background image

CAUTION: There are live circuits inside the controller even when the power switch is in the 

OFF position! Servicing and troubleshooting the controller must be performed by Qualified 

Service Personnel.

 

 

 

 

Section 3 (B): 

WEL-Transmitter Housing 

+ Electrode Reads Low or High Versus 

a Calibrated Handheld Meter; Cannot Calibrate the Electrode 

 

pH value versus mA reading 

 

  The pH analog input menu displays the mA measured by the electrode, with a 4-20 

mA range scaled to 0 to 14 pH standard units.   As a reference, please see the table 

below.  However, these reference points may change subsequent to calibration. 

 

 

 

 

 

 

  If the pH (mA) reading is not correct, using a multimeter, please check the mA signal coming 

from the sensor and into the controller as follows: 

 

  Place the WEL Transmitter Housing plus Electrode in the system tee/water, or place it in 

a buffer solution. 

 

  Power down the controller. Disconnect either the red or the black sensor lead (not the 

shield wire) and connect a multimeter in series as shown below to measure current (mA) 

 

  Power up the controller.  The multimeter will display the mA going to the controller from 

the sensor.   

 

o

  If the mA value is stuck on one value, no matter if the sensor is in the system 

tee/water or in different buffer solutions, then please refer to 

Section 2B

 in this 

guide. 

 

o

  If the mA value differs from the from the chart above, please perform a One point 

or Two Point calibration in accordance with the controller manual. 

 

 

mA 

pH 

12 

20 

14 

Содержание W100

Страница 1: ...ads Low or High Versus a Calibrated Handheld Meter Cannot Calibrate Section 4 Electrode Fault Section 5 pH Reading is Unstable Note pH electrodes are like batteries and their output voltage will chang...

Страница 2: ...ich means it wires into the controller analog input terminals o The WEL Transmitter Housing only works with the W600 and W900 controllers not with the W100 controller You can determine which configura...

Страница 3: ...ill depend upon the coating as well as the materials of construction of the electrode Do not use a solvent that will attack the electrode Oily coatings should be removed with a mild detergent or isopr...

Страница 4: ...ith the WEL PH housing wired into the electrode input terminals in the controller and the electrode threaded into the housing the reading should be the pH value of the solution as verified by a second...

Страница 5: ...t is programmed as pH and the following configurations are in place With nothing connected to the analog input terminals in the controller the reading should be about 0 mV 7 pH With just the WEL Trans...

Страница 6: ...00 for Walchem pH electrodes Temperature element Some electrodes do not have ATC If you are not using ATC in the Inputs menu Temperature Settings scroll to Element and select No Element And whatever t...

Страница 7: ...ctrode Input menu look at the pH Raw Value and the Gain Value What is the calibration range that you are allowed to go to o The controller shows us a current pH reading and a raw pH reading o This raw...

Страница 8: ...rect using a multimeter please check the mA signal coming from the sensor and into the controller as follows Place the WEL Transmitter Housing plus Electrode in the system tee water or place it in a b...

Страница 9: ...condition with stop control of any output using the electrode Possible Cause Corrective Action Electrode wires shorted Disconnect short Faulty electrode Replace electrode Faulty controller Replace or...

Страница 10: ...ater does the reading stay stable If the reading does not stay stable this can indicate a ground loop A ground loop could cause readings to be stuck at a high or low value Or there is some electrical...

Отзывы: