7.3.3 LED indicators
■
Power-LED:
Indicates presence of supply voltage. If the LED
does not come on, please check that the power supply is
properly connected.
■
Status-LED:
Flashes whenever there is network activity of the
Web-Thermo-Hygrometer. Periodic flashing indicates that the
unit is ready.
■
Error-LED:
The Error LED uses various flash codes to indicate
error conditions on the device or network port.
1x flashing of the Error-LED
= Check network connection.
The Web-Thermo-Hygrograph is not receiving a link pulse
from a hub or switch. Check the cable or the hub/switch
port.
2x bzw. 3x flashing of theError-LED
= Perform a reset by
interrrupting power. If the error cannot be cleared, reset the
device to its factory defaults. Since this resets all network
settings, you should first write down the existing network
settings.
Config -> Session Control -> LogOut -> Restore Defaults
After a reset the device is restored to its factory defaults.
Reconfigure your network settings.
Power-LED +Status-LED +Error-LED an = Self-test error
The self-test which is performed after every start or reset of the
Web-Thermo-Hygrobarograph could not be correctly finished,
for example due to an incomplete update of the firmware. When
in this state the device is no longer operational. Please return
the unit for service.
Содержание Web-Thermo-Hygrobarograph PoE 57612
Страница 20: ...20 W T Design and positioning of the graph is configurable 2 2 Config menu...
Страница 31: ...31 W T Subject to errors and changes 3 5 1 Basic Settings 3 5 Configuration of the graphics settings...
Страница 37: ...37 W T Subject to errors and changes...
Страница 42: ...42 W T 3 8 2 Alarm X Here you configure the desired alarm conditions...
Страница 90: ...90 W T 7 6 Declaration of Conformity...