![WAGO WAGO-I/O-SYSTEM 750 750-481/003-000 Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/wago/wago-i-o-system-750-750-481-003-000/wago-i-o-system-750-750-481-003-000_manual_3312766037.webp)
WAGO-I/O-SYSTEM 750
Process Image
37
750-481/003-000 2AI RTD Ex i
6.4
Configuration for Potentiometer Measuring
Potentiometer measuring is only possible using 3-wire devices.
When a potentiometer is used for measurement, the relative position of the
connected potentiometer is expressed in percent:
.
)
(R
R
*
%
100
)
(
S
Slider
G
Total
R
R
x
Two settings are available, one for potentiometers with total resistance up to 1.2
k
Ω
and one for potentiometers up to 5.0 k
Ω
.
The resolution is 1 digit per 0.0049 %. The increment is determined by the total
resistance RG of the potentiometer. As RG is measured with 16 bit resolution,
using RG = 200
Ω
in the measuring range of 5.0 k
Ω
, the increment is given by
%
04
,
0
200
*
65536
0
,
5
*
%
100
k
d
Table: 17 Process Image Configuration for potentiometer measuring
Numercial value
Percentage
%
binary
hex.
dec.
Status-
byte
hex.
LED
Error
AI 1,2
0.0 '0000.0000.0000.0000'
0x0000 0 0x00
off
20.0 '0000.0111.1101.0000'
0x1000
4096
0x00
off
40.0 0000.1111.1010.0000'
0x2000
8192
0x00
off
60.0 '0001.0111.0111.0000'
0x3000
12288
0x00
off
80.0 '0001.1111.0100.0000'
0x4000
16384
0x00
off
100.0 '0010.0111.0001.0000'
0x4FFF
20479
0x00
off
>ca.100.0 '0010.0111.0001.0000'
0x4FFF 20479 0x40 on
Values marked with "ca." are not calibrated.
Po
s: 68 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1
Manual
1.1.0