background image

21

warmhaus.com

Figure 31 

Exhaust gas discharge through the building chimney and fresh intake from the building chimney with split 

flue sets

Attention:

 The minimum usable 

diameter must not be under 80 mm 

or equivalent for the vertical duct 

supplying the combustion air.

Attention:

 

a)  nominal working combustion product temperature : > 70°C max 

conditions 

b) overheat combustion products temperature : 105° C

c)  the minimum length of the specified connecting ducts; 1 mt / maximum 

length of the specified connecting ducts; 10 mt

d) For size/shape of the end of the fitting please refer 2.2.14. Installation with 

Vertical Flue Sets page 13, Fig.26.

e)  Please re adjust TsP Paramater P22 = Flues gas pipe length ( value 1 = 1 

meter ) according to actual flue lenght  

f)  Its MUST to use NON RETURN valve ON the flue gas system. 

g) non-return valve function has to be checked annually by authorised 

service.

Information for the design of the common duct system for a 

type C(10) boiler

a)  The boiler is designed to become connected to a common duct system 

that is designed to operate where the static pressure in the common flue 

duct might exceed the static pressure in the common air duct by 25 Pa 

under the condition that n-1 boilers are running at maximum nominal heat 

input (Qn,max) and 1 boiler at the minimum heat input allowed by the 

controls

b) combustion product mass flow rate at maximum nominal heat input are 

given technical table.

c)  combustion product mass flow rate at minimum heat input allowed by the 

controls are given technical table.

d) G20 : CO2 or O2 content of the combustion products at nominal operating 

conditions 9 % ( +0,5/-0,5 )  

G30 / G31 : CO2-content; 10.00 % ( tolerance : +%0,5 / -0,5 % )

e)  minimum allowable pressure difference between combustion product 

outlet and air inlet shall be declared as -200 Pa (including -100 Pa wind 

pressure).

General for connection of a type C(10) boiler to a common duct 

system

Characteristics and the applications of the common duct system to which 

the boiler can be connected, with at least the following information:

a)  the flue duct system shall be CE marked and comply with EN 15502 

standart 12.2.1.4.111.2;

b) nominal combustion products temperature for dimensioning the common 

duct system shall be declared as 25 °C;

c)  the combustion product mass flow rate at maximum heat input shall be 

specified for every connection point; the terminal of the common duct 

shall be designed to induce a draft;

d) condensate flow into the boiler is allowed;

e)  maximum allowable recirculation rate of 10 % under wind conditions;

f)  the maximum allowable pressure difference between combustion 

product inlet and air outlet of the common duct system shall not be 

exceeded when n-1 boilers are running at maximum nominal heat input 

(Qn,max) and 1 boiler at the minimum heat input allowed by the controls;

g) the common flue duct shall be appropriate for an overpressure of at least 

200 Pa;

h) the duct system shall not include a draft diverter.

Warning:

  the boiler if it is installed as a C (10) boiler  and IF / when the 

boiler is disconnected the air outlet and the combustion product inlet 

openings shall be closed and checked on tightness. 

C

C

10

Содержание MINERWA 25

Страница 1: ...MINERWA 25 CONDENSING COMBI BOILER INSTALLATION USER MANUAL...

Страница 2: ...2 warmhaus com MINERWA 25...

Страница 3: ...Emptying Radiator Installation 15 2 3 3 Circulation Pump 17 2 4 CONTROLS FOR INITIAL OPERATION OF COMBI BOILER 18 2 5 COMBI COMPONENTS 18 2 6 COMBI BOILER FLUE CONNECTIONS 19 2 6 1 Exhaust Gas Flue Pi...

Страница 4: ...ers authorized by a gas company located at your city should be preferred for performing project and etude studies In order to enable use of the combi boiler with LPG bottles or LPG tanks conversation...

Страница 5: ...g more detailed information regarding legal regulations on installation of gas fired heating devices www warmhaus com Manufacturer WARMHAUS Is tma ve So utma Sistemleri Tic A Bursa I ktepe OSB Mah Par...

Страница 6: ...L3B P Natural Gas 20 mbar G20 Available DE YES I 2L Natural Gas 25 mbar G25 Available NL YES I 2E Natural Gas 25 mbar G25 Available BE FR YES I 2ELL Natural Gas 20 mbar G25 Available DE YES II 2L3P Na...

Страница 7: ...2H3B P Buthane Gas 50 mbar G30 Available AT CH SK YES II 2E3B P Buthane Gas 50 mbar G30 Available DE YES II 2L3B P Buthane Gas 30 mbar G30 Available NL YES II 2ELL3B P Buthane Gas 50 mbar G30 Availabl...

Страница 8: ...es operating with natural gas and your gas meter Immediately evacuate the place with gas odour Natural Gas Emergency Line from your neighbour or another suitable place Do not make any intervention on...

