![WAGO WAGO-I/O-SYSTEM 750 750-481/003-000 Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/wago/wago-i-o-system-750-750-481-003-000/wago-i-o-system-750-750-481-003-000_manual_3312766033.webp)
WAGO-I/O-SYSTEM 750
Process Image
33
750-481/003-000 2AI RTD Ex i
Table: 12 Process Image Configuration for Pt 100, Pt 200, Pt 500 and Pt 1000, with broken wire
diagn.
Numercial value
1)
Temperature
°C
binary
hex.
dec.
Status-
byte
hex.
LED
Error
AI 1, 2
<-200.0 '1000.0000.0000.0001'
0x8001
-32767
0x41
on
-200.0 '1111.1000.0011.0000'
0xF830
-2000
0x00
off
-100.0 '1111.1100.0001.1000'
0xFC18
-1000
0x00
off
0.0 '0000.0000.0000.0000'
0x0000 0
0x00
off
100.0 '0000.0011.1110.1000'
0x03E8
1000
0x00
off
200.0 '0000.0111.1101.0000'
0x07D0
2000
0x00
off
500.0 '0001.0011.1000.1000'
0x1388
5000
0x00
off
750.0 '0001.1101.0100.1100'
0x1D4C
7500
0x00
off
800.0 '0001.1111.0100.0000'
0x1F40
8000
0x00
off
850.0 '0010.0001.0011.0100'
0x2134
8500
0x00
off
>850.0 '0010.0001.0011.0100'
0x2134 8500
0x42
on
Broken wire
against RL
'0010.0001.0011.0100'
0x2134 8500 0x42 on
1) Temperature values below 0 °C are represented in two’s complement binary form.
The measured value can exceed the range from –2000 to 8500 until the limitation
applies.
Manual