Instructions condensing  Air heaters type HR version HR-GB-4001-a 

 

 

 

 

 

 

 

Page 

5.4  Summer ventilation 

It is possible to let the ventilator run on a certain speed in the summer. Please follow the 
instructions in the manual from the thermostat. 

5.5  High limit protection 

5.5.1 T max. Heat exchanger 

The unit contains 2 temperature protections. The NTC thermostat monitors the air temperature 
electronically. Should the temperature, as a first step, become too high, the burner will modulate 
to the minimum input and the system fan will modulate to the maximum speed. 
When the temperature still increases, the burner will switch off. The display will show E05 / E36. 
When the heat exchanger has been cooled to normal levels the burner will start automatically.  
Should the temperature increase to an unacceptable level, the heater stops. The display will 
show L31. Only after a manual reset the heater can start again. Manual reset can be done on 
the electronic circuit board or with the special Winterwarm Room thermostat 

5.5.2 T max. Flue gas 

For the application of plastic flue material on the HR heaters the maximum flue gas temperature 
is monitored (Tflue < 120 °C). A temperature sensor in the flue outlet the heater monitors the 
temperature of the flue. When the flue temperature is too high (Tflue > 110 °C), the burner 
modulates its capacity to the minimum. When the temperature keeps rising, and reaches  
115°C,  the burner stops. When after an automatic restart the situation repeats itself the heater 
will lock out. The error L-16 will be show in the display. 

5.6  Flue Transport  Supervision 

The unit is provided with a pressure switch to control the transport of combustion air through the 
heat exchanger. It checks in the pre purge phase if there is sufficient movement of combustion 
air through the heat exchanger by measuring the pressure difference over the heat exchanger. 
If the pressure difference is too low in the pre purge phase, the fault L14 will occur. This could 
mean that combustion air is leaking from the heat exchanger and so the heat exchanger must 
be checked on leakage. 

6

 

 Putting into operation and adjustment 

6.1  General 

Prior to packaging, each unit is checked in detail on safety and functioning. It is adjusted to the 
right efficiency of combustion. In general, the heater does not need to be adjusted after 
installation, only a check of functioning is necessary. Also obtain a flue gas analysis and record 
it for later reference. 

Use only a calibrated instrument !  

The CO2 value can be adjusted if the CO2 reading differs 0,3% from its setting. Do not ever 
turn injudiciously the adjusting screws! 
Adjustment of the gas control without a supporting flue gas analysis will invalidate the warranty. 
 
Once the unit is installed according this manual, the unit can be put into operation. Make sure 
the gas pipe is clean, gastight and free from air. 
Switch on the electric supply with the maintenance-switch, and open the door in order to be able 
to observe the first start-up and so become familiar with the functioning of the heater.  
Should the gas line not be purged correctly the heater will attempt to start twice before going 
into a lock-out condition. Manual reset is necessary in that case. 
 
Do not forget to instruct the end user about a safe use of the heater (presence of gas, place of 
the manual gas valve !), the operation of the heater (lock-out indication and reset) and about the 
necessary maintenance. This manual must be left with the end user.  

6.2  Start by using the thermostat 

Put the thermostat in the highest position. The start sequence is always the same 
NOTE:The heater will always burn for minimum 4 minutes before it switches off. 

Содержание HR10

Страница 1: ...on from 2019 THIS DOCUMENT MUST ABSOLUTELY BE READ BEFORE STARTING THE INSTALLATION INSTRUCT USER AND LEAVE THIS DOCUMENT WITH HEATER FOR REFERENCE Date 01 02 2019 Instruction manual version HR GB 400...

Страница 2: ...WALL TERMINAL 14 7 FUNCTIONING OF THE UNIT 17 7 1 GENERAL 17 7 2 BURNER CYCLE 17 7 3 DELTA T REGULATION TEMPERATURE CONTROLLED DE STRATIFICATION FAN 17 7 4 SUMMER VENTILATION 18 7 5 HIGH LIMIT PROTECT...

Страница 3: ...itch The main gas switch should be situated upstream in the gas line near the heater Turn off all electric power to the appliance After working on the heater always check for gas leaks Close the doors...

Страница 4: ...ke These vapours will result in corrosion of the heat exchanger and a leakage of condensate and flue gas Defects caused by this are not covered by guaranty Please consult your supplier This is also th...

Страница 5: ...fficiency s flow 97 6 96 4 94 6 95 0 94 8 94 6 Seas space heating efficiency 90 4 90 1 88 7 89 9 89 2 89 4 NOx emission GCV mg kWh 30 21 33 40 31 44 NOX class 5 5 5 5 5 5 Flue amount max kg hr 19 4 31...

Страница 6: ...Electrical current A 3 9 4 4 4 7 Emission efficiency s flow 95 5 95 6 95 5 Seas space heating efficiency 88 8 89 0 89 1 NOx emission GCV mg kWh 38 33 36 NOX class 5 5 5 Flue amount max kg hr 128 4 160...

