2787-2147
Configuration
Product manual | Version: 1.0.0
43
Power Supply Pro 2
Table 51: Dialog: Settings – DC Output
Section
Parameter
Description
General
Output On
If this box is checked, the DC output is activated.
Output voltage
Here you can enter the output voltage (unit: mV) that is
present when the output is active.
“active droop” parallel mode
If this box is checked, the “Active Droop” parallel
switching mode is active. In this mode, a smooth char-
acteristic curve ensures better current sharing for par-
allel operation of power supplies.
Enable switching the DC out-
put on and off via cyclic
process data
If this box is checked, the DC output can be switched
on and off via cyclic process data.
Overload behavior
Constant current
If this box is checked, the “Constant Current” overload
behavior is enabled. You can find more information in
section
8
.
Constant current (latching
mode)
If this box is checked, the “Constant Current with
Latching Shutdown” overload behavior is enabled. You
can find more information in section
8
.
Hiccup mode
If this box is checked, the “Hiccup Mode” overload be-
havior is enabled. You can find more information in
section
8
.
Electronic circuit breaker
If this box is checked, the “Electronic Circuit Breaker”
overload behavior is enabled. In the event of overload,
the power supply works like an electronic circuit
breaker and switches the energy off with a time delay.
You can find more information in section
8
.
Trip current
Here you can enter the trip current (unit: mA) for the
“Electronic Circuit Breaker” overload behavior.
Trip delay
Here you can enter the trip delay (unit: ms) for the
“Electronic Circuit Breaker” overload behavior.
Latching after thermal over-
load
If this box is checked, the “Latching Shutdown on
Thermal Overload” overload behavior is enabled. After
an overtemperature event, the power supply no longer
automatically switches the output back on as soon as it
has cooled off. To switch the output back on, manual
intervention is necessary. The following options are
available for this:
•
Communication interface
•
Buttons
•
Digital input
You can find more information in section
8
Shutdown on Thermal Overload [
PowerBoost
If this box is checked, the “Power Boost” overload be-
havior is enabled. The power supply offers up to
150 % of the output power for 5 s. You can find more
information in section
8
.
TopBoost
If this box is checked, the “Top Boost” overload behav-
ior is enabled. The power supply provides up to 600 %
more output power for 15 s. You can find more infor-
mation in section
8