Table A-1 Approximate current requirements for electric motors
Horsepower
Running watts
Starting watts
Universal
motor*
Induction
motor
Capacitor
motor
Split-phase
motor
1/6
275
400
600
850
1200
1/4
400
500
850
1050
1700
1/3
450
600
950
1350
1950
1/2
600
750
1300
1800
2600
3/4
850
1000
1900
2600
—
1
1000
1250
2300
3000
—
1 1/2
1600
1750
3200
4200
—
2
2000
2350
3900
5100
—
3
3000
—
5200
6800
—
5
4800
—
7500
9800
—
*Small appliance
NOTE: For pumps, air compressors, air conditioners, and inverters, add at least 25% to