Instructions for installers and maintenance workers
Leaking fume connection
Impassability of the heat exchanger
Door leakage
REGU THROTTLE
SMELL OF FUMES
CONDENSATE ACCUMULATION
RELEASE LEVER CAN'T BE MOVED
It shall be displayed when the fumes temperature
approaches the upper limit, which means:
High boiler load
Uncleaned boiler walls
Clogged pipe exchanger, reduced fumes
transmission
Excessive ash in the area below the heat exchanger
Clogged chimney
Try to change the activation of heating pumps with
external control
Clean the walls of the boiler
Clean the heat exchanger
Clean the ash in the area under the heat exchanger
Clean the fume pipes
No anti-condensation protection
Wet firewood
Check the operation of the pump and mixing valve
Replace wood with a maximum humidity of 15%
Irregular cleaning of the lever (necessary at least at
each loading and addition of firewood)
Boiler overdose
Clean the heat exchanger
Firewood is added as needed
Seal the fume connection
Clean the heat exchanger
Replace the door sealing cord