Страница 9: ...mm 110 mm 379 mm 595 mm 201 mm 129 mm 125 mm 575 mm 598 mm 89 mm 150 11 606 000076 G3 4 GAS G3 4 G3 4 G1 2 G1 2 MODE RESET Do not leave packing materials plastic nylon bags etc at places to be reached...

Страница 10: ...ll brick wall according to installation scheme and with connection screws and not to be used for other purposes In case of using different materials for installation combi boiler shall be out of the w...

Страница 11: ...gn substances therefore required filter systems must be available in the gas supply line for ensuring purification of the fuel 2 2 7 In Case of Using LPG Tank For heat requirements over 24 kW LPG tank...

Страница 12: ...e downwards Figure 8 Combi boiler bottled gas connection LPG LPG Ball Valve COLLECTOR 370 mmH2O 2 kg Hood 12 kg or 24 kg LPG BOTTLE 2 2 9 Filling the siphon for Condensation Line After hanging the boi...

Страница 13: ...h connection of the combi boiler and electrical connections not being made by a competent electrician in accordance with directives and standards in force Also ensure that the electricity installation...

Страница 14: ...WHEN THE TIMER OR OPENTHERM ROOM THERMOSTAT CONNECTED THE BOILER ROOM THERMOSTAT ORANGE WHITE GREEN W W O O G G COMBI BOILER CONTROL ACCESSORIES RC07 Modulated Weekly Program Scheduled Cable room the...

Страница 15: ...ombi boiler can function at minimum 0 5 bar tap water pressure and that corresponds to a very low flow rate and therefore it is quite probable that the requested tap water temperature can not be provi...

Страница 16: ...al Drain Gulley or Rainwater Hopper 45 cross sectional drainage pipe outlet Open air flusher Figure 15 Outside Connection of Condensate Water Drainage Pipe SECTION 2 INST Outdoor flusher Condensate Wa...

Страница 17: ...r Min 19 mm Inner pipe 75 mm flusher bathroom shower drainage combined with other drainage lines Minimum 30 mm Inner pipe Water Air proof insulation 25 Distance under grid 45 pipe termination 75 100 F...

Страница 18: ...3 DHW Filter 34 DHW Inlet 1 3 4 5 6 7 8 10 14 2 18 20 21 24 26 29 30 31 32 34 19 15 16 13 33 9 11 12 23 27 28 25 17 22 Figure 23 Components of Combi Boiler 2 4 CONTROLS FOR INITIAL OPERATION OF COMBI...

Страница 19: ...alled without suitable protection against UV and weather conditions to distances over 40 cm and exteriors Every pipe is defined with an explanatory and discriminative Warmhaus mark mentioned in remark...

Страница 20: ...t system to which the boiler can be connected condensate flow into the appliance is not allowed Maximum allowable temperature of combustion air 40 C maximum allowable recirculation rate of 10 under wi...

Страница 21: ...heat input allowed by the controls are given technical table d G20 CO2 or O2 content of the combustion products at nominal operating conditions 9 0 5 0 5 G30 G31 CO2 content 10 00 tolerance 0 5 0 5 e...

Страница 22: ...nal on the same wall 1500 N Horizontally from a terminal on the same wall 300 R From adjacent wall to flue vertical only 300 S From an adjacent opening window vertical only 1000 T Adjacent to windows...

Страница 23: ...3_1 press down and tighten the screw Fig 33_6 to secure the flue elbow see picture B Fit the outer and inner wall flanges Fig 33_13 14 on the terminal pipe Fig 33_12 Connect flue to the boiler positio...

Страница 24: ...ndard Flue Set Elbow 90 b Flue Extension Pipe c Additional 90 Elbow d Standard Flue Set Pipe Figure 38 II Two 90 elbow sample flue installations d a b c a b c d 9 m Figure 37 I Single 90 bended sample...

Страница 25: ...connections 60 100mm vertical flue set should not exceed 11 m A 60 100 mm L max 11 m A Figure 40 Vertical flue set installation ATTENTION For C3 boilers the terminal outlets from separete combustion...

Страница 26: ...alent length L8 0 5 m L9 0 5 m 45 elbow equivalent length L10 1 5 m L11 1 0 m 90 elbow equivalent length L12 1 5 m L Total 12 m 12 m Lmax 30 m Correct in implementation Figure 42 Hermetic flue type in...

Страница 27: ...e flue pipe The flue and air pipes must extend by at least 40 mm from the wall surface Condensing boiler emit a visible plume of water vapour from the flue terminal this is normal It is the responsibi...

Страница 28: ...0 100 Condensing Flue Extension L 1000 mm 153 11 660 600111 Black 153 11 660 600015 White 153 11 660 600118 Grey 60 100 Condensing Flue Extension L 2000 mm 153 11 660 600112 Black 153 11 660 600016 Wh...

