Additional Considerations
Do Not install vent terminal under any patio or deck.
To help prevent moisture from freezing on walls and under
eaves, do not locate vent terminal on the side of a building
with prevailing winter winds.
To help prevent water lines from freezing do not locate vent
terminal on the side of a building with prevailing winter
winds.
Do Not terminate vent directly on brick or masonry surfaces.
A rust-resistant sheet metal backing plate
(1 x 1 foot) (30 x 30 cm) is recommended behind vent. (See
Figure.)
Do Not locate vent terminal too close to shrubbery, as flue
gasses may damage them.
Caulk all cracks, seams and joints within six (6) feet (1.8 m)
of vent terminal.
Caulk around thimble face plate for weather tight seal.
All painted surfaces should be primed to lessen the chance of
physical damage. Painted surfaces will require maintenance.
Insulate vent pipe of water heaters exposed to cold
conditions (attics, crawl spaces, etc.) with inflammable
material to help prevent moisture from accumulating in vent
pipe. The insulation should be rated for the temperature and
should not contain substances that corrode the vent pipe.
Do Not extend exposed vent pipe of water heaters outside of
building.
Guard vent against accidental contact with people and pets.
WARNING
:
Moisture in the flue gas will condense as it
leaves the vent terminal. In cold weather this condensate can
freeze on the exterior wall, under the eaves and on
surrounding objects. Some discoloration to the exterior of
the building is to be expected. However, improper location
or installation can result in severe damage to the structure
or exterior finish of the building
Inside
Corner
Caulk
6’ (1.8 m)
Caulk Zone
If soffit vent is too close,
block off and install new
vent at another location.
Caulk
Caulk
Rising moisture will
collect under eaves.
6’
4’
1 ft. sq. (30 x 30 cm) sheet metal plate on
brick or masonry surface, recommended.
(1.8 m)
6’ (1.8 m)
Caulk
zone or to edge of window
etc.,starting within 6’ (1.8 m).
RTV silicone caulk
(1.2 m)
12
Installing the water heater.
Vent Kit Information
(Kits sold separately.)
Vertical Termination
Adapter
Faceplate
Air Intake Tee -
Heat Fab
Air Intake Tee - Pro-
Tech or Z-Flex
Horizontal
Termination
Adapter
4”/7” Concentric
Pipe
Vertical Outlet
Termination
Self Tapping Screw
Contact the service department on the page 36 of this manual for kit part number information
Horizontal Heat Fab
Qty
Vertical Heat Fab
Qty
Horizontal Pro Tech
Qty
Vertical Pro Tech
Qty
12” x 12” Faceplate
12” Length - 4”/7”
Concentric Pipe
Horizontal Termination
Adapter
Air Intake Tee-Heat
Fab
Self Tapping Screws
2
1
1
1
8
36” Length - 4”/7”
Concentric Pipe
Vertical Termination
Adapter
Air Intake Tee-Heat Fab
Self Tapping Screws
Vertical Outlet
Termination
1
1
1
8
1
12” x 12” Faceplate
12” Length - 4”/7”
Concentric Pipe
Horizontal Termination
Adapter
Air Intake Tee-Pro Tech
Self Tapping Screws
2
1
1
1
8
36” Length - 4”/7”
Concentric Pipe
Vertical Termination
Adapter
Air Intake Tee-Pro Tech
Self Tapping Screws
Vertical Outlet
Termination
1
1
1
8
1
WARNING
:
For multiple unit installation, a minimum
distance between vent terminations must be maintained to
prevent recirculation of vent gases. Maintain a center-to-
center distance between vent terminations of 19 inches (48
cm) for two unit installation. Maintain a center-to-center
distance between vent terminations of 21 inches (53 cm) for
three or more unit installation.