background image

5

P100-991-400B

P100 Installation

Inlet Piping

Provide for permanent or temporary installation of a compound 

pressure  gauge  to  monitor  the  inlet  pressure.  To  maintain 

maximum flow, the pump inlet should be under flooded suction 

conditions at all times. Do not supply more than one pump 

from the same inlet line.

Supply Tank

Use a supply tank that is large enough to provide time for any 

trapped air in the fluid to escape.  The tank size should be at 

least twice the maximum pump flow rate.
Install  a  separate  inlet  line  from  the  supply  tank  to  each 

pump.
Place a cover over the supply tank, to prevent foreign objects 

from falling into it.

Hose Sizing and Routing

To minimize acceleration head and frictional losses, size the 

suction line at least one size larger than the pump inlet, and 

keep the suction line as short and direct as possible.
Recommendations:
•   Keep inlet lines less than 3 ft. (1 m) long
•   Use at least 5/8” (16 mm) I.D. inlet hose
•  Minimize fittings (elbows, valves, tees, etc.)

Inlet Piping (Pressure Feed)

Provide for permanent or temporary installation of a pressure 

gauge to monitor the inlet pressure. Pressure at the pump inlet 

should  not  exceed  50  psi  (17.3  bar).  For  higher  pressures 

install a pressure reducing valve. Do not supply more than 

one pump from the same inlet line.
Note: System back pressure must exceed the pump inlet 

pressure by at least 15 psi (1 bar) in order to prevent flow 

thru.

Discharge Piping

Hose and Routing

Use the shortest, most-direct route for the discharge line.
Select pipe or hose with a working pressure rating of at least 

1.5 times the maximum system pressure. EXAMPLE:  Select a 

1500 psi (103 bar) W.P. rated hose for a system to be operated 

at 1000 psi (69 bar) gauge pressure.
Support the pump and piping independently.

Pressure Regulation

Install a pressure relief valve in the discharge line. Bypass 

pressure must not exceed the pressure limit of the pump.
Size the valve so that, when fully open, it will be large enough 

to relieve the full capacity of the pump without overpressurizing 

the system.
Locate the valve as close to the pump as possible and ahead 

of any other valves.
Adjust the pressure relief valve to no more than 10% over the 

maximum working pressure of the system.  Do not exceed the 

manufacturer’s pressure rating for the pump or valve.
Route the bypass line to the supply tank.
CAUTION:  

Never

 install shutoff valves in the bypass line or 

between the pump and pressure regulator or relief valve.
Provide for permanent or temporary installation of a pressure 

gauge to monitor the discharge pressure at the pump.

Minimum Discharge Pressure

To  ensure  proper  capacity  control,  a  minimum  discharge 

pressure of 50 psi (3.5 bar) is required.

Содержание P100

Страница 1: ...ervice P100 991 2400B P100 Metering Pump Metallic Pump shown 1204 Chestnut Avenue Minneapolis MN 55403 TEL 612 332 5681 FAX 612 332 6937 TOLL FREE FAX US only 800 332 6812 www hydra cell com metering...

Страница 2: ...ry for performance characteristics of pumps with PTFE diaphragms Consult factory for performance specifications Gallons Per Hour GPH Maximum Flow at Designated Pressure GPH All Pumps GPH Metallic Pump...

Страница 3: ...0 1 50 1 60 1 80 1 100 1 W0036 1 2 NPT or 1 2 BSPT 3 8 NPT or 3 8 BSPT OUT IN 5 75 146 1 7 27 184 7 8 61 218 7 9 03 229 4 0 41 10 4 4X 5 65 143 5 4 50 114 3 0 78 19 8 5 90 149 9 6 50 165 1 NEMA 56C 0...

Страница 4: ...t the inlet line will not be obstructed See Inlet Piping on page 6 Positive Displacement This is a positive displacement pump To avoid severe system damage if the discharge line ever becomes blocked i...

Страница 5: ...more than one pump from the same inlet line Note System back pressure must exceed the pump inlet pressure by at least 15 psi 1 bar in order to prevent flow thru Discharge Piping Hose and Routing Use t...

Страница 6: ...tions are tight The oil reservoir beneath the reservoir diaphragm 71 is completely full NOTE The reservoir is filled and sealed at the factory If you are unsure about the oil level remove the cover 70...

Страница 7: ...lastic retainer is used Outlet Valve Insert dampening washer 10 valve seat 9 Tetra seal 7 valve 6 spring 5 and spring retainer 4 Install flat Tetra seal O ring 14 between spring retainer 4 and valve s...

Страница 8: ...Watch oil level in reservoir If oil gets too low during priming air will be drawn into piston inside hydraulic end Air will cause pump to have loss in flow and repriming will be necessary Fill oil re...

Страница 9: ...P100 991 2400B W0039 R O P100 Fluid End Parts List Bolt Torque Specifications Ref No in lbs N cm 1 90 1 017 20 14 158 22 10 113 23 14 158 W0037 W0040 W0038...

Страница 10: ...ST 1 D10 020 1017 Valve Seat inlet Hastelloy C 1 D10 020 3300 Valve Seat inlet ceramic 1 14 D10 092 2110 Tetra Seal inlet Buna 1 D10 092 2111 Tetra Seal inlet Viton 1 D10 092 2112 Tetra Seal inlet neo...

Страница 11: ...1033 Pump Housing 1 65 D10 085 2210 Key shaft 1 69 D10 038 2210 Plug drain 1 70 F20 105 1020 Cover Nameplate oil reservoir SST 1 71 F20 091 1010 Diaphragm oil reservoir 1 72 G20 090 2010 Screw cap hex...

Страница 12: ...1 112 109 Reducer 60 1 ratio 56C 1 112 110 Reducer 80 1 ratio 56C 1 112 111 Reducer 100 1 ratio 56C 1 101 112 112 Kit Protective Cover 1 102 112 116 Kit Output Flange FD 1 103 108 108 101 100 105 103...

Страница 13: ...ief valve or repair clean or replace with new relief valve Delivery Too Low and or Erratic Review all Probable Causes and Solutions in Problem 2 No Delivery above Air leak s in inlet line Locate all l...

Страница 14: ...Diaphragm Kit 6 9 5 3 2 1 8 4 Kit Designator Part Number Description Qty K D V D03 018 ___ Diaphragm 1 F20 073 ___ O ring outlet manifold 1 F20 074 ___ O ring inlet manifold 1 D03 035 ___ O ring outle...

Страница 15: ...t Avenue Minneapolis Minnesota 55403 This warranty does not cover 1 The electric motors if any which are covered by the separate warranties of the manufacturers of these components 2 Normal wear and o...

Страница 16: ...Revised 2 2007 2005 Wanner Engineering Inc Printed in USA 1204 Chestnut Avenue Minneapolis MN 55403 TEL 612 332 5681 FAX 612 332 6937 TOLL FREE FAX US only 800 332 6812 www hydra cell com metering em...

Отзывы: