IOM_RevE_0421 D3400025...
Страница 25: ...25 HVAC_BAC_ELECTRIC_IOM_RevE_0421 E024 and E029 E031 ON OFF CONTROL...
Страница 26: ...26 2600 Emrick Blvd Bethlehem PA 18020 USA 800 922 0085 www warrencontrols com NOTES...
Страница 27: ...27 HVAC_BAC_ELECTRIC_IOM_RevE_0421 NOTES...