765-4501/0100-0000
Planning
Product manual | Version: 1.1.0
61
8PORT IOL-A FLD EI DC 24V 2.0A
6.2.4 Power Supply Examples
The product can be powered alone with its operating voltage or form part of a power sup-
ply group along with multiple products.
Power supply groups of multiple products can be formed in two ways:
1. Via the PWR OUT connection:
One or more additional products can be powered via the PWR OUT (X32) power sup-
ply output and then form a power supply group together with the product.
2. Through an IO-Link hub*:
One product forms a common power supply group with IO-Link hubs
(765-170x/0200-0000) connected via IO-Link.
* Only applies to modules with integrated IO-Link master ports
In what follows, we present one example for the 765-4204/0100-000 product with four IO-
Link inputs/outputs for each of the following:
• Individual power supply
• Power supply group via PWR OUT connection (with calculation of the permissible cur-
rent feedthrough)
• Power supply group with IO-Link hubs
These examples assume that the IO-Link inputs/outputs are configured as digital outputs.
Example of Individual Power Supply
This example considers a single 765-4501/0100-0000 module where no additional de-
vices are powered through its PWR OUT connection (X32).
Figure 4: Connection Example for 765-4501/0100-0000 Module with Individual Power Supply
One IO-Link class A device with max. current consumption of 1 A is connected to each of
ports X01 through X08 of the module. The module’s current consumption is 0.2 A.