background image

3

warema_890416_alhb_en_v2•2022-10-01

We reserve the right to make technical modifications

Obligations for the disposal of electrical 

devices 

A marking with this symbol indicates the following 

obligations under the scope of legal regulations:

 

 

 

 

The owner of this electrical device must dispose of it 

separately from unsorted municipal waste for further 

recycling.

 

 

Used batteries and accumulators that are not enclosed 

in the old device, as well as lamps/bulbs that can be 

removed from the old device without breaking, must be 

disposed of separately.

 

 

Distributors of electrical devices and disposal compa-

nies are obliged to take back the equipment free of 

charge.

 

 

The owner must take it upon themselves to delete any 

personal data contained in the electrical device prior to 

disposal.

Liability

Failure to comply with the product information in these in-

structions and use of the unit in a manner that contravenes 

its intended use and purpose may result in the manufactur-

er refusing to honour warranty claims for product damage. 

In this case, liability for consequential harm to persons or 

damage to property will also be excluded. Follow the in-

structions in the operating instructions of your sun shad-

ing system. Liability is also excluded for damage to the sun 

shading system resulting from operation under icy condi-

tions.

Technical data

LONMPM 8DI/8DO

Min.

Typ.

Max.

Unit

Supply voltage

207

230

253

V AC

Network frequency

50

Hz

Current consumption with 

all relays pulled in

106

119

130

mA

Current consumption 

without relay

32

mA

Thermal fuse (primary)

115

120

125

°C

Safety class 

(with protective earth)

I

Floating output

Switching capacity at 230 

V AC / cos ϕ 1

16

A

LON

®

 input

FTT-10

Inputs, local operating elements/contacts (make contact) 

Local voltage active

8

12

15

V DC

Local current active

0.3

0.6

1

mA

Local voltage inactive

-0.5

0

1.5

V DC

Conformity

Available at 

www.warema.de/ce

This device complies with the EMC directives for use in residen-

tial and commercial areas.

Ambient conditions

Operating temperature

0

20

50

°C

Storage temperature

0

50

°C

Rel. humidity 

(non-condensing)

10

40

85

%RH

Degree of soiling

2

Connection

Supply line, drives, push 

buttons

Screwed terminals

Network

Spring terminals

Wire cross sections

Supply line, drives, push 

buttons

Max. 2.5 mm

Network

Max. 0.8 mm 

 

Housing variants

Degree of protection

AP/REG housing

IP30

Article numbers

LONMPM 8DI/8DO REG

1002816

LONMPM 8DI/8DO AP

1002817

Strain relief set for AP 

housing

1002236

WAREMA Renkhoff SE

Hans-Wilhelm-Renkhoff-Strasse 2

97828 Marktheidenfeld

Germany

210 mm

180 mm

60 mm

119 mm

184 mm

-

Fig. 6 

Dimensions of surface-mounted housing

60 mm

95 mm

90 mm

210 mm / 12 TE

  12 TE / 210mm    

Fig. 7 

Dimensions of DIN rail-mounted housing