Страница 29: ...3 11 660 600091 80 Condensing Twin Flue Extension Pipe L 1000 mm 80 mm L 1000 mm 153 11 660 600092 80 Condensing Twin Flue Extension Pipe L 2000 mm 80 mm L 2000 mm 153 11 660 600093 80 Twin Flue Elbow...

Страница 30: ...rminal Kit With 1 m Extension and Two Brackets 153 11 660 6000 31 Plume Displacement Kit Elbow 900 153 11 660 6000 32 Plume Displacement Kit Elbow 450 153 11 660 6000 33 Plume Terminal 153 11 660 6000...

Страница 31: ...assageway check that combustion products will not cause a nuisance and that the terminal will not obstruct the passageway 3 If a terminal is less than 2 metres above a balcony above ground or above a...

Страница 32: ...or control device is connected ensure that it is at ON position If you will shut off the combi boiler for a long period perform below written operations Discharge the radiator installation water not c...

Страница 33: ...liminating the failure in case of combi boiler failure MODE Used for Winter Summer OFF mode adjustment Operating modes and related notifications OPERATING MODES EXPLANATIONS CLOSED or OFF WINTER Radia...

Страница 34: ...s started flame modulation symbol is seen at the middle section of the screen At that position you can increase and decrease the temperature with CH temperature adjustment buttons see Figure 40 3 betw...

Страница 35: ...ons c Failing to follow instructions given in this book and room thermostat booklets Important It is compulsory to have two different lines according to legal regulations being in force regarding elec...

Страница 36: ...ng passive active In order to rapidly prepare DHW faster and reducing the cold water consumption during waiting grid water is heated in the plate exchanger and ready hot water is stored Activation of...

Страница 37: ...e has a drain cock first turn the boiler off and let the pressure drop to 1 1 5 bar then switch it on again 4 If the pressure increase occurs again call an authorized service E 04 Domestic heating wat...

Страница 38: ...E 11 Gas valve modulator disconnected Boiler does not work E11 error code flashing on the screen Gas valve harness 1 Call for authorised service 2 Check gas valve between board and gas valve E 13 Exh...

Страница 39: ...aximum allowed consecutive lock out reset reached Usable RESET number reached Too many consecutive lock out failures followed by reset due to other possible causes 1 Removing power supply reset will b...

Страница 40: ...me from out side room units or thermosad bridge etc 1 Reset Restart boiler 2 Call for authorised service E 62 Calibration request Boiler does not work E62 error code flashing on the screen Calibration...

Страница 41: ...blem on electronic gas valve driver Boiler does not work E80 error code flashing on the screen Electronic board Gas valve failiure 1 Call for authorised service at first E 81 Lock out for combustion p...

Страница 42: ...or code flashing on the screen Aging or rust on the electrode Recirculation on fluegas path Blokage on flue or wrong flue Electrode position Cabling disconnections Combustion calibration Electronic bo...

Страница 43: ...on Combustion calibration 1 Call for authorised service at first E 96 Flue or air suction way blockage Boiler does not work E96 error code flashing on the screen Blokage on flue Blokage on air suction...

Страница 44: ...om as you wish and also you can acquire approximately 6 power saving with every degree of temperature decrease Ventilation Do not leave windows slightly open for ventilating room rooms In such case co...

Страница 45: ...hall be performed against payment Our distinguished customer we believe the importance of providing good products to you as well as rendering good services Recommendations and Data to be Followed 1 Wh...

Страница 46: ...0 l h flow rate mH2O 7 Pump pressure at 500 l h flow rate mH2O 7 3 Max Pump Flow Rate h 2500 Pump Energy Efficiency Index EEI 0 20 Domestic Hot Water Circuit Maximum DHW Heat Input kW 31 Minimum DHW H...

Страница 47: ...ntained in this product information is applicable and valid Electricity Fuel Natural Gas G20 HANDING OVER After completing the installation and commissioning of the system the installer should hand ov...

Страница 48: ...n Qfuel kWh 14 809 23 152 Annual fuel consumption AFC GJ 11 18 Condensing boiler Yes Yes Low temperature boiler Yes Yes Combination boiler Yes Yes B1 Boiler No No Room boiler with combined heat and po...

Страница 49: ...49 warmhaus com 3 10 ENERGY LABEL...

Страница 50: ...50 warmhaus com...

Страница 51: ...nt have been carefully prepared but we reserve the right to make changes and improvements in our products which may affect the accuracy of the information contained in this leaflet All goods are sold...

Страница 52: ...Minerwa Installation User Manual code 150 11 606 000081 Revision Date R01 11 2019 MINERWA CONDENSING COMBI BOILER INSTALLATION USER MANUAL...

Отзывы: