To access advances setting,
PRESS
and
HOLD
and simultaneously for 5 seconds.
PRESS
SET
to navigate through the different advanced settings. Use or to adjust the setting.
PRESS OK
to
exit advanced settings
Display Function
Range
Default
CL
Display temperature calibration
-4 °C - + 4 °C
0
bL
Backlight
1 = (OFF) 2 = (ON) 3 = (Always ON)
2
AF
Sensor selection
A = Air sensor
F = Floor sensor AF = Air with
floor limit**
AF
AH
Set maximum settable temperature
for floor sensor (F), air sensor (A)
and air sensor with floor limit (AF)
Floor Sensor
(F) + 18°C - + 35°C
Air Sensor/Air Sensor with Floor Limit
(A/AF) + 18°C - + 45°C
F = (45°C)
A = (35°C)
AF = (35°C)
FL
Minimum floor
temperature limit
Floor Sensor (F) + 5°C - + 20°C
10°C
FH
Maximum floor
temperature limit
Floor Sensor (F) + 25°C - + 50°C
50°C
PS
Weekly schedule day selection
3 = (1-5 Block, 1 + 1) 7 = 7 Days
3
CS
No. of programs per day
P4 = 4 Programs per day / P6 = 6 Programs per day
P4
CF
Select °Celsius / °Fahrenheit
C = °Celsius / F = °Fahrenheit
°C
CO
Set 24hr
/
12hr Clock
24h / 12h
24h
LD
Set heating load*
HH = (16 - 12 A), H = (11 - 8 A), L (
≤
7 A)
H
SE
Sensor Selection
100 = 100K / 10 = 10K sensor
100
To reset advanced settings to factory default
PRESS
and
HOLD
for 3 seconds when the thermostat is idle and the
heating schedule mode is displayed, .
ConF
will flash,
PRESS OK
to accept.
* Failing to set the Heating Load correctly will reduce the accuracy of the thermostats air temperature reading
** To view current floor temperature when the thermostat is set to AF (Air with floor limit),
PRESS
and
HOLD
for 3
seconds
Advanced Settings
Troubleshooting
Code Fault
Action
E1
Floor sensor short circuit in type F or AF
Check the sensor resistance and replace if it is damaged. Expected
resistance: 100kΩ at 25°C, 125.5kΩ at 20°C, 157.4kΩ at 15°C
E2
Floor sensor not installed or broken in
type AF
Check the sen
sor resistance and replace if it is damaged. Expected
resistance: 100kΩ at 25°C, 125.5kΩ at 20°C, 157.4kΩ at 15°C
E3
Air sensor short circuit
Exchange device or operate using floor sensor only
E4
Air sensor damaged
Exchange device or operate using floor sensor only
E5
Wrong floor sensor installed
Remove floor sensor and install a 100K or 10K floor sensor
2
Open Window Function -
The
Warmup One features open window function which detects when there is a sudden drop
in temperature (1.5°C or more within 3 minutes) when a window is opened and will switch your heating off saving
you energy. The heating will reactivate if the temperature increases again (1.5°C in 30 minutes).
PRESS
any button to
return to heating schedule mode.