Страница 7: ...0 20 575 795 670 565 575 650 125 470 545 M10 4x M10 M10 115 140 110 100 105 Gas 3 4 ext INO80 OUTO80 325 400 180 35 85 180 815 470 650 125 4X M10 565 670 1065 Gas 3 4 ext 100 115 105 110 140 35 85 IN...

Страница 8: ...the heater The heater can be installed horizontally or on an angle of maximum 45 degrees downwards When the heater is installed other than horizontal Always re adjust the CO2 setting from the gas val...

Страница 9: ...4001 a Page B 150 390 A C XR10 30 XR40 60 HR10 20 HR30 40 A 550 665 B 640 815 C 800 990 Available suspensions Standard bracket for type HR10 to 40 Design bracket type HR10 and 20 Horizontal horizontal...

Страница 10: ...working and standing supply pressure must be a minimum of 17 mbar and a maximum of 30 mbar measured at the inlet pressure nipple of the gas control in the heater In case the heater needs to be convert...

Страница 11: ...ir can circulate free pass the thermostat Take notice that the sun does not shine directly upon the thermostat in the winter Do not place the thermostat on a cold wall Place the thermostat on an inner...

Страница 12: ...se one flue pipes from the same diameter as the flue spigots on the heater Different manufacturers have different connections systems from the flue pipes It is not allowed to combine systems from diff...

Страница 13: ...HOH 110 HR10 up to 60 horizontal discharge art IA8216 HR10 up to 60 vertical discharge art IA8214 roof distance 0 5m IA8217 The following flue terminals are allowed 1775 O200 990 O130 HOH 225 max 300...

Страница 14: ...ensate should be drained away to the sewer The condensate outlet from the heater should never be closed Protect the condensate drain from freezing Ice can also close the condensate drain To be sure th...

Страница 15: ...nnection Make sure that the gasket is not damaged Ensure that the flue tube and the air inlet tube are not exchanged the flue tube is the pipe in the centre of the flue terminal 10 Finally secure the...

Страница 16: ...y with allowed lubricant from the manufacturer Maximum 1 of soap or water is allowed ATENTION Do not use grease Vaseline or oil Fixation Fix every elbow on or near the socket Exception when connecting...

Страница 17: ...nd starts to modulate 9 Minimum Before the flame stops the burner will modulate to minimum power 10 Burner off Gas valve closes the flame stops 11 Post Purge Burner fan purges with fresh air System fa...

Страница 18: ...there is sufficient movement of combustion air through the heat exchanger by measuring the pressure difference over the heat exchanger If the pressure difference is too low in the pre purge phase the...

Страница 19: ...de will automatically end 7 Adjusting the gas control In principle it is not necessary to adjust the gas control after putting the unit into operation In case it needs to be adjusted e g after fitting...

Страница 20: ...not react too soon and the signals of the LEDs and the code on the display on the electronic circuit board Volatile lock out Can only be reset by hand Display Explanation Cause L 0 Internal error Inte...

Страница 21: ...ive Case 2 There is not enough gas pressure The mixture of gas air is poor adjust the gas valve The gas valve does not open check during ignition for 230V on the valve Check whether the ignition elect...

Страница 22: ...me failures Check the right setting of the gas control the right CO2 setting is important for the correct ignition Check the ignition cable 1kOhm Check the setting of the ignition electrode the spark...

Страница 23: ...right The distance between the electrode and the burner should be 5 0 0 5 mm The distance between the two electrodes should be 3 6 0 4 mm Check the setting of the ignition electrode the spark has to b...

Страница 24: ...on Each heater needs his own unique number to recognise the heater by the room thermostat The number of the heater can be set by the micro switch on the heater control in the heater The number at the...

Страница 25: ...5 6 7 8 ON 0 1 1 2 3 4 5 6 7 8 ON 0 1 J14 J14 S1 S1 Heater 1 Heater 2 Heater 3 Heater 4 HR80 100 of 120 Module 1 HR80 100 of 120 Module 2 1 2 3 4 max 4 modules max 8 heaters At the first HR80 100 of...

Страница 26: ...J8 1 J8 2 J6 7 J6 14 T1 J2 1 6 J1 1 J1 5 J1 2 J1 6 J1 3 J1 7 J1 4 J1 8 J3 2 J3 6 J3 1 J3 7 J3 3 J3 8 J3 4 J3 9 J3 5 J3 10 J4 2 J4 3 J4 5 J4 4 J4 1 J4 6 J5 1 J5 2 J5 4 J5 3 4 3 1 2 J25 LED RESET 4 3 1...

Страница 27: ...0 GA3000 GA3000 GA3000 GA3000 GA3000 7 System fan IX4201 IX4201 IX4201 IH4206 IH4206 GX4207 IH4206 IH4206 GX4207 8 Main board EBM 966 GY5901 GY5901 GY5901 GY5901 GY5901 GY5901 GY5901 GY5901 GY5901 9 P...

Страница 28: ...Instructions condensing Air heaters type HR version HR GB 4001 a Page 12 4 Exploded view HR80 120 7 5 6 8 2 1 11 10 14 13 9 12...

Отзывы: