background image

CAUTION: There are live circuits inside the controller even when the power switch is in the 

OFF position! Servicing and troubleshooting the controller must be performed by Qualified 

Service Personnel.

 

 

 

Section 2 (A): 

WEL-PH Housing 

+  Electrode Reading is Stuck on one Value

 

 

Step 1: 

 

The following are normal (expected) readings when the controller electrode input is programmed as pH, 

and the following configurations are in place:

 

 

  With nothing connected to the electrode input terminals in the controller, the reading should 

be about 0 mV (7 pH). 

 

  With just the WEL-PH housing wired into the electrode input terminals in the controller (but no 

electrode installed), the reading should float (vary low to high to low to high, etc.). 

 

  With the WEL-PH housing wired into the electrode input terminals in the controller, and the 

electrode threaded into the housing, the reading should be the pH value of the solution, as 

verified by a secondary means, such as a handheld pH meter. 

 

Step 2: 

 

If a controller’s electrode input is programmed as pH, and the controller has a WEL-PH housing wired 

into the correct electrode input terminals (with the electrode threaded into the housing), and the pH 

reading is stuck on some incorrect pH value, please check the following: 

 

  There could be an electrical short between controller input terminals IN+ and IN- 

  Either the electrode wires, or electrode cable wires, are contacting each other when they 

normally should not be. 

 

  The glass on the end of the electrode could be broken or compromised.   

 

  There is an open circuit between controller input terminals IN+ and IN- 

  This could mean the electrode/electrode cable has broken wires.

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Содержание W100

Страница 1: ...ads Low or High Versus a Calibrated Handheld Meter Cannot Calibrate Section 4 Electrode Fault Section 5 pH Reading is Unstable Note pH electrodes are like batteries and their output voltage will chang...

Страница 2: ...ich means it wires into the controller analog input terminals o The WEL Transmitter Housing only works with the W600 and W900 controllers not with the W100 controller You can determine which configura...

Страница 3: ...ill depend upon the coating as well as the materials of construction of the electrode Do not use a solvent that will attack the electrode Oily coatings should be removed with a mild detergent or isopr...

Страница 4: ...ith the WEL PH housing wired into the electrode input terminals in the controller and the electrode threaded into the housing the reading should be the pH value of the solution as verified by a second...

Страница 5: ...t is programmed as pH and the following configurations are in place With nothing connected to the analog input terminals in the controller the reading should be about 0 mV 7 pH With just the WEL Trans...

Страница 6: ...00 for Walchem pH electrodes Temperature element Some electrodes do not have ATC If you are not using ATC in the Inputs menu Temperature Settings scroll to Element and select No Element And whatever t...

Страница 7: ...ctrode Input menu look at the pH Raw Value and the Gain Value What is the calibration range that you are allowed to go to o The controller shows us a current pH reading and a raw pH reading o This raw...

Страница 8: ...rect using a multimeter please check the mA signal coming from the sensor and into the controller as follows Place the WEL Transmitter Housing plus Electrode in the system tee water or place it in a b...

Страница 9: ...condition with stop control of any output using the electrode Possible Cause Corrective Action Electrode wires shorted Disconnect short Faulty electrode Replace electrode Faulty controller Replace or...

Страница 10: ...ater does the reading stay stable If the reading does not stay stable this can indicate a ground loop A ground loop could cause readings to be stuck at a high or low value Or there is some electrical...

Отзывы: